Plan Review Notes
Plan Review Notes For Permit 05121022
Permit Number 05121022
Review Stop B
Sequence Number 2
Notes
Date Text
2006-05-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)THE SCOPE OF WORK IS NOT CLEAR.
 THE APPLICATION STATES "EXPANSION",
 WHICH IMPLIES AN ADDITION, BUT A
 FOUNDATION PLAN IS NOT SHOWN.NO SITE
 PLAN WAS PROVIDED.THE PLANS STATE BOTH
 "EXIST CART BARN" AND "NEW LAUNDRY".
  
 SECOND REVIEW - SCOPE OF WORK WAS
 CLARIFIED, BUT CHANGES TO THE PLAN HAVE
 TRIGGERED NEW COMMENTS.
  
 2.)ONLY A PARTIAL FLOOR PLAN WAS
 PROVIDED.WHAT IS IN THE REST OF THE
 BUILDING?DECLARE OCCUPANCY FOR THIS
 AREA AND ADJACENT AREA, ADDRESSING ANY
 FIRE RATING REQUIREMENTS, IF ANY.SHOW
 NEARBY STRUCTURES.
  
 SECOND REVIEW - BUSINESS OCCUPANCY WAS
 DECLARED.READ FBC 311.THIS IS NOT
 BUSINESS OCCUPANCY, READ FBC304.1. THE
 CART STORAGE AREA IS S1.THE LAUNDRY IS
 EITHER MIXED USE F1 306.2 OR INCIDENTAL
 USE FBC 302.1.1.READ CHAPTER 3 AND
 DECLARE CORRECT OCCUPANCY. IF THIS IS
 MIXED USE, SHOW REQUIRED FIRE SEPARATION
 OF 2 HOURS.
  
 DECLARE CONSTRUCTION TYPE FBC6.TYPE
 III WAS DECLARED, A OR B?
  
 3.)THE SINGLE DOORAPPEARS TO LEAD
 OUTSIDE; IS THIS CORRECT?WHY DOES THE
 WALL THAT IT IS PERPENDICULAR TO EXTEND
 FURTHER, IMPLYING ADDITIONAL AREA?ALSO
 THIS DOOR IS FIRE RATED, IMPLYING A
 SEPARATION, AND THE DOUBLE DOOR DOES NOT
 SHOW A FIRE RATING.IF THIS DOOR LEADS
 TO INTERIOR SPACE, EVEN IF IT IS A WORK
 SPACE, THE DOOR MUST MEET MANEUVERING
 CLEARANCE FBC11-4.13.6.
  
 SECOND REVIEW - THE DOOR HAS BEEN
 RELOCATED BUT NOW BLOCKS OVER HALF THE
 REQUIRED WIDTH OF THE PASSAGEWAY,
 FBC1008.1.8.8.
  
 4.)ADDRESSED, NOT AN ADDITION.
  
 5.)IF THIS IS AN ADDITION, SHOW A WALL
 DETAIL CONTINUOUS FROM THE FOUNDATION
 THROUGH THE ROOF, ALL WIND DESIGN
 CRITERIA, FBC16.
  
 SECOND REVIEW - ALTHOUGH THIS IS NOT AN
 ADDITION, THERE IS STILL AN EXTERIOR
 ALTERATION (DOORS).PROVIDE WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 6.) ADDRESSED.A LOCAL PRODUCT APPROVAL
 WILL BE ISSUED USING THE NOA.
  
 7.)ADDRESSED.
  
 NEW COMMENTS:
  
 8.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.