Plan Review Notes For Permit 05121022 |
Permit Number |
05121022 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-06-02 00:00:00 | DENIED; | | 1.WASHING MACHINE WASTE CONNECTION TO BE | | 3"FBC-2004 SEC. 406.3. A SANIARY CROSS | | CAN NOT BE USED. 3"X2" Y FITTING MUST BE | | USED SEC. 706.3 (EXCEPTION) CLEANOUT AT | | 48"AFF IS ALSO REQUIRED. | | 2.SHOW LOCATION OF VENT FOR FLOOR DRAIN | | AND TRAP PRIMER AND TYPE OF PRIMMER TO | | BE USED. | | 3.WATER HEATER DETAIL, SHOW MEANS OF | | CONTROLING THERMAL EXPANTION. SEC. | | 607.3. | | 4.WATER HAMMER ARRESTORS REQUIRED ON | | WATER PIPES AT WASHER HOOK UP. SEC 604.9 | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|