Plan Review Notes
Plan Review Notes For Permit 05121091
Permit Number 05121091
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)A-1, DECLARE OCCUPANCY FBC3.THIS
 IS A MIXED USE BUILDING.DECLARE
 OCCUPANCY FOR THE FIRST FLOOR OFFICE
 AREA, FIRST FLOOR ART STUDIO, FIRST
 FLOOR WORKSHOP, SECOND FLOOR APARTMENTS.
  
  
 4.)ON THE AREA CALCULATIONS, INCLUDE
 EXISTING AREA, PROPOSED NEW, AND NEW
 TOTAL.THERE IS AN ADDITION FOR THE
 FIRST FLOOR SHOWN ON THE PLAN.
  
 5.)AS1, GOVERNING CODE IS FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 6.)AS1, INCORRECT ASCE7 REFERENCE,
 FBC35.
  
 7.)AS1, ACCESSIBLE PARKING, CANNOT
 WALK BEHIND PARKED CARS AND IS TO BE ON
 AN ACCESSIBLE ROUTE MINIMUM 44IN.
 FBC11-4.6.2(1), FBC FIGURE 11-9(A).
  
 8.)AS1 SHOWS THE SIGNAGE FOR THE
 ACCESSIBLE PARKING ON ANOTHER PROPERTY.
 ALTHOUGH THERE IS AN EASEMENT, THE
 EASEMENT IS REVOCABLE WITH 30 DAYS
 WRITTEN NOTICE BY EITHER PARTY AND ALSO
 UNDER OTHER CONDITIONS.THE SIGN IS
 REQUIRED AND MUST BE ON THE SAME PARCEL
 AS THE PARKING SPACE.
  
 9.)AS1, PARKING STRIPING TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS,
 SEE ATTACHED.
  
 10.)AS1, DECLARE BUILDING TYPE
 ACCORDING TO FBC2004 CHAPTER 6.ALSO
 NOTE WHETHER THIS BUILDING IS FULLY
 SPRINKLED OR UNSPRINKLED.NO SPRINKLER
 PLANS SUBMITTED AND NO INFORMATION
 PROVIDED ON THE PLAN.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE 602
 AND FBC704.8.THE EAST SIDE IS LESS
 THAN 10' FROM THE PROPERTY LINE, WEST
 SIDE IS AT THE PROPERTY LINE.SHOW FIRE
 RESISTANCE RATING OF THE WALL AND
 OPENINGS IF APPLICABLE.
  
 12.)SHOW FINISHED FLOOR ELEVATION ON
 BOTH SIDES OF THE REAR ENTRANCE DOOR AND
 THE MAXIMUM SLOPE AT THE FRONT ENTRANCE
 DOOR A-A6, FBC11-4.1.6(1).
  
 13.)SHOW THE PROPERTY LINE A-A6.THE
 FOOTER CANNOT ENCROACH THE PROPERTY
 LINE.
  
 14.)DECLARE LEVEL OF ALTERATION, FBC
 EXISTING BUILDING CODE.
  
 15.)ARE THERE MULTIPLE TENANTS OR ONE
 TENANT ON THE FIRST FLOOR?
  
 16.)PROVIDE INFORMATION IN REGARDS TO
 WHAT MATERIALS WILL BE STORED IN THE ART
 STUDIO AND WORKSHOP, FBC 3.
  
 17.)THE PARTITION LEGEND SYMBOL FOR
 THE EXISTING CONCRETE BLOCK WALL IS NOT
 CONSISTENT WITH THE FLOOR PLAN.
  
 18.)S2, BEAM B2, SPECIFY WIDTH.ONLY
 QUANTITY AND HEIGHT IS SHOWN.
  
 19.)SEMCO IS NO LONGER IN BUSINESS.
 SPECIFY AVAILABLE CONNECTORS, 4-A7.
 CHECK ALL DETAILS (OTHERS ARE ALSO
 SPECIFY SEMCO).
  
 20.)PROVIDE FLOOR LOADING DESIGN
 CRITERIA, FBC TABLE 1607.1.ALSO
 PROVIDE FLOOR LOADING CERTIFICATION;
 SHOW ON THE PLAN THAT THE EXISTING ROOF
 FRAMING CAN ACCOMMODATE THE FLOOR
 LOADING DESIGN.
  
 21.)THE FIRE RATING AT THE EXIT ON THE
 FIRST FLOOR IS NOT CONTINUOUS.FOR
 INSTANCE, NO FIRE RATING IS SHOWN AT THE
 WORKSHOP, ART STUDIO, COLUMNS.
  
 22.)THE EXIT SHOWN ON THE FIRST FLOOR
 (STAIR AREA) CANNOT HAVE A KITCHEN,
 FBC1013.2.
  
 23.)NO STORAGE ALLOWED UNDER THE
 STAIRS, FBC1019.1.5.
  
 24.)NO OPENINGS OR PENETRATIONS
 ALLOWED IN THE EXIT ENCLOSURE,
 FBC1019.1.2 (THE DOOR TO THE STORAGE
 AREA, THE KITCHEN, DUCTWORK).
  
 25.)FOR EGRESS PURPOSES, DECLARE
 DESIGN OCCUPANT LOADS, A1, FBC1004.1.
  
 26.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.5.
  
 27.)PROVIDE A DETAIL FOR THE UL
 ASSEMBLY, VERTICAL SEPARATION.ONE IS
 SPECIFIED BUT NO DETAIL WAS PROVIDED.
 FBC402.7.2, TENANT SEPARATION.
  
 28.)SMOKE DETECTORS REQUIRED AT
 SLEEPING ROOMS IN ACCORDANCE
 FBC907.2.10.1.2.
  
 29.)SHOW HALLWAY WIDTH BETWEEN THE
 STAIR AND ART STUDIO, FIRST FLOOR.
  
 30.)HORIZONTAL SEPARATION REQUIRED,
 FBC 302.3, FBC TABLE 302.3.2, OCCUPANCY
 SEPARATION.SPECIFY UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE.
  
 31.)THE ASTM REFERENCES ON S2 ARE
 OUTDATED.YOU HAVE SPECIFIED VERSIONS
 WHICH ARE OVER TEN YEARS OLD.REVISE TO
 A MORE CURRENT STANDARD.
  
 32.)THE EXIT STAIR IS TO BE ENCLOSED,
 FBC1019.1.
  
 33.)NO FIRE RATING IS SHOWN FOR THE
 ELEVATOR SHAFT, FBC707.14.NOTE ALL
 FIRE RATING REQUIREMENTS ON THE FLOOR
 PLAN TO AVOID CONFUSION WITH OTHER
 TRADES.
  
 34.)SPECIFY FIRE RATING FOR DOORS, FBC
 TABLE 715.3.
  
 35.)THE ELEVATOR IS TO BE IN
 CONFORMANCE WITH ASME A17.1, FBC3001.2.
 NOTE ON THE PLAN.
  
 36.)THE DOOR AT THE ELEVATOR (FIRST
 AND SECOND FLOORS) AND THE DOOR AT THE
 MEN?S RESTROOM BLOCK THE EGRESS,
 FBC1005.2.
  
 37.)PROVIDE A DETAIL FOR THE BREAKROOM
 SINK, FBC11-4.24.SHOW CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 38.)SHOW MANEUVERING CLEARANCE PULL
 SIDE, FBC11-4.13.6, FBC FIGURE 11-25.
 FOR THE DOOR AT THE END OF THE HALLWAY
 LEADING TO THE EXIT ENCLOSURE, FIRST
 FLOOR.NOTE THAT NORMALLY FOR
 COMMERCIAL PLANS DOORS AND ROOMS ARE
 NUMBERED TO ASSIST IN REFERENCE.
  
 39.)THE MASONRY OPENING SIZES FOR THE
 EAST ELEVATION ARE NOT CONSISTENT WITH
 THE ELEVATION OR THE FLOOR PLAN, A4.
  
 40.)HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF THE STAIR, FBC1009.11.
  
 41.)HANDRAIL EXTENSIONS REQUIRED,
 FBC1009.11.5.
  
 42.)3-A7, SOME DIMENSIONS ARE MISSING,
 SUCH AS THE MINIMUM HANDRAIL DIMENSION,
 DISTANCE FROM WALL.PROVIDE ONLY
 COMPLETE SPECIFIC DETAILS.
  
 43.)THE PLUMBING PLAN IS LABELED AIR
 CONDITIONING PLAN.
  
 44.)DUCTS THROUGH FIRE RATED WALLS ARE
 TO BE PROTECTED, FBC712.4.4.AC1, FIRST
 FLOOR.
  
 45.)FIREBLOCKING REQUIRED, 4-A7,
 FBC717.2.3.
  
 46.)NO FIRE PROTECTION SHOWN FOR THE
 ENCLOSURE UNDER THE STAIR, FBC1019.1.5.
  
 47.)NO CONTINUOUS FIRE RESISTANCE
 SHOWN BETWEEN FIRST FLOOR TENANT AND THE
 COMMON SPACE.NOTE THAT THERE ARE TWO
 FIRE RESISTANCE REQUIREMENTS; ONE FOR
 TENANT (COMMON SPACE) SEPARATION, ONE
 FOR PROTECTION OF THE EXIT WHICH IS THE
 ONLY MEANS OF EGRESS FROM THE SECOND
 FLOOR.
  
 WHEN RESUBMITTING, PROVIDE A RESPONSE
 LETTER STATING HOW EACH ITEM WAS
 ADDRESSED.