2006-02-07 00:00:00 | ************ UNSAT **************** |
| |
| *** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| FOR A COMPLETE REVIEW FOR CODE |
| COMPLIANCE AT THIS TIME. |
| PLEASE SEE NOTES BELOW. |
| |
| 1)NOTE: PLEASE BE SURE TO COMPLETE ALL |
| CIRCUITING ON PLANS AND CORRELATE WITH |
| THE SUBMITTED PANEL SCHEDULES. |
| PLEASE SEE THERE ARE MANY DEVICES WHICH |
| DO NOT INDICATE ANY CIRCUITS AND MANY |
| CIRCUITS WHICH DO NOT CORRELATE WITH THE |
| SUBMITTED SCHEDULES. |
| |
| 2)NOTE: PLEASE BE SURE PLANS REFERENCE |
| THE CURRENT CODES IN EFFECT AS LISTED. |
| NFPA-101 2003, NFPA-72 2002, NFPA-70, |
| 2002. |
| |
| 3)NOTE: PLEASE SEE THERE ARE LOCATIONS |
| ON PLANS WHICH MAKE REFERENCE TO "FOUR |
| APTS"?? PLEASE DECIDE THE USE, AND |
| ADJUST PLANS AS NEED. PLEASE SEE OTHER |
| COMMENTS WITH RESPECT TO FEEDERS/ LOAD CALCULATIONS |
| ETC. |
| ** PLEASE KNOW, IF INDEED THERE IS GOING |
| TO FOUR APT UNITS, PLEASE SEE THE |
| FOLLOWING COMMENT. |
| |
| 4)NOTE: IF 4 APTS? |
| PLEASE PROVIDE COMPLETE HEIGHT/DEVICE |
| LOCATIONS AS REQUIRED UNDER FAIR HOUSING |
| ACT REGULATIONS 24 CFR100.205 |
| |
| 5)NOTE:PLEASE SEE NO MAIN OR OCP IS |
| SHOWN ON RISER FOR SERVICE. 230.70, |
| 215.5 |
| |
| 6)NOTE: PLEASE SEE NO OCP IS SHOWN FOR |
| MAINS/FEEDS TO EACH PANEL. PLEASE SEE |
| RISER SHOWS FEEDERS "TYPICAL OF 4"?? |
| PLEASE INDICATE THE OCP FOR EACH, |
| 240.4,310.16, 230.70 ETC. |
| |
| 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR TO EACH PANEL. |
| 250.110,250.122 ETC. |
| |
| 8)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| SYSTEM MENTIONS TO ATTACHED TO FOOTER |
| STEEL? PLEASE KNOW,IN AN EXISTING |
| BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE |
| TO THE STRUCTUAL |
| INTEGRITY OF THE EXISTING STEEL/FOOTER. |
| PLEASE KNOW HOWEVER THIS IS PERMITTED, |
| AND IF SHOWN ON RISER , IT WILL BE |
| REQUIRED. |
| 250.50 |
| |
| 9)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| GROUNDING ELECTRODE CONDUCTOR AS THIS IS |
| CURRENTLY SHOWN AS A "6/0"? PLEASE KNOW, |
| THIS IS NOT A RECOGNIZED AMERICAN WIRE |
| GAUGE STANDARD. |
| PLEASE ADJUST AS NEED BASED ON SERVICE |
| ENTRANCE CONDUCTORS WHICH WILL BE BASED |
| ON LOAD CALCULATIONS."NOTE: PLEASE SEE |
| COMMENTS BELOW FOR LOAD CALCS AS SEC'S |
| MAY CHANGE. |
| 215.5 |
| |
| 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| ** PLEASE SEE NOTE #20 ON NOTES WHICH |
| MENTIONS THE USE OF FUSES, HOWEVER NONE |
| ARE SHOWN? |
| |
| 11)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| PLEASE SEE THIS IS A MIXED USE. |
| PLEASE SEE THE RESIDENTIAL LOAD |
| CALCULATIONS ARE BEING USED FOR THE |
| COMMERICAL SPACE AND ONCE AGAIN THE LOAD CALCULATIONS |
| MAKE REFERENCE TO THE |
| INSTALLATION OF"4-APTS" AND DERATING |
| IS TAKEN FROM TABLE 220.32?? |
| PLEASE ADJUST ALL LOAD CALCULATIONS AND |
| SEEOTHER COMMENTS WHICH WILL AFFECT |
| LOADS AS SHOWN. |
| |
| 12)NOTE: PLEASE SHOW ALL PANEL LOCATIONS |
| FOR VERIFICATION OF CODE COMPLIANCE. |
| 110.26,240.24 ETC. |
| |
| 13)NOTE: PLEASE CORRELATE PANEL |
| SCHEDULES AND RISER, PANELS SHOWS TWO |
| PANEL "A"'S? (MISPRINT) |
| 215.5 |
| |
| 14)NOTE: PLEASE CORRELATE ALL LOAD FOR |
| A/C SYSTEMS, AS MECHANICAL PLANS |
| INDICATE 10KW UNITS, LOAD CALCUALTIONS |
| INDICATE BOTH 9KW LOAD AND 5KW LOAD AND |
| PANEL SCHEDULES INDICATE 5KW HEAT FOR |
| ALL?? |
| PLEASE ADJUST LOAD CALCS ETC 215.5 |
| |
| 15)NOTE: PLEASE SEE 424.3B WHICH |
| REQUIRES ALL MIN OCP FOR AHU'S HEAT TO |
| BE SIZED AT A MIN OF 125%. |
| PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 |
| AWG ON 5KW UNITS. |
| ** PLEASE KNOW, THERE IS ALSO A MAX OCP. |
| |
| 16)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS |
| WHICH DO NOT SEEM TO |
| INDICATE THE REQUIRED NEUTRAL CONDUCTOR |
| PER 250.140 |
| |
| 17)NOTE: PLEASE VERIFY ALL CONDUCTORS |
| LISTED ON PANEL SCHEDULE(S). |
| PLEASE SEE MANY ARE SHOWING 15A OCP ON |
| #12 AWG. PLEASE ALSO SEE NOTES WHICH |
| MENTIONS THE MIN SIZE AWG SHALL BE #12? |
| PLEAS KNOW, #12 IS PERMITTED ON 15A OCP. |
| |
| 18)NOTE: PLEASE SEE AN ELEVATOR IS SHOWN |
| ON PLANS, HOWEVER THERE IS NO INDICATION |
| ON ANY PLANS OF THIS EQUIPMENT?? |
| 215.5 |
| |
| 19)NOTE: PLEASE SEE 620.23 WHICH |
| REQUIRES A DEDICATED BRANCH CIRCUIT FOR |
| PIT LTS/GFI RECEPT. |
| |
| 20)NOTE: PLEASE ALSO SEE 620.24 WHICH |
| REQUIRES A DEDICATED BRANCH CIRCUIT FOR |
| ANY ELEVATOR EQUIPMENT ROOM /AREA FOR |
| SERVICE. |
| |
| 21)NOTE: PLEASE KNOW, ANEMERGENCY |
| BATTERY BACK UP TYPE LT FIXTURE WILL BE |
| REQUIRED AT ANY ELEVATOR EQUIPMENT |
| LOCATION.700.16,LS101 7.8/7.9 |
| |
| 22)NOTE: PLEASE SEE WHAT APPEARS TO BE |
| OUTSIDE LTS ON 2ND FLOOR LEVEL WHICH |
| INDICATES THESE LTS TO BE CIRCUIT B-8 |
| AND A-8, HOWEVER ALSO INDICATE THESE TO |
| BE ON A TC (TIMECLOCK)? PLEASE CORRELATE |
| THESE IF INDEED THEY ARE TO BE ON WITH |
| THE FIRST FLR OUTSIDE TC CIRCUIT? |
| |
| 23)NOTE: PLEASE SEE THE MISSING REQUIRED |
| DEDICATED SIGN CIRCUIT AS PER 600.5 |
| |
| 24)NOTE: PLEASE SEE THE NEW FBC 2004, |
| CHAPTER 13 (ENERGY CODE) FOR EXPANDED |
| REQUIMENTS FOR COMMERCIAL BLDGS. |
| 13-413,13-415 ETC. |
| PLEASE ADJUST AS NEEDED. |
| |
| 25)NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 |
| WHICH REQUIRES A MIN OF BATTERY BACK UP |
| EM LTS FOR MEANS OF EGRESS TO THE PUBLIC RIGHT-OF-WAY. |
| PLEASE SEE FIRE REVIEW |
| COMMENTS ALSO FOR THIS. |
| PLEASE SEE 7.8.1.3 WHICH NOW REQUIRES A |
| MIN OF 10 FT CANDLES (108 LUX) FOR ALL |
| LEVELS OF STAIRS DURING NORMAL POWERE |
| AND THE PERMITTED DE-RATINGS ALLOWED BY |
| 7.9.2.2 UNDER EMERGENCY CONDITIONS. |
| TO 10.8 LUX. |
| |
| 26)NOTE: PLEASE PROVIDE A FIXTURE |
| SCHEDULE AND CORRELATE WITH THE PLANS. |
| PLEASE SEE NOTES #24 AND #25 FOR TYPES |
| OF FIXTURES. |
| |
| 27)NOTE: PLEASE SEE 700.12E FOR |
| CIRCUITING OF ALL EM/EXT LTS. THESE |
| SHALL BE CIRCUITED TO THE LOCAL BRANCH |
| CIRCUIT SUPPLYINGLIGHTING IN THAT |
| AREA. |
| |
| 28)NOTE: PLEASE SEE 210.8A6 WHICH |
| REQUIES ALL RECEPTS SERVIING KITCHEN |
| COUNTERSPACES TO BE GFI/GFI PROTECTED. |
| |
| 29)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS |
| IN OTHER THAN DWELLING UNITS. |
| |
| 30)NOTE: PLEASE SEE MISSING THE REQUIRED |
| DEDICATED BATH CIRCUITS PER |
| 210.52D,210.11C3. SHALL BE #12 AND 20. |
| PLEASE SEE #14, 15A SHOWN FOR BOTH APTS |
| UPSTAIRS. |
| ** PLEASE SEE WHAT APPEARS TO BE APT |
| WHICH SHOWS A CIRCUIT #8 FOR BATH GFI'S. |
| PLEASE KNOW, THE DEDICATED BATH CIRCUIT |
| MAY NOT FEED ANY OTHER AREAS. |
| |
| 31)NOTE: PLEASE SEE THE CIRCUIT |
| INDICATED ON PLANS FOR WHAT APPEARS TO |
| BE A WASHER LOCATION IS SHOWN AS A SPARE |
| ON PANEL SCHEDULE?? |
| PLEASE SEE 210.11C2, 220.16B WHICH |
| REQUIRES A LAUNDRY CIRCUIT AND WASHER |
| CIRCUIT TO BE A MIN 1500 VA , 20A AND |
| #12 AWG. |
| PLEASE ADJUST LOAD CALCUALTIONS ETC. |
| |
| 32)NOTE: PLEASE SEE MISSING SMOKE |
| DETECTORS AS REQUIRED UNDER NFPA-72 |
| 11.5.1.1. |
| MISSING INSIDE AND OUTSIDE ALL SLEEPING |
| RMS. |
| PLEASE ALSO SEE 11.8.3.5 FOR LOCATIONS |
| OF SD'S WHICH ARE REQUIRED TO BE A MIN |
| OF 3' FROM KITCHEN AND BATH DOORS AND |
| SHALL BE A MIN OF 20' FROM ANY COOKING |
| APPLIANCES. (COOKING APPLIANCES WITH |
| EXCEPTIONS). |
| PLEASE ALSO SEE NOTE ON PLANS WHICH |
| MENTIONS SD'S ARE TO BE WIRED AHEAD OF |
| THE SWITCHES ON EITHER BATH OR KITCHEN |
| LIGHTING CIRCUIT, PLEASE SEE THIS IS OK, |
| HOWEVER ARC FAULT PROTECTION WILL THEN |
| BE REQUIRED FOR THOSE LIGHTING CIRCUITS, |
| PLEASE SEE BATH LTS ARE ALSO WIRED TO BE |
| A DEDICATED CIRCUIT FOR EACH BATH RM. |
| ** PLEASE SEE COMMENT FOR REQUIRED ARC |
| FAULT. |
| |
| 33)NOTE: PLEASE LIST ALL THE REQUIRED |
| ARC FAULT PROTECTED CIRCUITS AS REQUIRED |
| PER 2002 NEC 210.12B |
| |
| 34)NOTE: PLEASE SEE A MIN OF TWO SMALL |
| APPLIANCE CIRCUITS ARE SHOWN, HOWEVER |
| ONLY ONE IS SHOWN FOR KITCHEN. PLEASE |
| ADJUST CIRCUITING AS THE MIN OF TWO SM |
| APPL CIRCUITS SHALL BE IN KITCHEN. 210.11C1,220.16A, |
| 215.5 ETC |
| |
| 35)NOTE: PLEASE SEE ELECTRICAL PLANS ARE |
| MISSING ALL A?C SYSTEMS?? AHU'S, CU'S. |
| PLEASE SHOW ALL DISCONNECTS AS REQUIRED |
| PER 440.11, 110.26 |
| |
| 36)NOTE: PLEASE SEE 210.63 FOR THE |
| SERVICE RECEPT REQUIRED. (GFI) 210.8A |
| |
| 37)NOTE: PLEASE SEE MANY CIRCUITS ON |
| PLANS MENTIONS "GEN LTS" GEN RECEPTS" |
| PLEASE LIST THESE TO BE SPECIFIC TO THE |
| AREAS IN WHICH THEY ARE FEEDING. |
| |
| 38)NOTE: PLEASE LABEL APTS ON PLANS AND |
| CORRELATE. PLEASE SEE WHAT APPEARS TO BE |
| APT "B". |
| |
| 39)NOTE: PLEASE VERIFY WHAT IS SHOWN AS |
| A QUAD RECEPT IN KITCHEN ON FIRST FLR |
| WHICH IS SHOWN AS 15AON PANEL |
| SCHEDULE? |
| PLEASE ALSO SEE PREVIOUS COMMENT WITH |
| RESPECT TO GFI PROTECTION. |
| |
| 40)NOTE: PLEASE SEE PLANS WHICH SHOWS A |
| CIRCUIT FOR WHAT IS LISTED ON PANEL |
| SCHEDULE AS BEING A MICROWAVE # 14, |
| HOWEVR NO DEVICE OR LOCATION IS SHOWN ON |
| PLANS. |
| |
| 41)NOTE: PLEASE SEE SWITCHES WHICH ARE |
| SHOWN WIRED TO A 3-WAY SYSTEM, HOWEVER |
| DO NOT INDICATE BEING S3. |
| PLEASE SEE REDLINED LOCAITONS. |
| |
| 42)NOTE:PLEASE SEE REDLINED MISSING |
| RECEPT PER 210.52, 2' OF WALL. |
| |
| 43)NOTE: PLEASE SHOW THE LOCATION OF THE |
| SERVICE ON PLANS/BLDG. |
| 230.70,240.24,110.26, ETC |
| |
| ** PLEASE KNOW, DUE TO PLANS NOT BEING |
| COMPLETE AND THE EXTENT OF COMMENTS, |
| PLEASE COMPLETE ALL OF THE ABOVE TO |
| ALLEAVIATE FUTHER COMMENTS ON THE |
| FOLLOWING REVIEW. |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| ONLY ONE COPY OF OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE TO GO OVER ANY COMMENTS OR |
| QUESTIONS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
2006-01-12 00:00:00 | SENT TO INCOMING AS BLDG IS MIXED USE |
| AND SHOULD BE ON COMMERCIAL BOARD. |