2006-07-05 00:00:00 | DENIED BY BUILDING |
| |
| 1621 WORTHINGTON ROAD |
| 5 STORY PARKING GARAGE |
| TYPE II-B (SPRINKLERED)(PER PLANS) |
| MIXED OCCUPANCY (S-2 STORAGE & BUSINESS) |
| FLOOD ZONE A9 BFE 13' (+ 6" CITY REQ.) |
| REQUIRED SOIL BEARING PER PLANS 8,000 |
| PSF. |
| |
| 1) THE STRUCTURE IS LOCATED IN AN A9 |
| FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| BE REQUIRED. ALL EQUIPMENT MUST ALSO BE |
| LOCATED 6" ABOVE BFE. |
| |
| 2) THE PROPERTY LINES HAVE BEEN CHANGED |
| BY A DECLARATION OF CONDOMINIUM ON FILE |
| WITH THE PROPERTY APPRAISER. THE NEW |
| PROPERTY CONTROL NUMBER THAT HAS BEEN |
| ASSIGNED IS PCN 74-43-43-29-22-000-0030. |
| |
| SEE ATTACHMENT. THESE NEW PROPERTY LINES |
| ARE THE ONES THAT THE FIRE SEPARATION |
| DISTANCES WILL BE BASED ON. PROVIDE A |
| SITE PLAN/SURVEY WITH THE DISTANCES FROM |
| THE BUILDING TO THE "CONDO" PROPERTY |
| LINES SPECIFIED. BASED ON THE LOCATIONS |
| OF THE "CONDO" PROPERTY LINES, THE |
| STRUCTURE DOES NOT COMPLY WITH FBC 704.8 |
| FOR ALLOWABLE AREA OF OPENINGS. NOTE: |
| FOOTNOTE C TO TABLE 704.8 ALLOWS |
| UNLIMITED OPENING AREAS FOR OPEN PARKING |
| STRUCTURES WITH A FIRE SEPARATION OF |
| GREATER THAN 10 FEET. |
| |
| 3)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| THE FOUNDATION PLANS SUBMITTED TO THE |
| COUNTY DID NOT SPECIFY THE FUTURE 2700 |
| SQFT TENNANT SPACE FOR A BUSINESS. THERE |
| WILL BE FEES DUE FOR THIS AREA. |
| |
| 4) THE FIRE SPRINKLER PLANS THAT WERE |
| SUBMITTED SPECIFY THAT THE OPEN GARAGE |
| IS NOT REQUIRED TO BE SPRINKLERED AND |
| THAT THE TENNANT SPACE AND STORAGE/ |
| EQUIPMENT ROOMS ARE SPRINKLERED. THIS IS |
| NOT CORRECT. PLEASE SEE FBC 903.6.1. |
| ANY BUILDING WHICH IS OF THREE STORIES |
| OR MORE IN HEIGHT SHALL BE EQUIPPED WITH |
| AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH SECTION |
| 903.1 . |
| EXCEPTIONS: |
| 2.A STAND-ALONE PARKING GARAGE |
| CONSTRUCTED WITH NONCOMBUSTIBLE |
| MATERIALS, THE DESIGN OF WHICH IS SUCH |
| THAT ALL LEVELS OF THE GARAGE ARE |
| UNIFORMLY OPEN TO THE ATMOSPHERE ON ALL |
| SIDES WITH THE PERCENTAGES OF OPENINGS |
| EQUAL TO OR GREATER THAN THOSE SPECIFIED |
| IN SECTION 406.3 . SUCH GARAGES SHALL BE |
| SEPARATED FROM ANY OTHER STRUCTURE BY |
| NOT LESS THAN 20 FEET (6096 MM). A |
| STAND-ALONE PARKING GARAGE IS ONE THAT |
| IS SOLELY FOR THE PARKING OF VEHICLES |
| AND DOES NOT HAVE ANY OTHER OCCUPANCY |
| GROUP IN THE BUILDING. |
| THERE IS A BUSINESS OCCUPANCY IN THE |
| BUILDING AND THE DISTANCE TO PROPERTY |
| LINES IS LESS THAN 20 FEET (ANOTHER |
| STRUCTURE COULD BE BUILT WITHIN 20 |
| FEET). |
| |
| 5) THE BUILDING DATA ON SHEET A2.0.1 |
| INCORRECTLY REFERENCES TABLE 500. THE |
| CORRECT TABLE IS 2004 FBC TABLE 503. |
| |
| 6) THE BUILDING DATA ON SHEET A2.0.1 IS |
| INCORRECT. SEE FBC TABLE 503. BUSINESS/ |
| TYPE II-B IS LIMITED TO 4 STORIES AND |
| 23,000 SQFT. PER FLOOR.STORAGE S-2/ |
| TYPE II-B IS ALSO LIMITED TO 4 STORIES |
| AND 26,000 SQFT PER FLOOR. |
| UNLESS THE BUILDING OCCUPANCY IS |
| SEPARATED BY 2 HOUR FIRE BARRIER WALLS |
| AND CEILING ASSEMBLY PER FBC 302.3.2 THE |
| MOST RESTRICTIVE LIMITS FOR HEIGHT AND |
| AREA OF TABLE 503 BASED ON CONSTRUCTION |
| TYPE AND OCCUPANCY SHALL BE APPLIED TO |
| THE ENTIRE BUILDING. |
| NOTE: FBC 504.2 ALLOWS HEIGHT & STORY |
| INCREASES FOR A BUILDING EQUIPPED |
| THROUGHOUT WITH AN APPROVED SPRINKLER |
| SYSTEM IN ACCORDANCE WITH SECTION |
| 903.3.1.1. |
| FBC 406.3.6 ALLOWS OPEN PARKING GARAGES |
| OF TYPE II CONSTRUCTION WITH ALL SIDES |
| OPEN TO HAVE UNLIMITED AREA WHEN THE |
| HEIGTH DOES NOT EXCEED 75 FEET. |
| |
| 7) FBC* (CITY AMENDMENTS)109.3.6.1 |
| REQUIRES A STRUCTURAL INSPECTION PLAN TO |
| BE SUBMITTED PRIOR TO THE ISSUANCE OF A |
| BUILDING PERMIT FOR THE CONSTRUCTION OF |
| A THRESHOLD BUILDING. PLEASE SUBMIT A |
| SIGNED AND SEALED STRUCTURAL INSPECTION |
| PLAN FROM THE ENGINEER OF RECORD FOR THE |
| STRUCTURE. |
| |
| 8) PLEASE REVISE THE REFERENCE TO |
| ASCE7-98 IN THE NOTES UNDER THE GROSS |
| UPLIFT AND WALL DESIGN TABLES ON S4.O. |
| THE CORRECT REFERENCE IS ASCE7-02. |
| |
| 9) ON SHEET A8.1.1 PLEASE REPLACE SBC |
| WITH FBC. |
| |
| 10) ON SHEET A9.1.1 PLEASE CORRECT THE |
| NOTE UNDER TYPE "C" WALLS TO REFERENCE |
| THE FBC AND NOT THE SFBC. ALSO CORRECT |
| THE TABLE SPECIFIED. |
| |
| 11) FBC 11-4.6.4 VAN ACCESSIBLE PARKING |
| SPACES LOCATED WITHIN A PARKING |
| STRUCTURE SHALL HAVE AN ADDITIONAL SIGN |
| READING ?VAN ACCESSIBLE? MOUNTED BELOW |
| THE SYMBOL OF ACCESSIBILITY. SUCH SIGNS |
| SHALL BE LOCATED SO THEY CANNOT BE |
| OBSCURED BY A VEHICLE PARKED IN THE |
| SPACE. |
| |
| 12) PROVIDE NOTE ON PLANS TO SHOW |
| COMPLIANCE WITH FBC 3002.4, WHICH |
| REQUIRES AT LEAST ONE PASSENGER ELEVATOR |
| TO ACCOMMODATE AN AMBULANCE STRETCHER |
| 76" LONG AND 26" WIDE IN THE HORIZONTAL |
| POSITION. |
| |
| 13) PROVIDE NOTE ON PLANS TO SPECIFY |
| THAT ELEVATOR IS TO COMPLY WITH FBC |
| 11-4.10 FOR ACCESSIBILITY AND ASME |
| A17.1-1990 'SAFETY CODE FOR ELEVATORS |
| AND ESCALATORS'. |
| |
| 14) FBC 11-4.6.2 INDICATE THE ACCESSIBLE |
| ROUTE OF TRAVEL FROM THE PARKING GARAGE |
| TO THE ACCESSIBLE ENTRANCE OF THE |
| BUILDING IT SERVES. |
| |
| 15) FBC 1008.1.2 REQUIRES EGRESS DOORS |
| TO SWING IN THE DIRECTION OF TRAVEL |
| WHERE SERVING AN OCCUPANT LOAD OF 50 OR |
| MORE PERSONS. THE MIDLEVEL PLANS ON |
| SHEETS A2.0.2 AND A2.2.1 SHOW DOOR 201 |
| WITH THE WRONG SWING. |
| |
| 16) FBC 1008.1.1 REQUIRES EGRESS DOORS |
| TO HAVE A MINIMUM CLEAR WIDTH OF NOT |
| LESS THAN 32". ON A2.0.1 E7 THRU E10 ARE |
| SPECIFIED WITH 30" WIDTHS. |
| |
| 17) ON SHEET A8.1.1 OPENINGS 103 & 104 |
| ARE SPECIFIED AS WINDOWS W/SIDELITES AND |
| AS FUTURE EGRESS DOORS. THESE SHOULD NOT |
| BE LISTED AS EGRESS OPENINGS ON SHEET |
| A2.0.1. PLEASE CLARIFY. |
| |
| 18) SUBMIT PRODUCT APPROVALS FOR THE |
| ROOFING MATERIALS. PLANS SPECIFY 4 PLY |
| MODIFIED HOT MOP. |
| |
| 19) THE EXTERIOR BUILDING ELEVATIONS |
| ELEVATIONS ON SHEET A3.1.3 APPEAR TO |
| SHOW TRANSOM WINDOWS ABOVE THE EXTERIOR |
| STAIRWAY DOORS AT THE FIRST LEVEL. |
| SPECIFY THIS IN THE DOOR SCHEDULE AND |
| SUBMIT PRODUCT APPROVALS FOR THE TRANSOM |
| WINDOWS AND THE STRUCTURAL MULLIONS. |
| |
| 20) IF THE PRODUCTS HAVE A STATE PRODUCT |
| APPROVAL IN ADDITION TO THE MIAMI DADE |
| NOA, PLEASE PRINT A COVER SHEET WITH THE |
| FL# FROM THE STATE WEBSITE |
| (WWW.FLORIDABUILDING.ORG) AND ATTACH IT |
| TO THE NOA. |
| |
| 21) FBC 106.3.3*(CITY AMENDMENTS) |
| REQUIRES PRODUCTS REGULATED BY DCA RULE |
| 9B-72 TO BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. |
| PRODUCT APPROVALS SUBMITTED HAVE NOT |
| BEEN APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. |
| |
| 22) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLAN SHEETS IN ORDER |
| TO ADDRESS THE COMMENTS, PLEASE REMOVE |
| THE OLD SHEETS AND INSERT THE NEW ONES. |
| ONE COPY OF THE OLD PLANS SHEETS SHOULD |
| BE ATTACHED TO FORM A SET OF 'OLD/VOIDED |
| SHEETS' FOR COMPARISON OF REVISIONS WHEN |
| REVIEWING THE RESUBMITTED PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |