Plan Review Notes
Plan Review Notes For Permit 05120992
Permit Number 05120992
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-16 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- A) ENGINEER CALCULATIONS SUBMITTED
 NEED TO HAVE ORIGINAL SEAL, SIGNATURE
 AND DATE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
  
 B) PROVIDE 2 COPIES.
  
  
 2- SINGLE HUNG FLORIDA PRODUCT APPROVAL
 FL2742 IS NOT APPROVED. APPROVAL STATUS
 SAYS THAT MANUFACTURER NEEDS TO
 RE-APPLY.PRODUCT APPROVAL MUST BE
 APPROVED IN ORDER TO BE USED.
  
 3- ENGINEER WHO PROVIDE CALCULATIONS ON
 ITEM #1 ABOVE TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 OF CITY AMENDMENTS TO TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712