Plan Review Notes For Permit 05120987 |
Permit Number |
05120987 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-21 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE | | | | 1.PER CITY AMENDMENTS TO THE 2004 | | FLORIDA BUILDING CODE 106.1.3, BUILDING | | PLANS SHALL BE DRAWN TO A MINIMUM OF 1/8 | | INCH SCALE.PLANS INDICATE 3/32. | | | | 2.PLAN SHEET M2.1 INDICATES EXHAUST | | FROM THE ELEVATOR EQUIPMENT ROOM BUT | | DOES NOT INDICATE MAKE-UP AIR.PLEASE | | SHOW COMPLIANCE WITH 2004 FMC 403.1. | | | | 3.PLEASE PROVIDE ELEVATION OF THE | | DISCHARGE FROM EF-1.PLEASE NOTE, | | EXHAUST SHALL TERMINATE AS TO NOT CREATE | | A NUISANCE. | | | | 4.PLEASE INDICATE MEANS OF VENTILATION | | INTO ALL THE MECHANICAL ROOM AREAS. | | SHOW COMPLIANCE WITH 2004 FMC 401.2 & | | 401.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|