Plan Review Notes For Permit 05120987
Permit Number 05120987
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2006-10-23 13:00:15***APPROVED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 ALARM AND STANDPIPE SYSTEMS.
  
 2) TEMPORARY STANDPIPES REQUIRED WHEN BUILDING REACHES
 (3) STORIES OR (30') IN HEIGHT.
  
 3) FIRE DEPARTMENT VALVES ON STANDPIPES TO BE 2 1/2"- 1
 1/2" REDUCER WITH CHAINS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722