Plan Review Notes For Permit 05120987 |
Permit Number |
05120987 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-07-28 00:00:00 | DENIED:2004 FMC | | RESPONSE TO COMMENTS DATED 2-21-06: | | | | COMMENT 1:OK | | COMMENT 2:OK | | | | 3.RESPONSE INDICATES ELEVATION HAS | | BEEN PROVIDED FOR ALL INTAKE & RELIEF | | LOUVERS.PLEASE NOTE, COMMENT REQUESTED | | THE ELEVATION BE PROVIDED FOR THE | | TERMINATION OF EF-1.TERMINATION TO | | EF-1 IS TO THE INTERIOR OF THE PARKING | | GARAGE & APPEARS TO BE DISCHARGING ONTO | | WALKWAY.SHOW COMPLIANCE WITH 2004 FMC | | 401.5.2 & 501.2. | | | | COMMENT 4:OK | | | | ***************NEW COMMENT************* | | | | 5.PLEASE INDICATE WHAT WILL BE IN | | STORAGE AREA.PLEASE NOTE THE | | TERMINATION OF EXHAUST FROM EF-2, 3, 4, | | 5, & 6 ALL TEMRINATE WITHIN 10 FT OF THE | | DOOR.PLEASE CLARIFY. | | | | PLEASE PROVIDE ADDITIONAL INFORMAITON | | FOR THE EMERGENCY GENERATOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|