2006-02-15 00:00:00******DENIED******
  
 1) BUILDING SHALL MEET ALL REQUIREMENTS
 FOR MULTIPLE OCCUPANCIES.
  
 2) PLEASE SEE NFPA 101, 2003 EDITION
 SEC. 24.1.2.2 THAT PROHIBITS THE "SOLE
 MEANS OF EGRESS OF DWELLING UNITS TO
 PASS THROUGH A NON-RESIDENTIAL OCCUPANCY
 IN SAME BUILDING".
  
 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 4) IT APPEARS THAT THE DOOR TO THE
 ELEVATOR MAY OBSTRUCT THE DOOR TO APT.
 #1.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS
 THAT SHALL BE CLASS A,B OR C.
  
 7) IN ADDITION TO PRIMARY ESCAPE,
 DWELLING UNITS TO COMPLY WITH
 REQUIREMENT FOR SECONDARY ESCAPE.
  
 8) INTERIOR STAIRWAYS TOO BE PROVIDED
 WITH ARTIFICAL LIGHTING.
  
 9) SMOKE ALARMS ARE REQUIRED TO BE
 INSTALLED INSIDE AND OUTSIDE SLEEPING
 ROOMS.
  
 10) AN ADDRESS IS REQUIRED ON BUILDING
 THAT SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING TO THE BACKGROUND.
  
 11) WORK TO COMPLY WITH CURRENT BUILDING
 CODES, AND NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  