Plan Review Notes
Plan Review Notes For Permit 05120987
Permit Number 05120987
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-10 00:00:00******DENIED******
  
 1) KNOX BOX LOCKING CAPS ARE REQUIRED
 FOR FIRE DEPARTMENT CONNECTION.
  
 2) FIRE DEPARTMENT CONNECTION TO BE
 LOCATED NO FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS TO
 BE MOUNTED AT DISTANCE NOT TO EXCEED
 75'.
  
 5) PARKING GARAGE TO COMPLY WITH
 APPLICABLE BUILDING CODES AND NFPA 88A.
  
 6) WILL PROPOSED TENANT SPACE MEET
 SEPARATION REQUIREMENTS?
  
 7) PLEASE PROVIDE CLARIFICATION ON HOW
 AND WHERE PERSONS WILL BE EXITING THE
 BUILDING.
  
 8) THE STAIRWELL DOOR SWINGS ON UPPER
 FLOORS APPEAR TO SWING AGAINST DIRECTION
 OF TRAVEL.
  
 9) PANIC DOORS ARE MENTIONED ON SHT
 A-400, HOWEVER THIS IS NOT ILLUSTRATED
 IN THE DOOR SCHEDULE.
  
 10) THE COOLING TOWER TO COMPLY WITH
 NFPA 214.
  
 11) FIRE ALARM SYSTEM SHALL BE UL LISTED
 FOR CENTRAL STATION SERVICE.
  
 12) NO FIRE SPRINKLER LAY OUT HAS BEEN
 SUBMITTED WITH DRAWINGS.
  
 13) DUCT SMOKE DETECTOR SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 14) ARE SMOKE DETECTORS PLANNED FOR
 ELEVATOR RECALL?
  
 15) IT WOULD APPEAR THAT MORE
 AUDIBLE/VISUAL DEVICES ARE NEEDED ON
 UPPER FLOORS.
  
 16) EXIT LIGHTS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'.
  
 17) PLEASE EXPLAIN WHY EXIT SIGNS DIRECT
 PERSONS INTO STAIWELLS ON FLOOR #1.
  
 18) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  