 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 DENIED
 1) SHT P6.2 WATER RISER HOSE BIBBS
 SEC 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 2. ON THE WATER SUPPLY PIPE TO EACH
 SILLCOCK IN OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 2) SHT P6.2 SEC 608.15.4.2
 HOSE CONNECTIONS.
 SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND
 OTHER OPENINGS WITH A HOSE CONNECTION
 SHALL BE PROTECTED BY AN
 ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM
 BREAKER OR A PERMANENTLY ATTACHED HOSE
 CONNECTION VACUUM BREAER.
  
 3)PLUMBING RESPONSE:DATED MAY 19, 2006
 REFERENCE TO SHEET P7.2 DEPICTS A
 CISTERN PIPING DIAGRAM.
 NOT INCLUDE WITH THIS SET OF PLANS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.