Plan Review Notes For Permit 05120987 |
Permit Number |
05120987 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-04-22 09:06:12 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE 620.23, 620.24 FOR REQUIRED | | DEDICATED CIRCUITS. THESE MAY NOT FEED OTHER AREAS | | AND/OR EACH OTHER. | | | | 2) NOTE: PLEASE SEE REDLINED NOTES FROM 10/6/06 WHICH | | REQUIRED THE ATTACHMENT LOCATIONS TO BE SHOWN FOR | | TRANSFORMER. | | PLEASE SEE 250.20,250.30, 250.66. | | PLEASE KNOW THIS WAS REDLINED ON PLANS FOR ISSUANCE. | | | | ** PLEASE SEE POSSIBLE BUILDING REVIEW NOTES. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|