2006-01-13 00:00:00 | DENIED |
| |
| REFERENCE:FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR GAS PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). INDICATE THESE LOADS ON THE |
| ISOMETRIC DRAWING |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| 5. THE 48" GAS RANGE LOOKS COMERCIAL |
| GRADE. PLEASE SUBMIT A COPY OF PRODUCT |
| LISTING FROM MANUFACTURE STATING RANGE |
| IS ACCEPTABLE FOR RESIDENTIAL USE. MAKE |
| SURE MODEL NUMBER BEING INSTALLED IS ON |
| THIS LISTING. SEE FBC-2004 FUEL GAS SEC- |
| TION 623.2 |
| |
| PLAN REVIEW BY MIKE PERSON |