2006-04-17 00:00:00 | DENIED BY BUILDING |
| |
| 1621 WORTHINGTON ROAD |
| 5 STORY PARKING GARAGE |
| TYPE II-A (SPRINKLERED) |
| MIXED OCCUPANCY (S-2 STORAGE & |
| BUSINESS) NOTE: PLUMBING SHEET P3.4 |
| INDICATES A FUTURE GYM WHICH WOULD BE AN |
| ASSEMBLY OCCUPANCY. |
| FLOOD ZONE A9 BFE 13' (+6"CITY REQ.) |
| REQUIRED SOIL BEARING PER PLANS 2,000 |
| PSF |
| |
| 1) STRUCTURE IS LOCATED IN AN A9 FLOOD |
| ZONE AN ELEVTION CERTIFICATE WILL BE |
| REQUIRED. ALL EQUIPMENT MUST ALSO BE |
| LOCATED 6" ABOVE REQUIRED BFE. |
| |
| 2) SUBMIT A SIGNED AND SEALED SURVEY. |
| INDICATE THE LOCATION OF THE ASSUMED |
| PROPERTY LINE BETWEEN THE PROPOSED |
| PARKING GARAGE AND THE PROPOSED BUILDING |
| TO THE WEST. SEE FIRE SEPARATION |
| DISTANCE FBC 702.1 AND 704.3. |
| |
| 3) FBC 1802.2.1AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 5)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 6) SUBMIT FIRE SPRINKLER DRAWINGS AS |
| REQUIRED BY FBC 106.3.5. |
| |
| 7) FBC 13-103.0ENERGY CODE COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE CODE COMPLIANCE FORMS. |
| FBC 13-101.1.6SHELL BUILDINGS. |
| THE WHOLE BUILDING (INCL. FUTURE TENANT |
| SPACE) SHALL BE CONSIDERED.SHELL |
| BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| METHOD B (SEE SUB-CHAPTER 4).ALL |
| ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| SHOWN ON THE CURRENT PLANS, SHALL BE |
| LISTED AND APPENDED TO THE FORM 400B FOR |
| SUBMITTAL.THIS WILL BE COMPARED, AT A |
| LATER DATE, TO THE ACTUAL SYSTEMS |
| PROPOSED BY THE FUTURE TENANT(S).THE |
| ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| SHALL BE AT LEAST THE MINIMUM STANDARD |
| (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| BUILDING TO BE OCCUPIED FOR IT'S |
| INTENDED PURPOSE. |
| |
| 8) FBC* 109.3.6.1SPECIAL INSPECTOR.A |
| STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED PRIOR TO THE ISSUANCE OF A |
| BUILDING PERMIT FOR THE CONSTRUCTION OF |
| A THRESHOLD BUILDING.A THRESHOLD |
| BUILDING IS ANY BUILDING WHICH IS |
| GREATER THAN THREE STORIES OR 50 FEET IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY |
| OCCUPANCY WITH 5,000 SQFT AREA AND |
| GREATER THAN 500 OCCUPANTS.THREE |
| COPIES OF THE PLANS AND OTHER DOCUMENTS |
| WILL BE REQUIRED FOR PERMITTING |
| PURPOSES. ALSO, PLEASE ARRANGE WITH |
| HAROLD PISKURA (INSPECTION SERVICES |
| MANAGER - TEL:561 805 6711), A MEETING |
| INVOLVING THE OWNER, THRESHOLD |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND |
| ENGINEER. |
| |
| 9)FBC* 109.3.6.4.4 ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED |
| AND SEALED BY THE ARCHITECT OR ENGINEER |
| OF RECORD CON- TAIN A STATEMENT THAT, TO |
| THE BEST OF THE ARCHITECT'S PR |
| ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 10) FBC* 106.1.3 QUALITY OF BUILDING |
| PLANS. BUILDING PLANS SHALL BE DRAWN TO |
| A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER |
| ACCEPTABLE MEDIUM. |
| |
| 11) FBC 1603.1.4WIND DESIGN DATA.THE |
| PLANS SHALL STATE THE BASIC WIND SPEED, |
| WIND IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES.ADD THIS |
| INFORMATION TO THE PLANS. INFORMATION |
| LEFT BLANK ON SHEET S4.O. |
| |
| 12) THE EDITION OF ASCE 7 REFERENCED IN |
| THE 2004 FBC IS ASCE 7-02. PLEASE REVISE |
| THE EDITIONS OF ASCE 7 SPECIFIED ON |
| SHEET S4.0. |
| |
| 13) SPECIFY ON THE PLANS IF THE |
| STRUCTURE IS DESIGNED AS ENCLOSED, |
| PARTIALLY ENCLOSED OR OPEN. |
| |
| 14) SPECIFY THE SCALE OF THE LIFE SAFETY |
| PLAN FOR THE EQUIPMENT ROOMS ON SHEET |
| A003. |
| |
| 15) SPECIFY THE NEGATIVE AND POSITIVE |
| WINDLOAD PRESSURES FOR THE STOREFRONTS |
| AT THE TENNANT SPACE, THE EXTERIOR DOOR |
| TO THE MECHANICAL ROOMS, AND THE DOORS |
| TO THE EGRESS STAIRS. FBC 1609 |
| |
| 16) NOTE 2 ON S5.0 IS COVERED BY A |
| PRINTING ERROR. PLEASE CORRECT. |
| |
| 17) SUBMIT PRODUCT APPROVALS FOR THE |
| DOOR AND WINDOW OPENINGS SUBJECT TO |
| WINDLOADING, ROOFING MATERIALS, STORM |
| PANELS, ETC. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE WWW. |
| FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| (IF YOU FIND THAT THE QUOTED WEB PAGE IS |
| NO LONGER AVAILABLE, PLEASE INFORM THE |
| PLAN REVIEWER) |
| FBC 106.3.3*(CITY AMENDMENTS) REQUIRES |
| PRODUCTS REGULATED BY DCA RULE 9B-72 TO |
| BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 18) SUBMIT SPECIFICATIONS FOR THE FIRE |
| RATED DOORS, DOOR CLOSERS, HARDWARE, |
| ETC. |
| |
| 19) PLEASE REVISE OCCUPANCY TYPE FOR |
| FUTURE GYMNASIUM TO GROUP A (ASSEMBLY, |
| A-3). REVISE OCCUPANT LOAD CALCS., |
| TENANT SEPARATION, ETC. ACCORDINGLY. THE |
| PARKING AREA AND STORAGE AREA ARE GROUP |
| S-2 STORAGE. |
| |
| 20) ON SHEET S1.0 SOME OF THE SECTION |
| MARKERS ARE NOT AT THE PROPER LOCATIONS. |
| PLEASE CORRECT. |
| |
| 21) ON SHEET S2.0 THERE ARE TWO |
| DIFFERENT SECTION DRAWINGS LABELED |
| 5/S2.0. SECTION 6/S2.0 SHOULD BE LABELED |
| AS 7/S2.0. |
| |
| 22) PROVIDE A COLUMN SCHEDULE. SEE NOTE |
| 14 ON S1.0. |
| |
| 23) SHEETS S1.1 AND A1.2 HAVE SECTIONS |
| MARKED X/X. PLEASE CLARIFY. |
| |
| 24) MARKS 5/S3.0 ON SHEET S1.1 MARK |
| 6/S3.0 ON SHEET S1.2 ARE NOT AT THE |
| CORRECT LOCATIONS. PLEASE CORRECT. |
| |
| 25) PLEASE REVISE NOTE 8.06 ON A000 TO |
| COMPLY WITH THE 2004 FLORIDA BUILDING |
| CODE. SEE FBC 1609.1.4. |
| |
| 26) THE NUMBERS OF PARKING SPACES LISTED |
| FOR THE FIRST FLOOR ON A002 AND A003 DO |
| NOT CONCUR. |
| |
| 27) THE ELEVATOR SHALL COMPLY WITH FBC |
| 11-4.10 FOR ACCESSIBILITY AND WITH ASME |
| A17.1-1990, 'SAFETY CODE FOR ELEVATORS |
| AND ESCALATORS'. |
| |
| 28) FBC 3002.4STRETCHER ACCESSIBLE |
| ELEVATOR.AT LEAST ONE PASSENGER |
| ELEVATOR SHALL ACCOMMODATE AN AMBULANCE |
| STRETCHER 76" LONG AND 24" WIDE IN THE |
| HORIZONTAL POSITION.THIS ELEVATOR |
| SHALL BE IDENTIFIED BY SIGNAGE.AMEND |
| THE PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 29) FBC 11-4.1.2(5)(B) REQUIRES ONE IN |
| EVERY EIGHT ACCESSIBLE SPACES TO BE VAN |
| ACCESSIBLE AND BE DESIGNED AS REQUIRED |
| BY SECTION 11-4.6.3. BASED ON THE NUMBER |
| OF ACCESSIBLE SPACES, TWO VAN ACCESSIBLE |
| SPACES ARE REQUIRED. FBC 11-4.6.4 |
| REQUIRES VAN ACCESSIBLE SIGNAGE. FBC |
| 11-4.6.5 REQUIRES 98" MINIMUM VERTICAL |
| CLEARANCE AT THE VAN ACCESSIBLE PARKING |
| SPACES AND ALONG THE ACCESS ROUTE TO AND |
| EXITS FROM SUCH SPACES. NO SPRINKLER |
| PIPING, ROOF DRAIN PIPING, ETC. WITHIN |
| THE REQUIRED 98" CLEARANCE. SHOW |
| COMPLIANCE. |
| |
| 30)FBC 406.2.2 REQUIRES THE CLEAR HEIGHT |
| OF EACH FLOOR LEVEL IN VECHICAL AND |
| PEDESTRIAN TRAFFIC AREAS TO BE NOT LESS |
| THAN 7 FEET. |
| |
| 31) SHOW COMPLIANCE WITH FBC 11-4.6.2 |
| INDICATE THE ACCESSIBLE ROUTE OF TRAVEL |
| FROM THE PARKING GARAGE TO THE |
| ACCESSIBLE ENTRANCE OF THE BUILDING IT |
| SERVES.ACCESSIBLE PARKING SPACES MUST |
| BE LOCATED ON AN ACCESSIBLE ROUTE NO |
| LESS THAN 44" WIDE SO THAT USERS WILL |
| NOT BE COMPELLED TO WALK OR WHEEL BEHIND |
| PARKED VECHILES. |
| |
| 32) ON SHEET A003 UNDER APPLICABLE |
| CODES, HIGH VELOCITY HURRICANE ZONES, |
| CHAPTERS 15 & 16 DO NOT APPLY TO THIS |
| PROJECT. PLEASE REVISE. CITY OF WEST |
| PALM BEACH IS NOT LOCATED IN THE HVHZ. |
| ALSO ON A003 THE SECTION TITLED |
| HURRICANE CRITERIA CHAPTER 15 & 16 NEEDS |
| TO BE REVISED. SEE NOTES ON PLANS. |
| |
| 33)FBC 11-4.15.2 SPECIFIES THAT |
| ACCESSIBLE DRINKING FOUNTIANS SHALL BE |
| NO HIGHER THAN 36" TO THE SPOUT OUTLET. |
| REVISE DRINKING FOUNTAIN DRAWING ON |
| A006. |
| |
| 34) NOTE 1 ON SHEET A006 FOR FAIR |
| HOUSING GUIDELINES DOES NOT APPLY TO |
| THIS PROJECT. THIS PARKING GARAGE IS NOT |
| ACCESSORY TO A RESIDENTIAL OCCUPANCY. |
| |
| 35) THE FIRE RATING OF THE WALLS IS NOT |
| INDICATED ON THE LIFE SAFETY PLANS, |
| ALTHOUGH THE LEGEND IS GIVEN ON SHEET |
| A003. SPECIFY THE FIRE RATINGS OF THE |
| WALLS AND FLOOR/CEILINGS. |
| |
| 36) THE EXIT FROM THE SOUTHEAST EGRESS |
| STAIR DOES NOT EXIT TO THE EXTERIOR OF |
| THE BUILDING. FBC 406.2.5 DOES NOT ALLOW |
| VECHICLE RAMPS TO SERVE AS AN EXIT |
| ELEMENT. |
| |
| 37) PROVIDE A STAIR DETAIL SPECIFYING |
| THE RISERS, TREADS, VERTICAL RISE |
| BETWEEN LANDINGS, HEADROOM, HANDRAILS, |
| GUARDS, STAIR WIDTH, ETC. PLEASE USE A |
| LARGER SCALE THAN SHOWN ON A2O2 & A203. |
| SEE FBC 1009. |
| |
| 38) NOTE: THE COMMON PATH OF TRAVEL IN |
| THE FUTURE TENNANT SPACE IS ACCEPTABLE |
| FOR A BUSSINESS OCCUPANCY, BUT MAY NOT |
| BE FOR AN ASSEMBLY OCCUPANCY. THE COMMON |
| PATH OF TRAVEL IS 20' FOR ASSEMBLY WITH |
| MORE THAN 50 OCCUPANTS. |
| |
| 39) FBC 1008.1.2 REQUIRES EGRESS DOORS |
| TO SWING IN THE DIRRECTION OF TRAVEL |
| WHERE SERVING AN OCCUPANT LOAD OF 50 OR |
| MORE PERSONS. EGRESS STAIRS DO NOT |
| COMPLY. |
| |
| 40) THE EXIT TO THE EXTERIOR IS NOT |
| SHOWN FOR THE NORTHWEST EGRESS STAIR. |
| THE SITE PLAN ON A001 SHOWS EXTERIOR |
| STAIRS AT THIS LOCATION. PROVIDE |
| DETAILS. |
| |
| 41) THE DOOR SCHEDULE ON A400 LISTS ALL |
| DOORS AS 3-0 X 8-0, THIS APPEARS TO |
| DIFFER WITH THE EGRESS WIDTHS PROVIDED |
| ON THE LIFE SAFETY PLAN AT THE TENNANT |
| SPACE. FBC 1008.1.1 REQUIRES A MINIMUM |
| CLEAR WIDTH OF NOT LESS THAN 32". |
| |
| 42) THE EXIT LIGHTS AT THE ELEVATOR AND |
| DOOR 115 APPEAR TO BE LOCATED |
| INCORRECTLY. THE EXIT LIGHT AT DOOR 116 |
| IS LOCATED SO THAT IT WILL DIRECT PEOPLE |
| BACK INTO THE GARAGE. PLEASE CORRECT. |
| |
| 43) SPECIFY GUARDS AND VECHICLE BARRIERS |
| AS REQUIRED BY FBC 406.2.3 AND 406.2.4 |
| AND DESIGNED IN ACCORDANCE WITH FBC |
| 1607.7. PROVIDE DETAILS. |
| |
| 44) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |