2006-07-09 00:00:00 | 7/9/06 ***FAILED*** |
| |
| 1) THE NORTH WALL ON THE SITE PLANS |
| APPEARS TO BE IN THE INCORRECT |
| LOCATION...IT IMPEDES WITH THE WALKING |
| PATH, NORTHWEST STAIRS, ETC. |
| |
| 2) PROVIDE DETAILS REGARDING THE |
| CHILLER/COOLING TOWERS.WHY ARE THESE |
| NOW BEING PLACED AT GRADE?DETAILS, |
| SUCH AS HEIGHT, NEED TO BE PROVIDED AS |
| WELL AS SUFFICIENT SCREENING (I.E. SOLID |
| WALL OF ADEQUATE HEIGHT WITH |
| SHRUBS/HEDGES). |
| |
| 3) PROVIDE DETAILS REGARDING THE |
| PROPOSED GENERATOR, SUCH AS THE HEIGHT, |
| TO ENSURE THAT THE PROPOSED 6 FOOT |
| SCREEN WALL IS SUFFICIENT. |
| |
| 4) THE NUMBER OF PARKING SPACES |
| INDICATED ON THE SITE PLAN DATA TABLE |
| DOES NOT CORRESPOND WITH WHAT IS DRAWN |
| ON THE FLOOR PLANS.THERE APPEARED TO |
| BE 491 SPACES ON THE FLOOR PLANS (300 |
| REGULAR, 179 COMPACT, AND 12 |
| ACCESSIBLE). |
| |
| 5) PROVIDE AN ENLARGEMENT OF THE DOUBLE |
| STRIPING FOR THE PARKING SPACES.THE |
| DETAIL PROVIDED APPEARS INCORRECT. |
| THERE SHOULD BE 1 FOOT 4 INCHES FROM THE |
| CL OF THE STRIPE TO THE CL OF THE STRIPE |
| WITH 12 INCHES FROM INSIDE OF THE STRIPE |
| TO INSIDE OF THE STRIPE.REFER TO |
| SECTION 94-485 OF THE CITY OF WEST PALM |
| BEACH ZONING AND LAND DEVELOPMENT |
| REGULATIONS FOR AN EXAMPLE.THE |
| HANDICAP STRIPING IS INCORRECT IN REGARD |
| TO THIS AS WELL. |
| |
| 6) PROVIDE A STRIPING DETAIL THAT SHOWS |
| HOW THE SUPPORT COLUMNS RELATE TO THE |
| PROPOSED STRIPING.WHAT ARE THE |
| DIMENSIONS OF THE COLUMNS?WHERE DO |
| THEY FALL IN THE STRIPING?ETC. |
| |
| QUESTIONS/COMMENTS, CONTACT JOHN ROACH, |
| SENIOR PLANNER, AT (561) 822-1435. |