2005-12-21 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600C-04 (2004) PER FBC 13-600.3.C .
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER OR AGENT.
  
 3) A/C EQUIPMENT MUST BE LISTED ON PLANS
 (MANUFACTURE, MODEL NUMBER, SEER, TOTAL
 BTU'S, SENSIBLE BTU'S, COPPER LINE
 SIZE).
  
 4) PLANS NEED NAME OF PERSON RESPONSIBLE
 AND SIGNATURE.
  
 5) PARTS OF 2ND. COPY OF PLANS ARE NOT
 LEGIBLE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.