2006-02-15 00:00:00 | ******DENIED****** |
| |
| 1) BUILDING SHALL MEET ALL REQUIREMENTS |
| FOR MULTIPLE OCCUPANCIES. |
| |
| 2) PLEASE SEE NFPA 101, 2003 EDITION |
| SEC. 24.1.2.2 THAT PROHIBITS THE "SOLE |
| MEANS OF EGRESS OF DWELLING UNITS TO |
| PASS THROUGH A NON-RESIDENTIAL OCCUPANCY |
| IN SAME BUILDING". |
| |
| 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENT FOR HANDRAILS AND GUARDS. |
| |
| 4) IT APPEARS THAT THE DOOR TO THE |
| ELEVATOR MAY OBSTRUCT THE DOOR TO APT. |
| #1. |
| |
| 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| REQUIRED. |
| |
| 6) PLEASE PROVIDE INTERIOR FINISH |
| CLASSIFICATION FOR WALLS AND CEILINGS |
| THAT SHALL BE CLASS A,B OR C. |
| |
| 7) IN ADDITION TO PRIMARY ESCAPE, |
| DWELLING UNITS TO COMPLY WITH |
| REQUIREMENT FOR SECONDARY ESCAPE. |
| |
| 8) INTERIOR STAIRWAYS TOO BE PROVIDED |
| WITH ARTIFICAL LIGHTING. |
| |
| 9) SMOKE ALARMS ARE REQUIRED TO BE |
| INSTALLED INSIDE AND OUTSIDE SLEEPING |
| ROOMS. |
| |
| 10) AN ADDRESS IS REQUIRED ON BUILDING |
| THAT SHALL BE A MINIMUM OF 6" IN HEIGHT |
| AND CONTRASTING TO THE BACKGROUND. |
| |
| 11) WORK TO COMPLY WITH CURRENT BUILDING |
| CODES, AND NFPA 101, 2003 EDITION. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLANS REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |