Date |
Text |
2006-02-17 00:00:00 | DENIED: |
| 1.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS PER 2004 FMC 403.3. |
| |
| 2.INDICATE OUTSIDE AIR DUCT SIZE, |
| MATERIAL & LAYOUT. |
| |
| 3.PLAN SHEET AC-1 INDICATES FLEX DUCT |
| THORUGH A RATED WALL WITH A FIRE DAMPER. |
| PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS |
| & FLEX CONNECTORS SHALL NOT PASS THROUGH |
| ANY FIRE RESISTANCE RATED ASSEMBLY. |
| |
| 4.PLAN SHEET AC-2 HVAC DESIGN |
| REQUIREMENT CHART INDICATES FIRE DAMPERS |
| & DUCT SMOKE DETECTORS ARE NOT REQUIRED. |
| THIS IS INCORRECT.FIRE DAMPERS ARE |
| REQUIRED THROUGH FIRE RATED PARTITIONS. |
| PLAN SHEET A-1, FIRST FLOOR ACCORDING TO |
| THE PARTITION LEGEND THE FOLLOWING AREAS |
| ARE INDICATED AS FIRE RATED PARTITIONS: |
| 1) BETWEEN THE ART STUDIO & COMMON AREA |
| 2) BATHROOM AREAS AND THE COMMON AREA |
| 3) KITCHEN AREA TO THE CONFERENCE ROOM & |
| THE CORRIDOR. |
| |
| PLEASE NOTE, FIRE DAMPERS ARE NOT |
| REQUIRED SHOULD PENETRATION MEET ALL THE |
| REQUIREMENTS OF 2004 FMC 607.5.3 |
| EXCEPTION #2 ITEMS 2.1 THROUGH 2.6, |
| PLEASE ANNOTATE ON THE PLAN. |
| |
| 5. DUCT SMOKE DETECTORS REQUIRED IN |
| SYSTEMS THAT HAVE THE DESIGN CAPACITY TO |
| PRODUCE GREATER THAN 2,000 CFM.SYSTEM |
| 4 HAS THIS CAPACITY.PLEASE INDICATE |
| DUCT SMOKE DETECTOR ON THE PLAN IN |
| ACCORDANCE WITH 2004 FMC 606.2.1. |
| |
| 6.PLAN SHEET AC-2 DETAIL FOR THE ROOF |
| CURB.IS THIS FOR THE CONDENSER UNITS? |
| PROVIDE DETAIL OF HOW THE UNITS WILL BE |
| ATTACHED TO THE CURB.TYPICALLY |
| CONDENSER UNITS ARE MOUNTED ON STANDS IN |
| ACCORDANCE WITH 2004 FBC TABLE 1509.7. |
| |