Plan Review Notes
Plan Review Notes For Permit 05120987
Permit Number 05120987
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-21 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PER CITY AMENDMENTS TO THE 2004
 FLORIDA BUILDING CODE 106.1.3, BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM OF 1/8
 INCH SCALE.PLANS INDICATE 3/32.
  
 2.PLAN SHEET M2.1 INDICATES EXHAUST
 FROM THE ELEVATOR EQUIPMENT ROOM BUT
 DOES NOT INDICATE MAKE-UP AIR.PLEASE
 SHOW COMPLIANCE WITH 2004 FMC 403.1.
  
 3.PLEASE PROVIDE ELEVATION OF THE
 DISCHARGE FROM EF-1.PLEASE NOTE,
 EXHAUST SHALL TERMINATE AS TO NOT CREATE
 A NUISANCE.
  
 4.PLEASE INDICATE MEANS OF VENTILATION
 INTO ALL THE MECHANICAL ROOM AREAS.
 SHOW COMPLIANCE WITH 2004 FMC 401.2 &
 401.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.