2006-01-24 00:00:00 | *** UNSAT *** |
| |
| 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN |
| AS EXISTING, HOWEVER PLEASE INDICATE IF |
| THE EXISTING FEEDERS. THIS CAN BE NOTED. |
| PLEASE ALSO INDICATE OF PANEL CONTAINS A |
| MEANS OF DISCONNECT, MCB ?SINCE THIS |
| SEEMS TO BE SHOWN AS A DETACHED BLDG. |
| PLEASE ALSO INDICATE GROUNDING ELECTRODE |
| , NEW OR EXISTING FOR THIS PANEL AT |
| DETACHED BLDG. |
| ALL PER 240.4,310.16,225.31,250.32 ETC. |
| |
| 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| AND CORRELATE WITH THE PANEL SCHEDULE |
| SUBMITTED. |
| 215.5 |
| PLEASE BE SURE TO INDICATE THE EM LT |
| CIRCUITED TO THE SAME CIRCUIT FEEDING |
| THE LOCAL LIGHTING BRANCH CIRCUIT. |
| 700.12E. |
| |
| 3)NOTE: PLEASE SEE MIN OCP FOR WATER |
| HEATER SHALL BE SIZED A MIN OF 125%. |
| 422.13 |
| |
| 4)NOTE: PLEASE SEE WALL A/C UNIT ON |
| PANEL SCHEDULE WHICH INDICATES A 5KW |
| UNIT ON A 1-POLE 20A BRKR? PLEASE |
| CORRELATE WITH LOAD CALCUALTIONS, AS |
| LOAD CALCS INDICATE THE LOAD AS 1.5KW? |
| 215.5 |
| |
| PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |