Date |
Text |
2006-06-18 00:00:00 | IN ELEC FOR REVIEW, REVIEW IN PROGRESS. |
| ***** UNSAT 2ND REVIEW **** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW AND SOME NEW DUE TO MANY ITEMS ON |
| PLANS BEING COMPLETELY REVISED. |
| |
| ** PLEASE SEE THAT AN ADDRESS WAS |
| ASSIGNED FOR PROJECT AND SHOULD BE |
| REFLECTED IN TITLE BLOCKS OF ALL SHEETS. |
| (1621 WORTHINGTON RD.) |
| |
| 1) NOTE: PLEASE SUBMIT ALL MANUFACTURE'S |
| CUT/SPEC SHEETS FOR THE FOLLOWING. |
| FUEL TANK, WP ENCLOSURE FOR GEN. |
| THE GEN AND ATS SPCES WERE SUBMITTED AND |
| ARE OK. |
| PLEASE HOWEVER "HIGHLIGHT" THE GEN AS |
| INDICATED ON PLANS ON THE SPEC SHEETS. |
| |
| ** ON PREVIOUS REVIEW** |
| |
| 2) NOTE: PLEASE SUBMIT PHOTO-METRICS |
| UNDER NORMAL AND EM CONDITIONS FOR ALL |
| EGRESS AREAS. THE NORMAL WERE SUBMITTED, |
| HOWEVER COULD NOT LOCATE EM LEVELS. |
| MIN 1FT CANDLE. NFPA -101 7.8.1.3 , |
| 7.9.2.2. |
| |
| ** PREVIOUS REVIEW** |
| |
| 3) NOTE: PLEASE SEE FXTURE TYPES ON E0.1 |
| DO NOT CORRELATE WIHT MANY FIXTURES IN |
| GARAGE AND STAIRS. |
| STILL NEED TO VERIFY TYPE OF FIXTURE FOR |
| STAIRS. |
| 215.5 |
| |
| 4) NOTE: PLEASE INDICATE THE OCP ON THE |
| GENERATOR FOR EACH BREAKER THAT IS BEING |
| INDICATED ON RISER. |
| PLEASE INDICATE THE INTENDED LOAD(S). |
| (IT IS NOTED THAT THE LOAD ON GGDP IS |
| BEING SHOWN, HOWEVER RISER ALSO SHOWS |
| GEN FEEDING OTHER LOADS? |
| 215.5,220,702.5 ETC. |
| |
| ** PREVIOUS REVIEW NOTE** |
| |
| 5) NOTE: PLEASE SEE CALCULATIONS FOR FBC |
| CHAPTER 13 ARE NEEDED PER 13-415.1.AB.1, |
| 13-415.2.ABC.1. |
| PLEASE PROVIDE WITH ENERGY CALCS. |
| PLEASE SEE ENGERY CALCSMUST BE SIGNED, |
| DATED AND SEALED BY THE RESPONSIBLE |
| DESIGNER OF RECORD. |
| PLEASE SEE CALCS SUBMITTED FOR GYM SPACE |
| WERE NOT SIGNED/SEALED. |
| ** PLEASE SEE NEW "ST" DEVICES LOCATED |
| IN ROOMS DO NOT INDICATE THE MAX TIMED |
| FOR "ON". |
| PLEASE SEE THIS CAN/SHOULD ALSO BE |
| LOCATED ON ELECTRICAL LEGEND. |
| |
| ** PREVIOUS NOTES** |
| |
| 6) NOTE: PLEASE SEE LOADS WERE SHOWN AS |
| "BLANK" ON PREVIOUS PLANS. PLEASE SEE |
| LOADS ARE NOW SHOWN, HOWEVER CONTINUOUS |
| LOADS WHICH ARE REQUIRED TO BE SHOWN |
| @125% DO NOT INDICATE THIS? |
| PLEASE ALSO SEE ANY LARGEST MOTORS SHALL |
| ALSO INDICATE 125%. |
| PLEASE CLARIFY LOADS WHICH ARE BEING |
| SHOWN ON "GMDP" FOR "GLH/GL1" AS BOTH |
| PANELS ARE SHOWN WITHOUT ANY LOADS. |
| WHERE IS THE 20KV COMING FROM? |
| 215.5, 230.42,215.3 220 |
| |
| 7) NOTE: PLEASE SEE "GGDP" SHALL |
| INDICATE A SIGN AS EM MAIN. |
| PLEASE SEE 702.7 FOR SIGNALS REQUIRED. |
| 702.8,701.8,701.9, 230.2E |
| |
| ** FOLLOW NOTES DO NOT APPLY TO KAMM |
| CONSULTING ENG'S. |
| |
| 8) NOTE: PLEASE SEE "S" SHEETS ARE BIENG |
| SEAL WHICH IS NO LONGER ACCEPTABLE UNDER |
| FAC 61G15-23.001. |
| PLEASE KNOW, IN FEB 04, A RULING BY THE |
| FLORIDA BOARD OF PROFESSIONAL ENGINEER'S |
| FOR A CHANGE IN THE WORDING IN THE SEAL. |
| PLEASE KNOW, THE WORDING OF |
| "CERTIFICATE" COULD NO LONGER BE USED |
| AND THE NEW WORDING OF "LICENSE" WAS |
| REQUIRED IN SAID SEAL. |
| PLEASE KNOW THAT AN EXTENSION WAS |
| GRANTED TODEC 31ST, 2005 , HOWEVER ALL |
| PLANS AFTER SUCH DATE SHALL CONTAIN THE |
| NEW SEAL WITH THE WORDING OF "LICENSE". |
| THIS MAY ALSO BE IN BUILDING REVIEW |
| COMMENTS. |
| |
| 9) NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| STILL INDICATING ELECTRICAL LIGHTING |
| ETC. |
| PLEASE KNOW, ALL ELECTRICAL LIGHTING |
| SHALL BE REMOVED FROM SAID PLANS, OR |
| REVISE ELECTRICAL PLANS TO INCLUDE |
| THESE. |
| PLEASE ALSO SEE FBC CHAPTER 13 FOR |
| OUTSIDE LANDSCAPE LT-ING. |
| |
| 10) NOTE: PLEASE SEE MISSING REQUIRED |
| INFORMATION IN TITLE BLOCK FOR LANDSCAPE |
| ARCHITECT AND FIRM. |
| PLEASE SEE 61G1-16.004, FS 481.219 |
| MISSING CERTIFICATE OF AUTHORIZATION #. |
| |
| 11) NOTE: PLEASE SEE FS 553.80(2)(B) |
| WITH RESPECT TO ANY REPEAT COMMENTS. |
| THIS IS ONLY A NOTICE. |
| |
| ** PLEASE ONLY SUBMIT ONE COPY OF |
| OLD/VOIDED SETS FOR REVIEW AND |
| REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| ** NOTE ADDED TO FRONT SCREEN. |
| NOTICE OF COMMENCMENT IN PACKAGE HAS |
| EXPIRED PER FS 713.13(2). |
| WILL NEED A NEW RE-RECORDED NOC BEFORE |
| PICKING UP PERMIT. |