Plan Review Notes
Plan Review Notes For Permit 05120772
Permit Number 05120772
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-20 00:00:00****UNSAT ****
  
  
 1)NOTE: PLEASE INDICATE THE NEW
 CIRCUTING ON PLANS AND CORRELATE WITH A
 PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE SEE NEW BAR ARE ETC.
 215.5, 408.4
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM AND EXT LTS. THESE SAHLL BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FEEDING LOCAL LIGHTING.
  
 2)NOTE: PLEASE INDICATE A NEW OR
 EXISTING SIGN CIRCUIT AS REQUIRED PER
 600.5
  
 3)NOTE: PLEASE INDICATE THE SWITCHING
 FOR LIGHTING, FANS ETC ON PLANS.
  
 4)NOTE: PLANS SHOULD REFLECT THE CURRENT
 CODES IN EFFECT AS FOLLOWS.
 NFPA-101 2003, NFPA-72 2002, NFPA-70
 2002.
  
 5)NOTE: PLEASE INDICATE ANY NEW OR
 EXISTING LOADS BEING ADDED. PLEASE SE
 THE NUMBER OF RECEPTS BEING ADDED IS
 GREATER THAN THE EXISTING. PLEASE
 INCLUDE THE ADDED LOADS TO SERVICE AND
 VERIFY LOAD ON EXISTING SERVICE.
 220,215.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]