Plan Review Notes
Plan Review Notes For Permit 05121091
Permit Number 05121091
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00************ UNSAT ****************
  
 *** PLEASE KNOW, PLANS ARE NOT COMPLETE
 FOR A COMPLETE REVIEW FOR CODE
 COMPLIANCE AT THIS TIME.
 PLEASE SEE NOTES BELOW.
  
 1)NOTE: PLEASE BE SURE TO COMPLETE ALL
 CIRCUITING ON PLANS AND CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULES.
 PLEASE SEE THERE ARE MANY DEVICES WHICH
 DO NOT INDICATE ANY CIRCUITS AND MANY
 CIRCUITS WHICH DO NOT CORRELATE WITH THE
 SUBMITTED SCHEDULES.
  
 2)NOTE: PLEASE BE SURE PLANS REFERENCE
 THE CURRENT CODES IN EFFECT AS LISTED.
 NFPA-101 2003, NFPA-72 2002, NFPA-70,
 2002.
  
 3)NOTE: PLEASE SEE THERE ARE LOCATIONS
 ON PLANS WHICH MAKE REFERENCE TO "FOUR
 APTS"?? PLEASE DECIDE THE USE, AND
 ADJUST PLANS AS NEED. PLEASE SEE OTHER
 COMMENTS WITH RESPECT TO FEEDERS/ LOAD CALCULATIONS
 ETC.
 ** PLEASE KNOW, IF INDEED THERE IS GOING
 TO FOUR APT UNITS, PLEASE SEE THE
 FOLLOWING COMMENT.
  
 4)NOTE: IF 4 APTS?
 PLEASE PROVIDE COMPLETE HEIGHT/DEVICE
 LOCATIONS AS REQUIRED UNDER FAIR HOUSING
 ACT REGULATIONS 24 CFR100.205
  
 5)NOTE:PLEASE SEE NO MAIN OR OCP IS
 SHOWN ON RISER FOR SERVICE. 230.70,
 215.5
  
 6)NOTE: PLEASE SEE NO OCP IS SHOWN FOR
 MAINS/FEEDS TO EACH PANEL. PLEASE SEE
 RISER SHOWS FEEDERS "TYPICAL OF 4"??
 PLEASE INDICATE THE OCP FOR EACH,
 240.4,310.16, 230.70 ETC.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR TO EACH PANEL.
 250.110,250.122 ETC.
  
 8)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM MENTIONS TO ATTACHED TO FOOTER
 STEEL? PLEASE KNOW,IN AN EXISTING
 BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE
 TO THE STRUCTUAL
 INTEGRITY OF THE EXISTING STEEL/FOOTER.
 PLEASE KNOW HOWEVER THIS IS PERMITTED,
 AND IF SHOWN ON RISER , IT WILL BE
 REQUIRED.
 250.50
  
 9)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GROUNDING ELECTRODE CONDUCTOR AS THIS IS
 CURRENTLY SHOWN AS A "6/0"? PLEASE KNOW,
 THIS IS NOT A RECOGNIZED AMERICAN WIRE
 GAUGE STANDARD.
 PLEASE ADJUST AS NEED BASED ON SERVICE
 ENTRANCE CONDUCTORS WHICH WILL BE BASED
 ON LOAD CALCULATIONS."NOTE: PLEASE SEE
 COMMENTS BELOW FOR LOAD CALCS AS SEC'S
 MAY CHANGE.
 215.5
  
 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 ** PLEASE SEE NOTE #20 ON NOTES WHICH
 MENTIONS THE USE OF FUSES, HOWEVER NONE
 ARE SHOWN?
  
 11)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE THIS IS A MIXED USE.
 PLEASE SEE THE RESIDENTIAL LOAD
 CALCULATIONS ARE BEING USED FOR THE
 COMMERICAL SPACE AND ONCE AGAIN THE LOAD CALCULATIONS
 MAKE REFERENCE TO THE
 INSTALLATION OF"4-APTS" AND DERATING
 IS TAKEN FROM TABLE 220.32??
 PLEASE ADJUST ALL LOAD CALCULATIONS AND
 SEEOTHER COMMENTS WHICH WILL AFFECT
 LOADS AS SHOWN.
  
 12)NOTE: PLEASE SHOW ALL PANEL LOCATIONS
 FOR VERIFICATION OF CODE COMPLIANCE.
 110.26,240.24 ETC.
  
 13)NOTE: PLEASE CORRELATE PANEL
 SCHEDULES AND RISER, PANELS SHOWS TWO
 PANEL "A"'S? (MISPRINT)
 215.5
  
 14)NOTE: PLEASE CORRELATE ALL LOAD FOR
 A/C SYSTEMS, AS MECHANICAL PLANS
 INDICATE 10KW UNITS, LOAD CALCUALTIONS
 INDICATE BOTH 9KW LOAD AND 5KW LOAD AND
 PANEL SCHEDULES INDICATE 5KW HEAT FOR
 ALL??
 PLEASE ADJUST LOAD CALCS ETC 215.5
  
 15)NOTE: PLEASE SEE 424.3B WHICH
 REQUIRES ALL MIN OCP FOR AHU'S HEAT TO
 BE SIZED AT A MIN OF 125%.
 PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6
 AWG ON 5KW UNITS.
 ** PLEASE KNOW, THERE IS ALSO A MAX OCP.
  
 16)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS
 WHICH DO NOT SEEM TO
 INDICATE THE REQUIRED NEUTRAL CONDUCTOR
 PER 250.140
  
 17)NOTE: PLEASE VERIFY ALL CONDUCTORS
 LISTED ON PANEL SCHEDULE(S).
 PLEASE SEE MANY ARE SHOWING 15A OCP ON
 #12 AWG. PLEASE ALSO SEE NOTES WHICH
 MENTIONS THE MIN SIZE AWG SHALL BE #12?
 PLEAS KNOW, #12 IS PERMITTED ON 15A OCP.
  
 18)NOTE: PLEASE SEE AN ELEVATOR IS SHOWN
 ON PLANS, HOWEVER THERE IS NO INDICATION
 ON ANY PLANS OF THIS EQUIPMENT??
 215.5
  
 19)NOTE: PLEASE SEE 620.23 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 PIT LTS/GFI RECEPT.
  
 20)NOTE: PLEASE ALSO SEE 620.24 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 ANY ELEVATOR EQUIPMENT ROOM /AREA FOR
 SERVICE.
  
 21)NOTE: PLEASE KNOW, ANEMERGENCY
 BATTERY BACK UP TYPE LT FIXTURE WILL BE
 REQUIRED AT ANY ELEVATOR EQUIPMENT
 LOCATION.700.16,LS101 7.8/7.9
  
 22)NOTE: PLEASE SEE WHAT APPEARS TO BE
 OUTSIDE LTS ON 2ND FLOOR LEVEL WHICH
 INDICATES THESE LTS TO BE CIRCUIT B-8
 AND A-8, HOWEVER ALSO INDICATE THESE TO
 BE ON A TC (TIMECLOCK)? PLEASE CORRELATE
 THESE IF INDEED THEY ARE TO BE ON WITH
 THE FIRST FLR OUTSIDE TC CIRCUIT?
  
 23)NOTE: PLEASE SEE THE MISSING REQUIRED
 DEDICATED SIGN CIRCUIT AS PER 600.5
  
 24)NOTE: PLEASE SEE THE NEW FBC 2004,
 CHAPTER 13 (ENERGY CODE) FOR EXPANDED
 REQUIMENTS FOR COMMERCIAL BLDGS.
 13-413,13-415 ETC.
 PLEASE ADJUST AS NEEDED.
  
 25)NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9
 WHICH REQUIRES A MIN OF BATTERY BACK UP
 EM LTS FOR MEANS OF EGRESS TO THE PUBLIC RIGHT-OF-WAY.
 PLEASE SEE FIRE REVIEW
 COMMENTS ALSO FOR THIS.
 PLEASE SEE 7.8.1.3 WHICH NOW REQUIRES A
 MIN OF 10 FT CANDLES (108 LUX) FOR ALL
 LEVELS OF STAIRS DURING NORMAL POWERE
 AND THE PERMITTED DE-RATINGS ALLOWED BY
 7.9.2.2 UNDER EMERGENCY CONDITIONS.
 TO 10.8 LUX.
  
 26)NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE AND CORRELATE WITH THE PLANS.
 PLEASE SEE NOTES #24 AND #25 FOR TYPES
 OF FIXTURES.
  
 27)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS. THESE
 SHALL BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT SUPPLYINGLIGHTING IN THAT
 AREA.
  
 28)NOTE: PLEASE SEE 210.8A6 WHICH
 REQUIES ALL RECEPTS SERVIING KITCHEN
 COUNTERSPACES TO BE GFI/GFI PROTECTED.
  
 29)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS.
  
 30)NOTE: PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH CIRCUITS PER
 210.52D,210.11C3. SHALL BE #12 AND 20.
 PLEASE SEE #14, 15A SHOWN FOR BOTH APTS
 UPSTAIRS.
 ** PLEASE SEE WHAT APPEARS TO BE APT
 WHICH SHOWS A CIRCUIT #8 FOR BATH GFI'S.
 PLEASE KNOW, THE DEDICATED BATH CIRCUIT
 MAY NOT FEED ANY OTHER AREAS.
  
 31)NOTE: PLEASE SEE THE CIRCUIT
 INDICATED ON PLANS FOR WHAT APPEARS TO
 BE A WASHER LOCATION IS SHOWN AS A SPARE
 ON PANEL SCHEDULE??
 PLEASE SEE 210.11C2, 220.16B WHICH
 REQUIRES A LAUNDRY CIRCUIT AND WASHER
 CIRCUIT TO BE A MIN 1500 VA , 20A AND
 #12 AWG.
 PLEASE ADJUST LOAD CALCUALTIONS ETC.
  
 32)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS AS REQUIRED UNDER NFPA-72
 11.5.1.1.
 MISSING INSIDE AND OUTSIDE ALL SLEEPING
 RMS.
 PLEASE ALSO SEE 11.8.3.5 FOR LOCATIONS
 OF SD'S WHICH ARE REQUIRED TO BE A MIN
 OF 3' FROM KITCHEN AND BATH DOORS AND
 SHALL BE A MIN OF 20' FROM ANY COOKING
 APPLIANCES. (COOKING APPLIANCES WITH
 EXCEPTIONS).
 PLEASE ALSO SEE NOTE ON PLANS WHICH
 MENTIONS SD'S ARE TO BE WIRED AHEAD OF
 THE SWITCHES ON EITHER BATH OR KITCHEN
 LIGHTING CIRCUIT, PLEASE SEE THIS IS OK,
 HOWEVER ARC FAULT PROTECTION WILL THEN
 BE REQUIRED FOR THOSE LIGHTING CIRCUITS,
 PLEASE SEE BATH LTS ARE ALSO WIRED TO BE
 A DEDICATED CIRCUIT FOR EACH BATH RM.
 ** PLEASE SEE COMMENT FOR REQUIRED ARC
 FAULT.
  
 33)NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS AS REQUIRED
 PER 2002 NEC 210.12B
  
 34)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE SHOWN, HOWEVER
 ONLY ONE IS SHOWN FOR KITCHEN. PLEASE
 ADJUST CIRCUITING AS THE MIN OF TWO SM
 APPL CIRCUITS SHALL BE IN KITCHEN. 210.11C1,220.16A,
 215.5 ETC
  
 35)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 MISSING ALL A?C SYSTEMS?? AHU'S, CU'S.
 PLEASE SHOW ALL DISCONNECTS AS REQUIRED
 PER 440.11, 110.26
  
 36)NOTE: PLEASE SEE 210.63 FOR THE
 SERVICE RECEPT REQUIRED. (GFI) 210.8A
  
 37)NOTE: PLEASE SEE MANY CIRCUITS ON
 PLANS MENTIONS "GEN LTS" GEN RECEPTS"
 PLEASE LIST THESE TO BE SPECIFIC TO THE
 AREAS IN WHICH THEY ARE FEEDING.
  
 38)NOTE: PLEASE LABEL APTS ON PLANS AND
 CORRELATE. PLEASE SEE WHAT APPEARS TO BE
 APT "B".
  
 39)NOTE: PLEASE VERIFY WHAT IS SHOWN AS
 A QUAD RECEPT IN KITCHEN ON FIRST FLR
 WHICH IS SHOWN AS 15AON PANEL
 SCHEDULE?
 PLEASE ALSO SEE PREVIOUS COMMENT WITH
 RESPECT TO GFI PROTECTION.
  
 40)NOTE: PLEASE SEE PLANS WHICH SHOWS A
 CIRCUIT FOR WHAT IS LISTED ON PANEL
 SCHEDULE AS BEING A MICROWAVE # 14,
 HOWEVR NO DEVICE OR LOCATION IS SHOWN ON
 PLANS.
  
 41)NOTE: PLEASE SEE SWITCHES WHICH ARE
 SHOWN WIRED TO A 3-WAY SYSTEM, HOWEVER
 DO NOT INDICATE BEING S3.
 PLEASE SEE REDLINED LOCAITONS.
  
 42)NOTE:PLEASE SEE REDLINED MISSING
 RECEPT PER 210.52, 2' OF WALL.
  
 43)NOTE: PLEASE SHOW THE LOCATION OF THE
 SERVICE ON PLANS/BLDG.
 230.70,240.24,110.26, ETC
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AND THE EXTENT OF COMMENTS,
 PLEASE COMPLETE ALL OF THE ABOVE TO
 ALLEAVIATE FUTHER COMMENTS ON THE
 FOLLOWING REVIEW.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONLY ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE TO GO OVER ANY COMMENTS OR
 QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
2006-01-12 00:00:00SENT TO INCOMING AS BLDG IS MIXED USE
 AND SHOULD BE ON COMMERCIAL BOARD.