2007-03-01 07:36:34DENIED BY BUILDING
  
 1) THE EMBEDMENT POLE CALCULATIONS FROM PCSI ARE
 INCORRECT. THE CALCULATIONS THAT WERE USED ARE FROM FBC
 SECTION 1819.7.2.1 WHICH ONLY APPLIES TO THE HIGH
 VELOCITY HURRICANE ZONE. THE PROJECT IS LOCATED IN THE
 CITY OF WEST PALM BEACH, WHICH IS NOT LOCATED IN THE
 HVHZ.
  
 2) THE LATERAL SOIL BEARING PRESSURE THAT WAS USED IN
 THE CALCULATION WAS BASED ON SEDIMENTARY ROCK. THE
 SUBSURFACE SOIL REPORT FOR THE PROJECT FROM ARDAMAN AND
 ASSOCIATES, INC. INDICATES VERY LOOSE TO MODERATELY
 DENSE SANDS UNDERLYING THE SITE.
  
 3) THE EMBEDMENT DEPTH, HEIGHT ABOVE GROUND, MAXIMUM
 EPA, ETCON THE CUT SHEET ARE INCORRECT. SEE
 ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW