2006-01-31 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- THIS IS A HIGHRISE BUILDING. PROVIDE |
| ENGINEERING CALCULATIONS FOR THE |
| OPENINGS DESIGN PRESSURES AS REQUIRED BY |
| SEC. 1609 FBC 2004 AND SEC. 106.1.2 OF |
| CITY AMENDMENTS TO FBC 2004. |
| ***NEED TO VERIFY THAT PROPOSED WINDOWS |
| AND MULLIONS WILL RESIST THE CALCULATED |
| DESIGN PRESSURES. |
| |
| 2- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL AS REQUIRED BY RULE 9B-72 OF |
| DCA FOR: |
| A) SINGLE HUNG WINDOWS. FLORIDA |
| PRODUCT APPROVAL FL2742 WAS NOT |
| APPROVED. MANUFACTURER NEEDS TO |
| RE-APPLY. SEE NOTE ON FL 2742 UNDER |
| APPLICATION STATUTES. . |
| B) WINDOW MULLIONS IF THE WINDOWS ARE |
| GOING TO BE MULLED TOGETHER. |
| ***NOTE: CLEARLY SPECIFY HOW ARE |
| MULLIONS GOING TO BE ANCHORED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN |
| PRESSURES. SEC. 106.1.2 OF CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 3- PROVIDE RECORDED NOTICE OF |
| COMMENCEMENT. |
| |
| 4- DESIGNER OF RECORD (SEE ITEM #2 |
| ABOVE) TO REVIEW AND APPROVE THE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 106.3.3 OF |
| CITY AMENDMENTS TO FBC 2004 PRIOR TO |
| SUBMITTAL TO THIS OFFICE. |
| |