Plan Review Notes
Plan Review Notes For Permit 05120987
Permit Number 05120987
Review Stop B
Sequence Number 3
Notes
Date Text
2006-10-12 16:46:34 
 DENIED BY BUILDING
  
 1)THE SURVEY AND SITE PLANS DO NOT LOCATE THE
 CONDO/PROPERTY LINES 20 FEET FROM THE PARKING STRUCTURE
 AS REQUIRED BY 2004 FBC 903.6.1(2). SEE COMMENT #4 FROM
 PREVIOUS REVIEW.
  
 2)THE LOCATION OF THE CONDO/PROPERTYLINES DO NOT
 APPEAR TO BEGREATER THAN 10 FEET AS REQUIRED BY FBC
 TABLE 708.4 FOOTNOTE (C) SUCH THAT THE AREA OF OPENINGS
 IS NOT LIMITED. SEE COMMENT #2 FROM PREVIOUS REVIEW.
  
 3)THE SQUARE FOOTAGE ANALYSIS ON A2.0.1 STILL LISTS
 BUSINESS AND STORAGE OCCUPANCIES ON THE FIRST FLOOR.
  
 4) SHEETS A3.2.2 AND A4.1.2 SPECIFY 3PLY MODIFIED ROOF
 COVERING. THE PRODUCT APPROVAL THAT WAS SUBMITTED IS
 FOR A BUILT UP ROOF SYSTEM. PLEASE CORRECT.
  
 5) DETAIL 2 ON A1.1.0 SPECIFIES AN 8' HIGH GENERATOR
 SCREEN WALL AND THE SITE PLANS ON A 1.1.0 AND A1.1.1
 SHOW THE WALL AS6'. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714