Plan Review Notes
Plan Review Notes For Permit 05121022
Permit Number 05121022
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-24 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN
 AS EXISTING, HOWEVER PLEASE INDICATE IF
 THE EXISTING FEEDERS. THIS CAN BE NOTED.
 PLEASE ALSO INDICATE OF PANEL CONTAINS A
 MEANS OF DISCONNECT, MCB ?SINCE THIS
 SEEMS TO BE SHOWN AS A DETACHED BLDG.
 PLEASE ALSO INDICATE GROUNDING ELECTRODE
 , NEW OR EXISTING FOR THIS PANEL AT
 DETACHED BLDG.
 ALL PER 240.4,310.16,225.31,250.32 ETC.
  
 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE PANEL SCHEDULE
 SUBMITTED.
 215.5
 PLEASE BE SURE TO INDICATE THE EM LT
 CIRCUITED TO THE SAME CIRCUIT FEEDING
 THE LOCAL LIGHTING BRANCH CIRCUIT.
 700.12E.
  
 3)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATER SHALL BE SIZED A MIN OF 125%.
 422.13
  
 4)NOTE: PLEASE SEE WALL A/C UNIT ON
 PANEL SCHEDULE WHICH INDICATES A 5KW
 UNIT ON A 1-POLE 20A BRKR? PLEASE
 CORRELATE WITH LOAD CALCUALTIONS, AS
 LOAD CALCS INDICATE THE LOAD AS 1.5KW?
 215.5
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  