Date |
Text |
2006-02-10 00:00:00 | *** PLEASE SEE NOTES UNDER MAIN BLDG |
| ALSO FOR ADDRESS. |
| |
| PLEASE KNOW, THE LEGAL PROPERTY MAY NOT |
| CHANGE AS THE ELECTRICAL SERVICEAND |
| GENERATORS COME FROM GARAGE BLDG TO MAIN |
| BLDG. |
| PLEASE SEE ANY LEGAL PROPPERTY PCN |
| CHNAGE ETC WILL REQUIRE LEGAL EASEMENTS |
| ETC. |
2006-02-01 00:00:00 | ********** UNSAT ********** |
| |
| ** PLEASE KNOW, PLANS AND SUBMITTIALS |
| ARE NOT COMPLETE AT THIS TIME. |
| |
| |
| 1)NOTE: PLEASE SEE ALL CURRENT CODES |
| SHALL BE REFERENCED TO THE CURRENT CODES |
| IN EFFECT. PLEASE SEE PLANS CALL FOR |
| 2001 FLORIDA BUILDING CODE. PLEASE KNOW, |
| AS OF OCT 1ST, 2005 THE NEW FBC IS THE |
| 2004 EDITION. PLEASE SEE THE FOLLOWING |
| SHALL BE REFERENCED. 2003 NFPA-101, 2002 |
| NFPA-70, AND 2002 NFPA-72 |
| |
| 2)NOTE: PLANS WILL REQUIRED BATTERY BACK |
| UP LT FIXTURES IN MAIN ELECTRICAL RM, |
| ELEVATOR RMS. |
| PLEASE ALSO KNOW BATTERY BACK UP |
| FIXTURES WILL BE REQUIRED IN STAIRWAY |
| AND EGRESS PATHS TO PROVIDE A MIN OF 1FT |
| CANDLE OF LIGHT BY SOME SORT OF BATTEY |
| BACK UP FIXTURE. PLEASE SEE NFPA-101 |
| 7.9.2.2, TRIPPING OR SHUTTING OFF ANY |
| SINGLE DEVICE OR MEANS OF OVERCURRENT |
| PROTECTION SHALL NOT LEAVE ANY ONE |
| EGRESS PATH IN TOTAL DARKNESS. |
| PLEASE PROVIDE PHOTOMETRICS FOR |
| STAIRWAYS, AS THE 2003 LS 101 7.8.1.3 |
| REQUIRES A MIN OF 10FY CANDLES(108LUX) |
| IN STAIRWAYS UNDER NORMAL LIGHTING |
| CONDITIONS AND 7.9.2.2 PERMITS THE |
| DERATING TO A MIN OF 1FT CANDLE UNDER |
| EMERGENCY CONDITIONS. |
| 700.16.,700.12E ETC |
| |
| 3)NOTE: PLEASE SEE POSSIBLE BLDG |
| COMMENTS AS STAIRWAY DOORS SEEM TO SWING |
| IN, INSTEAD OF THE DIRECTION OF EGRESS. |
| PLEASE SEE ANY POSSIBLE COMMENTS WITH |
| RESPECT TO THE "FUTURE" TENANT SPACE. |
| (GYM). |
| |
| 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| SPECS/CUT SHEETS FOR GENERATOR, ATS, |
| ETC. PLEASE PROVIDE SPECS FOR ANY TANKS |
| FOR THE PRIME-MOVER OF GEN. |
| PLEASE BE SURE ALL SPECS ETC INDICATE |
| LISTINGS FROM A NRTL. |
| NO REVIEW CAN BE DONE AT THIS TIME. |
| |
| 5)NOTE: PLEASE SEE NO MAIN IS SHOWN ON |
| THE LINE-SIDE OF ATS SHOWN. PLEASE SEE |
| THE FOLLOWING COMMENT WITH RESPECT TO |
| GFP FOR SYSTEMS 277/480V 1000A'[S OR |
| MORE. |
| 230.70,ETC. |
| |
| 6)NOTE: PLEASE SEE ATS MANUFACTUREA S |
| GFP IS REQUIED BY THE NEC FOR SERVICE |
| AND MAY REQUIRE A 4-POLE ATS FOR GFP TO |
| WORK CORRECTLY. |
| PLEASE PROVIDE INFORMATION; PLEASE SEE |
| GENERATOR IS ALREADY SHOWN AS A |
| SEPARATELY DERIVED SYSTEM AS REQUIRED, |
| HOWEVER NOT ENOUGH ATS INFORMATION IS |
| SUBMITTED FOR CORRELATION OF REVIEW FOR |
| CODE COMPLIANCE. |
| EXAMPLE, PLEASE SEE TEXT TAKEN FROM |
| ASCO: |
| "WHERE GROUND FAULTPROTECTION IS |
| TRIGGERED BY THE CODE AND AN ALTERNATE |
| POWER SUPPLY IS INCLUDED,SWITCHING OF |
| THE NEUTRAL BECOMES NECESSARY. THE |
| CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A |
| CIRCUMSTANCE. THE SERVICE IS LARGER THAN |
| 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT |
| PROTECTION IS REQUIRED AT THE MAIN |
| SERVICE DISCONNECT AT A MINIMUM. IF IT |
| IS INSTALLED THERE AND THE GENERATOR |
| NEUTRAL GROUNDING WAS THROUGH A SOLID |
| CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| A GROUND FAULT WHEN THE GENERATOR IS |
| FEEDING THE LOAD WILL CAUSE THE MAIN |
| SERVICE DISCONNECT TO OPEN. THIS WILL |
| NOTDISCONNECT THE ARCING FAULT FROM |
| THE GENERATOR. COORDINATION IS THUS |
| LOST." |
| |
| 7)NOTE: PLEASE SEE SERVICE MAINS AS |
| REQUIRED DO NOT INDICATE ANY GFP PER |
| 230.95,240.13 ETC. |
| |
| 8)NOTE: PLEASE LABEL ALL MAINS, 1, 2, 3 |
| ETC, 1OF? 2 OF ? ETC. |
| |
| 9)NOTE: PLEASE PROVIDE ONE LINE |
| GROUNDING ELECTRODE DIAGRAM FOR BLDG, TO |
| INCLUDE GROUNDING ELECTRODE RISER FOR |
| ANY TRANSFORMERS. 250.30,250.58 |
| |
| 10)NOTE: PLEASE SEE PANELS , (MDP WHICH |
| ARE NOT COMPLETE AT THIS TIME. PLEASE |
| SEE SOME AREA OF PANELS WHERE XXX'S ARE |
| SHOWN FOR REQUIRED INFORMATION. |
| PLEASE SEE "GGP" WHERE BRANCH CIRCUIT |
| INFORMATION APPEARS IN THE TITLE BLOCK |
| OF SAID PANEL. |
| PLEASE SEE OTHER PANELS WHERE ALL |
| INFORMATION INDICATED IS SHOWN AS |
| "SPARE"? PLEASE SPECIFY "FUTURE" USE AND |
| FOR WHAT LOADS THESE WILL FEED. |
| |
| 11)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| AND PANELS. |
| PLEASE SEE "GLH", "GMDP", GLH", ETC, |
| THESE ARE SHOWN BEING FED FROM OTHER |
| EQUIPMENT ON RISER THAN LISTED ON PANEL |
| SCHEDULES. |
| PLEASE ALSO SEE "GDP", "GGP", AND "GLP", |
| PLEASE SEE RISER, PLEASE SEE "T1B" AS |
| THIS IS FED FROM TWO SEPARATE PANELS, |
| AND CORRELATE WIRTH RISER. |
| 215.5 |
| |
| 12)NOTE: PLEASE SEE NOTES FOR |
| DISTRIBUTION SYSTEM MENTIONS TO EXTEND |
| TO MAIN BLDG, PLEASE SEE NOTES FROM MAIN |
| BLDG REVIEW WHEN COMPLETED AS THIS MAY |
| AFFECT ELECTRICAL SERVICE OR DESIGN AS |
| SHOWN. |
| |
| 13)NOTE: PLEASE COMPLETE ALL SERVICE |
| ENTRANCE CONDUCTORS ON RISER ALONG WITH |
| ALL FEEDERS. |
| PLEASE SEE MISSING SEC'S TO EM SYSTEM, |
| ATS OR NEW MAIN DISCONNECT, PLEASE SEE |
| MISSING FEEDERS FROPM GEN, PLEASE SEE |
| MISSING SEC'S TO GMDP, ATS TO GDP ETC . |
| PLEASE COMPLETE RISER. |
| |
| 14)NOTE: PLEASE SEE MISSING OVERCURRENT |
| PROTECTION AT GENERATOR. PLEASE ALSO SEE |
| MISSING LOAD CALCUALTIONS FOR INTENDED |
| LOAD FOR GENERATOR. |
| PLEASE ALSO SEE FOLLOWING COMMENT. |
| |
| 15)NOTE: PLEASE COMPLETE AND SUBMIT MIN |
| LOAD CALCUALTIONS AS REQUIRED PER |
| NEC.220 |
| PLEASE SEE ALL MAIN DISTRIBUTIION |
| SYSTEMS ARE SHOWING "BLANKS" FOR LOADS?? |
| PLEASE BE SURE TO INDICATE ALL LOADS. NO |
| REVIEW OF THESE CAN BE DOINE AT THIS |
| TIME. |
| 215.5 |
| |
| 16)NOTE: PLEASE SEE NOTES FOR GENERATORS |
| AS INDICATED ON ELECTRICAL PLANS WHICH |
| NOTES ALL GENERATOR CONDUITS PROCEEDING |
| TO THE MAIN OFFICE BLDG?? |
| PLEASE INDICATE WHERE GENFOR GARAGE IS |
| LOCATED? |
| PLEASE ALSO SEE COMMENTS FOR MAIN BLDG |
| AS THESE NOTES INDICATE ALL THESE |
| FEEDERS SHALL PROCEED TO THE FIRST FLR |
| MAIN ELECTRICAL ROOM, HOWEVER THIS DOES |
| NOT SEEM TO CORRELATE WITH WHAT IS SHOWN |
| ON MAIN BLDG PLANS. |
| 215.5 |
| |
| 17)NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP |
| INFORMATION NEEDED. |
| |
| 18)NOTE: PELASE SEE LIGHTING |
| REQUIREMENTS UNDER 13-415 FOR AREAS OF |
| CONTROL AND TANDEM WIRING. |
| PLEASE SPECIFY THIS INFORMATION ON |
| PLANS. |
| |
| 19)NOTE: PLEASE SEE LANDSCAPE PLANS |
| MENTIONS AND NOTES LIGHTING AND TO SEE |
| ELECTRICAL PLANS FOR THESE, HOWEVER |
| THESE ITEMS COULD NOT BE LOCATED ON |
| ELECTRICAL PLANS. |
| PLEASE SUBMIT WIND LOAD CALCUALTIONS FOR |
| ALL SITE LIGHTING POLES TO MEET FBC 140 |
| MPH. |
| |
| 20)NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| SEALED "PHOTO-COPIES" OF ARCHITECT'S |
| SIGNATURE. PLEASE SEE FS 481.221 WHICH |
| REQUIRES THE SIGNATURE TO BE AN ORIGINAL |
| SIGNATURE. |
| |
| ** PLEASE KNOW, REVIEW FOR MAIN BLDG HAS |
| NOT COMMENCED AT THIS TIME. |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ON.Y INSERT NEW REVISED SHEETS INTO |
| COMPLETED SETS FOR REVIEW AND STAMPING. |
| ONLY SUBMIT ONE COPY OF OLD/VOIDED |
| SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| DPALMER2WPB.ORG |
| |
| |
| |