Plan Review Notes For Permit 05120987 |
Permit Number |
05120987 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-02-12 18:46:38 | SUBMITTAL OF WIND LOAD CALCULATIONS FOR LIGHT POLES ON | | TOP OF PARKING GARAGE ARE DENIED. | | | | 1) THREE SET OF SIGNED AND SEALED DRAWINGS ARE REQUIRED | | FOR THRESHOLD BUILDINGS. | | | | 2)THE ENGINEERING IS REQUIRED TO BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | STRUCTURE. | | | | 3) SUBMIT A DETAIL SPECIFYING HOW THE CONCRETE BASE | | SHOWN IN THE HAPCO DRAWING WITH 36" ANCHOR BOLTS | | EMBEDDED ARE ATTACHED TO THE STRUCTURE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|