2006-01-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- THIS IS A HIGHRISE BUILDING. PROVIDE
 ENGINEERING CALCULATIONS FOR THE
 OPENINGS DESIGN PRESSURES AS REQUIRED BY
 SEC. 1609 FBC 2004 AND SEC. 106.1.2 OF
 CITY AMENDMENTS TO FBC 2004.
 ***NEED TO VERIFY THAT PROPOSED WINDOWS
 AND MULLIONS WILL RESIST THE CALCULATED
 DESIGN PRESSURES.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 OF
 DCA FOR:
 A) SINGLE HUNG WINDOWS. FLORIDA
 PRODUCT APPROVAL FL2742 WAS NOT
 APPROVED. MANUFACTURER NEEDS TO
 RE-APPLY. SEE NOTE ON FL 2742 UNDER
 APPLICATION STATUTES. .
 B) WINDOW MULLIONS IF THE WINDOWS ARE
 GOING TO BE MULLED TOGETHER.
 ***NOTE: CLEARLY SPECIFY HOW ARE
 MULLIONS GOING TO BE ANCHORED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN
 PRESSURES. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 3- PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
  
 4- DESIGNER OF RECORD (SEE ITEM #2
 ABOVE) TO REVIEW AND APPROVE THE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004 PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  