Date |
Text |
2006-03-10 00:00:00 | ******DENIED****** |
| |
| 1) KNOX BOX LOCKING CAPS ARE REQUIRED |
| FOR FIRE DEPARTMENT CONNECTION. |
| |
| 2) FIRE DEPARTMENT CONNECTION TO BE |
| LOCATED NO FURTHER THAN 150' FROM A FIRE |
| HYDRANT. |
| |
| 3) SEPARATE SHOP DRAWINGS AND PERMITS |
| REQUIRED FOR FIRE SPRINKLER AND FIRE |
| ALARM SYSTEMS. |
| |
| 4) 2A-10B,C RATED FIRE EXTINGUISHERS TO |
| BE MOUNTED AT DISTANCE NOT TO EXCEED |
| 75'. |
| |
| 5) PARKING GARAGE TO COMPLY WITH |
| APPLICABLE BUILDING CODES AND NFPA 88A. |
| |
| 6) WILL PROPOSED TENANT SPACE MEET |
| SEPARATION REQUIREMENTS? |
| |
| 7) PLEASE PROVIDE CLARIFICATION ON HOW |
| AND WHERE PERSONS WILL BE EXITING THE |
| BUILDING. |
| |
| 8) THE STAIRWELL DOOR SWINGS ON UPPER |
| FLOORS APPEAR TO SWING AGAINST DIRECTION |
| OF TRAVEL. |
| |
| 9) PANIC DOORS ARE MENTIONED ON SHT |
| A-400, HOWEVER THIS IS NOT ILLUSTRATED |
| IN THE DOOR SCHEDULE. |
| |
| 10) THE COOLING TOWER TO COMPLY WITH |
| NFPA 214. |
| |
| 11) FIRE ALARM SYSTEM SHALL BE UL LISTED |
| FOR CENTRAL STATION SERVICE. |
| |
| 12) NO FIRE SPRINKLER LAY OUT HAS BEEN |
| SUBMITTED WITH DRAWINGS. |
| |
| 13) DUCT SMOKE DETECTOR SHALL INITIATE A |
| GENERAL FIRE ALARM IN ACCORDANCE WITH |
| LOCAL REQUIREMENTS. |
| |
| 14) ARE SMOKE DETECTORS PLANNED FOR |
| ELEVATOR RECALL? |
| |
| 15) IT WOULD APPEAR THAT MORE |
| AUDIBLE/VISUAL DEVICES ARE NEEDED ON |
| UPPER FLOORS. |
| |
| 16) EXIT LIGHTS TO BE MOUNTED AT |
| DISTANCES NOT TO EXCEED 100'. |
| |
| 17) PLEASE EXPLAIN WHY EXIT SIGNS DIRECT |
| PERSONS INTO STAIWELLS ON FLOOR #1. |
| |
| 18) PLEASE PROVIDE MANUFACTURER SPEC |
| SHEETS FOR GENERATOR. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLANS REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |