Plan Review Notes For Permit 05120865 |
Permit Number |
05120865 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-05 00:00:00 | NOTE: DUPLICATE PERMIT AND STAMPED PLANS | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. MINIMUM 3,750 CUBIC FEET | | REQUIRED. | | | | IF DRYER ROOM IS A CONFINED SPACE, | | OPENINGS REQUIRED PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,000 CUBIC FEET REQUIRED |
|