2006-04-17 00:00:00DENIED BY BUILDING
  
 1621 WORTHINGTON ROAD
 5 STORY PARKING GARAGE
 TYPE II-A (SPRINKLERED)
 MIXED OCCUPANCY (S-2 STORAGE &
 BUSINESS) NOTE: PLUMBING SHEET P3.4
 INDICATES A FUTURE GYM WHICH WOULD BE AN
 ASSEMBLY OCCUPANCY.
 FLOOD ZONE A9 BFE 13' (+6"CITY REQ.)
 REQUIRED SOIL BEARING PER PLANS 2,000
 PSF
  
 1) STRUCTURE IS LOCATED IN AN A9 FLOOD
 ZONE AN ELEVTION CERTIFICATE WILL BE
 REQUIRED. ALL EQUIPMENT MUST ALSO BE
 LOCATED 6" ABOVE REQUIRED BFE.
  
 2) SUBMIT A SIGNED AND SEALED SURVEY.
 INDICATE THE LOCATION OF THE ASSUMED
 PROPERTY LINE BETWEEN THE PROPOSED
 PARKING GARAGE AND THE PROPOSED BUILDING
 TO THE WEST. SEE FIRE SEPARATION
 DISTANCE FBC 702.1 AND 704.3.
  
 3) FBC 1802.2.1AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 5)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 6) SUBMIT FIRE SPRINKLER DRAWINGS AS
 REQUIRED BY FBC 106.3.5.
  
 7) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS.
 FBC 13-101.1.6SHELL BUILDINGS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED, AT A
 LATER DATE, TO THE ACTUAL SYSTEMS
 PROPOSED BY THE FUTURE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 8) FBC* 109.3.6.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING
 PURPOSES. ALSO, PLEASE ARRANGE WITH
 HAROLD PISKURA (INSPECTION SERVICES
 MANAGER - TEL:561 805 6711), A MEETING
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND
 ENGINEER.
  
 9)FBC* 109.3.6.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT OR ENGINEER
 OF RECORD CON- TAIN A STATEMENT THAT, TO
 THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10) FBC* 106.1.3 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO
 A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM.
  
 11) FBC 1603.1.4WIND DESIGN DATA.THE
 PLANS SHALL STATE THE BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ADD THIS
 INFORMATION TO THE PLANS. INFORMATION
 LEFT BLANK ON SHEET S4.O.
  
 12) THE EDITION OF ASCE 7 REFERENCED IN
 THE 2004 FBC IS ASCE 7-02. PLEASE REVISE
 THE EDITIONS OF ASCE 7 SPECIFIED ON
 SHEET S4.0.
  
 13) SPECIFY ON THE PLANS IF THE
 STRUCTURE IS DESIGNED AS ENCLOSED,
 PARTIALLY ENCLOSED OR OPEN.
  
 14) SPECIFY THE SCALE OF THE LIFE SAFETY
 PLAN FOR THE EQUIPMENT ROOMS ON SHEET
 A003.
  
 15) SPECIFY THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES FOR THE STOREFRONTS
 AT THE TENNANT SPACE, THE EXTERIOR DOOR
 TO THE MECHANICAL ROOMS, AND THE DOORS
 TO THE EGRESS STAIRS. FBC 1609
  
 16) NOTE 2 ON S5.0 IS COVERED BY A
 PRINTING ERROR. PLEASE CORRECT.
  
 17) SUBMIT PRODUCT APPROVALS FOR THE
 DOOR AND WINDOW OPENINGS SUBJECT TO
 WINDLOADING, ROOFING MATERIALS, STORM
 PANELS, ETC.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
 FBC 106.3.3*(CITY AMENDMENTS) REQUIRES
 PRODUCTS REGULATED BY DCA RULE 9B-72 TO
 BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 18) SUBMIT SPECIFICATIONS FOR THE FIRE
 RATED DOORS, DOOR CLOSERS, HARDWARE,
 ETC.
  
 19) PLEASE REVISE OCCUPANCY TYPE FOR
 FUTURE GYMNASIUM TO GROUP A (ASSEMBLY,
 A-3). REVISE OCCUPANT LOAD CALCS.,
 TENANT SEPARATION, ETC. ACCORDINGLY. THE
 PARKING AREA AND STORAGE AREA ARE GROUP
 S-2 STORAGE.
  
 20) ON SHEET S1.0 SOME OF THE SECTION
 MARKERS ARE NOT AT THE PROPER LOCATIONS.
 PLEASE CORRECT.
  
 21) ON SHEET S2.0 THERE ARE TWO
 DIFFERENT SECTION DRAWINGS LABELED
 5/S2.0. SECTION 6/S2.0 SHOULD BE LABELED
 AS 7/S2.0.
  
 22) PROVIDE A COLUMN SCHEDULE. SEE NOTE
 14 ON S1.0.
  
 23) SHEETS S1.1 AND A1.2 HAVE SECTIONS
 MARKED X/X. PLEASE CLARIFY.
  
 24) MARKS 5/S3.0 ON SHEET S1.1 MARK
 6/S3.0 ON SHEET S1.2 ARE NOT AT THE
 CORRECT LOCATIONS. PLEASE CORRECT.
  
 25) PLEASE REVISE NOTE 8.06 ON A000 TO
 COMPLY WITH THE 2004 FLORIDA BUILDING
 CODE. SEE FBC 1609.1.4.
  
 26) THE NUMBERS OF PARKING SPACES LISTED
 FOR THE FIRST FLOOR ON A002 AND A003 DO
 NOT CONCUR.
  
 27) THE ELEVATOR SHALL COMPLY WITH FBC
 11-4.10 FOR ACCESSIBILITY AND WITH ASME
 A17.1-1990, 'SAFETY CODE FOR ELEVATORS
 AND ESCALATORS'.
  
 28) FBC 3002.4STRETCHER ACCESSIBLE
 ELEVATOR.AT LEAST ONE PASSENGER
 ELEVATOR SHALL ACCOMMODATE AN AMBULANCE
 STRETCHER 76" LONG AND 24" WIDE IN THE
 HORIZONTAL POSITION.THIS ELEVATOR
 SHALL BE IDENTIFIED BY SIGNAGE.AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 29) FBC 11-4.1.2(5)(B) REQUIRES ONE IN
 EVERY EIGHT ACCESSIBLE SPACES TO BE VAN
 ACCESSIBLE AND BE DESIGNED AS REQUIRED
 BY SECTION 11-4.6.3. BASED ON THE NUMBER
 OF ACCESSIBLE SPACES, TWO VAN ACCESSIBLE
 SPACES ARE REQUIRED. FBC 11-4.6.4
 REQUIRES VAN ACCESSIBLE SIGNAGE. FBC
 11-4.6.5 REQUIRES 98" MINIMUM VERTICAL
 CLEARANCE AT THE VAN ACCESSIBLE PARKING
 SPACES AND ALONG THE ACCESS ROUTE TO AND
 EXITS FROM SUCH SPACES. NO SPRINKLER
 PIPING, ROOF DRAIN PIPING, ETC. WITHIN
 THE REQUIRED 98" CLEARANCE. SHOW
 COMPLIANCE.
  
 30)FBC 406.2.2 REQUIRES THE CLEAR HEIGHT
 OF EACH FLOOR LEVEL IN VECHICAL AND
 PEDESTRIAN TRAFFIC AREAS TO BE NOT LESS
 THAN 7 FEET.
  
 31) SHOW COMPLIANCE WITH FBC 11-4.6.2
 INDICATE THE ACCESSIBLE ROUTE OF TRAVEL
 FROM THE PARKING GARAGE TO THE
 ACCESSIBLE ENTRANCE OF THE BUILDING IT
 SERVES.ACCESSIBLE PARKING SPACES MUST
 BE LOCATED ON AN ACCESSIBLE ROUTE NO
 LESS THAN 44" WIDE SO THAT USERS WILL
 NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VECHILES.
  
 32) ON SHEET A003 UNDER APPLICABLE
 CODES, HIGH VELOCITY HURRICANE ZONES,
 CHAPTERS 15 & 16 DO NOT APPLY TO THIS
 PROJECT. PLEASE REVISE. CITY OF WEST
 PALM BEACH IS NOT LOCATED IN THE HVHZ.
 ALSO ON A003 THE SECTION TITLED
 HURRICANE CRITERIA CHAPTER 15 & 16 NEEDS
 TO BE REVISED. SEE NOTES ON PLANS.
  
 33)FBC 11-4.15.2 SPECIFIES THAT
 ACCESSIBLE DRINKING FOUNTIANS SHALL BE
 NO HIGHER THAN 36" TO THE SPOUT OUTLET.
 REVISE DRINKING FOUNTAIN DRAWING ON
 A006.
  
 34) NOTE 1 ON SHEET A006 FOR FAIR
 HOUSING GUIDELINES DOES NOT APPLY TO
 THIS PROJECT. THIS PARKING GARAGE IS NOT
 ACCESSORY TO A RESIDENTIAL OCCUPANCY.
  
 35) THE FIRE RATING OF THE WALLS IS NOT
 INDICATED ON THE LIFE SAFETY PLANS,
 ALTHOUGH THE LEGEND IS GIVEN ON SHEET
 A003. SPECIFY THE FIRE RATINGS OF THE
 WALLS AND FLOOR/CEILINGS.
  
 36) THE EXIT FROM THE SOUTHEAST EGRESS
 STAIR DOES NOT EXIT TO THE EXTERIOR OF
 THE BUILDING. FBC 406.2.5 DOES NOT ALLOW
 VECHICLE RAMPS TO SERVE AS AN EXIT
 ELEMENT.
  
 37) PROVIDE A STAIR DETAIL SPECIFYING
 THE RISERS, TREADS, VERTICAL RISE
 BETWEEN LANDINGS, HEADROOM, HANDRAILS,
 GUARDS, STAIR WIDTH, ETC. PLEASE USE A
 LARGER SCALE THAN SHOWN ON A2O2 & A203.
 SEE FBC 1009.
  
 38) NOTE: THE COMMON PATH OF TRAVEL IN
 THE FUTURE TENNANT SPACE IS ACCEPTABLE
 FOR A BUSSINESS OCCUPANCY, BUT MAY NOT
 BE FOR AN ASSEMBLY OCCUPANCY. THE COMMON
 PATH OF TRAVEL IS 20' FOR ASSEMBLY WITH
 MORE THAN 50 OCCUPANTS.
  
 39) FBC 1008.1.2 REQUIRES EGRESS DOORS
 TO SWING IN THE DIRRECTION OF TRAVEL
 WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS. EGRESS STAIRS DO NOT
 COMPLY.
  
 40) THE EXIT TO THE EXTERIOR IS NOT
 SHOWN FOR THE NORTHWEST EGRESS STAIR.
 THE SITE PLAN ON A001 SHOWS EXTERIOR
 STAIRS AT THIS LOCATION. PROVIDE
 DETAILS.
  
 41) THE DOOR SCHEDULE ON A400 LISTS ALL
 DOORS AS 3-0 X 8-0, THIS APPEARS TO
 DIFFER WITH THE EGRESS WIDTHS PROVIDED
 ON THE LIFE SAFETY PLAN AT THE TENNANT
 SPACE. FBC 1008.1.1 REQUIRES A MINIMUM
 CLEAR WIDTH OF NOT LESS THAN 32".
  
 42) THE EXIT LIGHTS AT THE ELEVATOR AND
 DOOR 115 APPEAR TO BE LOCATED
 INCORRECTLY. THE EXIT LIGHT AT DOOR 116
 IS LOCATED SO THAT IT WILL DIRECT PEOPLE
 BACK INTO THE GARAGE. PLEASE CORRECT.
  
 43) SPECIFY GUARDS AND VECHICLE BARRIERS
 AS REQUIRED BY FBC 406.2.3 AND 406.2.4
 AND DESIGNED IN ACCORDANCE WITH FBC
 1607.7. PROVIDE DETAILS.
  
 44) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714