Plan Review Notes
Plan Review Notes For Permit 05120987
Permit Number 05120987
Review Stop ENG
Sequence Number 3
Notes
Date Text
2006-10-06 00:00:00 
 FOUND INCONSISTENCY IN LEGEND, FOR
 EXAMPLE, CIVIL SH 2 OF 5,IN LEGEND,
 PROPOSED STORM SEWER & CATCH BASIN HAS
 SQUARE SYMBOL AND ON DRAWING 142 FT 15"
 RCP HAS ROUND SYMBOL ON NORTH END, IS
 THIS AN INLET? ALSO IT SAYS 10.0 N.S. IS
 IT NORTH INVERT ELE? WHY TWO ELEVATIONS,
 10.0 N. S. WE SEE ONLY ONE END OF PIPE.
 PLEASE MAKE CORRECTION IN ALL SHEETS.
  
 YOU NEED TO SHOW DUMPSTER ENCLOSURE
 DETAILS AND DIMENTIONS PER CITY OF WPB
 STANDARDS
  
 PLEASE SHOW DETAILS ON DRAWINGS PER CITY
 OF WPB STANDARDS FOR SIDEWALK,DRIVEWAY,
 APPROACH,PARKINGS,HANDICAP PARKING PER
 ADA, ETC.,
  
 PLEASE RESPOND EACH ITEM SEPARATELY ON
 YOUR RESPONSE TO EXPEDITE THE PERMIT.
  
 RASIK CHOKSHI 805-6723