Plan Review Notes For Permit 05120987 |
Permit Number |
05120987 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-07-08 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | DENIED | | 1) SHT P6.2 WATER RISER HOSE BIBBS | | SEC 606.2 LOCATION OF SHUTOFF VALVES. | | SHUTOFF VALVES SHALL BE INSTALLED IN THE | | FOLLOWING LOCATIONS: | | 2. ON THE WATER SUPPLY PIPE TO EACH | | SILLCOCK IN OTHER THAN ONE- AND | | TWO-FAMILY RESIDENTIAL OCCUPANCIES. | | | | 2) SHT P6.2 SEC 608.15.4.2 | | HOSE CONNECTIONS. | | SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND | | OTHER OPENINGS WITH A HOSE CONNECTION | | SHALL BE PROTECTED BY AN | | ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM | | BREAKER OR A PERMANENTLY ATTACHED HOSE | | CONNECTION VACUUM BREAER. | | | | 3)PLUMBING RESPONSE:DATED MAY 19, 2006 | | REFERENCE TO SHEET P7.2 DEPICTS A | | CISTERN PIPING DIAGRAM. | | NOT INCLUDE WITH THIS SET OF PLANS. | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT PLUMBING | | PLANS. | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|