Date |
Text |
2006-05-09 00:00:00 | ***** UNSAT ********* |
| |
| |
| 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS |
| REVIEW. PLEASE INDICATE THE FEEDERS TO |
| THIS EXISTING PANEL. |
| INDICATE THE MEANS OF DISCONNECT |
| REQUIRED PER 225.31-225.39 |
| PLEASE SEE 250.32. |
| 240.4,310.16, ETC. |
| |
| 2) NOTE: PLEASE SEE CIRCUITING FOR NEW |
| EM LT IS NOW SHOWN CIRCUITED TO THE |
| COUNTER SPACE RECEPT? |
| PLEASE SEE 700.12E. ALL EM/EXT LTS SHALL |
| BE CIRCUITED TO THE LOCAL LIGHTING |
| BRACNCH CIRCUIT. |
| |
| 3) NOTE: PLEASE SEE SEE ORIG NOTE |
| MENTIONED THE MIN OCP FOR THE WATRE |
| HEATER HAD TO BE 125%. PLEASE SEE NOW, |
| THE KW RATING IS SHOWN AT 4KW AND THE |
| OCP IS SHOWN TOO HIGH. |
| PLEASE SEE 422.11(E)3) MAX OCP SHOULD BE |
| 150%. PLEASE KNOW, THIS WOULD BE 25A'S. |
| |
| 4) NOTE: PLEASE SEE WATER HEATER IS NOW |
| BEINGSHOWN IN A CLOSED IN AREA AND |
| DOES NOT INDICATE WHERE THE ACCESS IS? |
| 422.17,110.26 ETC. |
| |
| 5) NOTE: PLEASE SEE THAT HAND DRAWN |
| CHNAGES ARE NOT PERMITTED ON PLANS WHICH |
| ARE SIGNED, DATED AND SEALED BY AN |
| ARCHITECT OR ENGINEER. |
| FS 471/481 |
| PLEASE SEE HAND WRITTEN CHANGE OVER WHAT |
| WAS SHOWN AS 100A PANEL, NOW DRAWN AS |
| 200A'S.? |
| |
| 6) NOTE: PLEASE SEE ATTACHED COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO REPEAT CODE |
| COMPLIANT COMMENTS. |
| |
| PLEASE CORRELATE ALL OF THE ABOVE. |
| |
| ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE BE SURE TO SEE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| EELCTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-05-08 00:00:00 | IN ELEC FOR REVIEW. |