Text |
2006-04-18 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED |
| |
| 2-5.)ADDRESSED. |
| |
| 6.)WHERE IS THE EXTERIOR WALL AT THE |
| ENTRY?IS THIS LOCATION CHANGING?ARE |
| THE FRENCH ENTRY DOORS SHOWN NEW OR |
| EXISTING?IF THEY ARE NEW, PROVIDE |
| PRODUCT APPROVALS.NOTE THAT IMPACT |
| PROTECTION IS REQUIRED FBC EB 507.3, |
| FBC16091.4.USE OF REMOVABLE SHUTTERS |
| FOR COMMERCIAL BUILDINGS MUST BE |
| APPROVED BY THE BUILDING OFFICIAL. |
| PLEASE CONTACT ME IF THIS IS YOUR |
| INTENT.RESUBMITTING WITH PLANS SHOWING |
| USE OF REMOVABLE SHUTTES WITHOUT AN |
| APPROVED INSTALLATION PLAN WILL RESULT |
| IN A DELAY OF PERMIT ISSUANCE. |
| |
| NOT ADDRESSED.IT IS NOW DETERMINED |
| THAT AN EXTERIOR WALL IS BEING RELOCATED |
| AND THAT NEW DOORS ARE BEING INSTALLED. |
| NO PRODUCT APPROVALS SUBMITTED.PRODUCT |
| APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| OF RECORD, FBC*106.3.3.AGAIN, FAILURE |
| TO PROPERLY ADDRESS THIS COMMENT WILL |
| RESULT IN A DELAY OF PERMIT ISSUANCE. |
| |
| 7-8.) ADDRESSED. |
| |
| 9.)IF THE BUILDING IS REQUIRED TO BE |
| SPRINKLED BY CODE, SUPPLY FIRE SPRINKLER |
| PLANS. |
| |
| NOT ADDRESSED.HAVING A SUBCONTRACTOR |
| SUBMIT SHOPS AT A FUTURE DATE IS NOT |
| SHOWING CODE COMPLIANCE ON THIS PLAN. |
| PROVIDE A FIRE SPRINKLER PLAN AS |
| REQUIRED BY FBC*106.3.5.1.1(5) AND |
| FLORIDA STATUTE. |
| |
| 10.)DECLARE GOVERNING CODE.IF |
| EXTERIOR ALTERATIONS ARE INCLUDED IN |
| THIS PROJECT, PROVIDE WIND DESIGN |
| INFORMATION FBC1603.1.4. |
| |
| THE ARCHITECT REFERS TO THE STRUCTURALS, |
| THE ENGINEER HAS STATED THAT NO EXTERIOR |
| WORK IS TO BE DONE.YOU ARE RELOCATING |
| AN EXTERIOR WALL AND INSTALLING EXTERIOR |
| DOORS.THIS IS EXTERIOR WORK.PROVIDE |
| INFORMATION REQUESTED, INCLUDING DESIGN |
| PRESSURES FOR THE NEW DOORS. |
| |
| 11-13.)ADDRESSED. |
| |
| 14.)THE RAMP IS TO COMPLY WITH |
| FBC11-4.8.NO DETAIL OR SLOPE WAS |
| PROVIDED.IF HANDRAILS ARE REQUIRED, |
| THEY ARE TO COMPLY WITH FBC11-4.8.5. |
| PROVIDE SLOPE AND ELEVATION CHANGE.THE |
| RAMP APPEARS TO LEAD TO THE REAR AREA, |
| WHICH WOULD IMPLY THAT THE HEAVY DASHED |
| LINE IS NOT A WALL.PLEASE PROVIDE A |
| LEGEND FOR CLARIFICATION. |
| |
| YOU HAVE CHANGED THE LINE FROM A DASHED |
| TO A SOLID, AND A LETTER STATING THAT |
| HIS DELINEATES THE WORK AREA.PROVIDE A |
| LEGEND ON THE PLAN AS REQUESTED AS A |
| RESPONSE LETTER IS TO ASSIST IN PLAN |
| REVIEW, NOT TO SHOW CODE COMPLIANCE, AND |
| THE LETTER IS NOT A PART OF THE PLAN. |
| |
| PROVIDE ELEVATIONS AS REQUESTED.THE |
| ARCHITECT HAS RESPONDED THAT HANDRAILS |
| ARE NOT NECESSARY.ACCESSIBILITY |
| REQUIRED TO ALL AREAS.PROVIDE THE |
| INFORMATION REQUESTED.THE PLANS ARE TO |
| SHOW CODE COMPLIANCE. |
| |
| 15.)ADDRESSED. |
| |
| 16.)HOW IS THE STAGE ACCESSIBLE?IT |
| IS NOT CLEAR IF THE DARK LINE IS A WALL |
| OR IF IT IS DELINEATING THE LINE BETWEEN |
| THE AREA OF WORK AND AREA NOT INCLUDED |
| IN THE REMODEL. |
| |
| VERTICAL ACCESSIBILITY REQUIRED, EITHER |
| IN THE FORM OF A PERMANENT RAMP OR A |
| LIFT, FBC11-4.1(1), 11-4.1.2(2), |
| 11-4.1.6(1)(B). |
| |
| 17.)SHOW COMPLIANCE WITH FBC11-5.NO |
| DETAILS IN REGARDS TO ACCESSIBILITY WERE |
| SHOWN. |
| |
| SEE ITEM 16.THE RAMP PREVIOUSLY SHOWN |
| ON THE PLAN IS NO LONGER ON THE PLAN. |
| THE RAMP IMPLIES A CHANGE OF ELEVATION. |
| OLD SHEETS WERE NOT INCLUDED IN THIS |
| RESUB.SHOW ELEVATION CHANGES ON THE |
| PLAN, INCLUDING IN THE AREA HATCHED AS |
| AN AREA NOT PART OF THE REMODEL.THERE |
| STILL MUST BE AN ACCESSIBLE ROUTE FROM |
| THE NEW AREA TO THE EXISTING AREA. |
| |
| NEW COMMENTS: |
| |
| 18.)TWO COPIES OF ALL DOCUMENTS |
| REQUIRED.ONLY ONE SET OF ENGINEERING |
| WAS SUBMITTED. |
| |
| 19.)WAS A SOILS INVESTIGATION REPORT |
| DONE TO DETERMINE SOIL BEARING CAPACITY? |
| IF IT WAS, PROVIDE TWO SIGNED, SEALED |
| ORIGINALS.IF NOT, THIS PERMIT WILL BE |
| ISSUED WITH A PROVISO THAT A SOILS |
| INVESTIGATION REPORT WILL BE REQUIRED |
| BEFORE FIRST INSPECTION. |
| |
| 20.)SEE ATTACHED FS553.80(2)(B).A 4X |
| PLAN REVIEW WILL BE CHARGED IF THE |
| COMMENTS ARE NOT PROPERLY ADDRESSED IN |
| THE THIRD REVIEW. |
| |
| |