Plan Review Notes
Plan Review Notes For Permit 05121091
Permit Number 05121091
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-17 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2004 FMC 403.3.
  
 2.INDICATE OUTSIDE AIR DUCT SIZE,
 MATERIAL & LAYOUT.
  
 3.PLAN SHEET AC-1 INDICATES FLEX DUCT
 THORUGH A RATED WALL WITH A FIRE DAMPER.
 PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS
 & FLEX CONNECTORS SHALL NOT PASS THROUGH
 ANY FIRE RESISTANCE RATED ASSEMBLY.
  
 4.PLAN SHEET AC-2 HVAC DESIGN
 REQUIREMENT CHART INDICATES FIRE DAMPERS
 & DUCT SMOKE DETECTORS ARE NOT REQUIRED.
 THIS IS INCORRECT.FIRE DAMPERS ARE
 REQUIRED THROUGH FIRE RATED PARTITIONS.
 PLAN SHEET A-1, FIRST FLOOR ACCORDING TO
 THE PARTITION LEGEND THE FOLLOWING AREAS
 ARE INDICATED AS FIRE RATED PARTITIONS:
 1) BETWEEN THE ART STUDIO & COMMON AREA
 2) BATHROOM AREAS AND THE COMMON AREA
 3) KITCHEN AREA TO THE CONFERENCE ROOM &
 THE CORRIDOR.
  
 PLEASE NOTE, FIRE DAMPERS ARE NOT
 REQUIRED SHOULD PENETRATION MEET ALL THE
 REQUIREMENTS OF 2004 FMC 607.5.3
 EXCEPTION #2 ITEMS 2.1 THROUGH 2.6,
 PLEASE ANNOTATE ON THE PLAN.
  
 5. DUCT SMOKE DETECTORS REQUIRED IN
 SYSTEMS THAT HAVE THE DESIGN CAPACITY TO
 PRODUCE GREATER THAN 2,000 CFM.SYSTEM
 4 HAS THIS CAPACITY.PLEASE INDICATE
 DUCT SMOKE DETECTOR ON THE PLAN IN
 ACCORDANCE WITH 2004 FMC 606.2.1.
  
 6.PLAN SHEET AC-2 DETAIL FOR THE ROOF
 CURB.IS THIS FOR THE CONDENSER UNITS?
 PROVIDE DETAIL OF HOW THE UNITS WILL BE
 ATTACHED TO THE CURB.TYPICALLY
 CONDENSER UNITS ARE MOUNTED ON STANDS IN
 ACCORDANCE WITH 2004 FBC TABLE 1509.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.