2006-02-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2.)SOME OF THE SHEETS ON A THIRD SET
 OF ENGINEERING ARE NOT SEALED.ONLY TWO
 SETS ARE REQUIRED FOR PERMITTING; EITHER
 HAVE THE UNSEALED SHEETS SEALED OR
 RETAIN THEM AND SUBMIT TWO SETS.
  
 3.)THE SITE PLAN HAS TWO SEPARATE
 PARCELS HIGHLIGHTED, BOTH 313 AND 309
 CLEMATIS AND PART OF301 CLEMATIS,
 ENDING IN PARCEL ID NUMBERS 0170, 0180,
 AND 0190 RESPECTIVELY.THE APPLICATION
 IS FOR 309 CLEMATIS.CLARIFY.THE
 IMPROVEMENT CANNOT CROSS OVER PROPERTY
 LINES.
  
 4.)THE EXISTING FLOOR PLAN PREPARED BY
 THE ENGINEER SHOWS ONE TENANT SPACE.
 THE ARCHITECT?S PLAN HAS A DASHED LINE
 WHICH APPARENTLY SHOWS SCOPE OF WORK.
 IS THIS CORRECT?OR IS THIS A WALL WITH
 A TENANT SEPARATION?USUALLY THE DASHED
 LINE AS SHOWN DEPICTS A 1 HOUR
 SEPARATION.NO WALL LEGEND WAS
 PROVIDED.
  
 5.)AREA 100, OUTDOOR PATIO, IS TO
 MATCH THE ELEVATION OF THE EXISTING
 SIDEWALK.WHAT IS THE ELEVATION
 DIFFERENCE BETWEEN THE NEW OUTDOOR PATIO
 AND THE FINISHED FLOOR OF THE INTERIOR
 (ACCESSIBLE ENTRANCE/EXIT)?SEE FBC11.
  
 6.)WHERE IS THE EXISTING EXTERIOR WALL
 AT THE ENTRY?IS THIS LOCATION
 CHANGING?ARE THE FRENCH ENTRY DOORS
 SHOWN NEW OR EXISTING?IF THEY ARE NEW,
 PROVIDE PRODUCT APPROVALS.NOTE THAT
 IMPACT PROTECTION IS REQUIRED FBC EB
 507.3, FBC1609.1.4.USE OF REMOVABLE
 SHUTTERS FOR COMMERCIAL BUILDINGS MUST
 BE APPROVED BY THE BUILDING OFFICIAL.
 PLEASE CONTACT ME IF THIS IS YOUR
 INTENT.RESUBMITTING WITH PLANS SHOWING
 USE OF REMOVABLE SHUTTERS WITHOUT AN
 APPROVED INSTALLATION PLAN WILL RESULT
 IN A DELAY OF PERMIT ISSUANCE.
  
 7.)NO DETAIL WAS PROVIDED FOR THE
 WALLS/COLUMNS ON EITHER SIDE OF THE
 ENTRY DOORS.IS THIS NEW OR EXISTING?
  
 8.)DECLARE THE TOTAL SQUARE FOOT AREA
 FOR THE SPACE, OCCUPANCY CLASSIFICATION
 FBC 3, OCCUPANT LOAD FBC1004, BUILDING
 TYPE, SPRINKLED OR UNSPRINKLED.
  
 9.)IF THE BUILDING IS REQUIRED TO BE
 SPRINKLED BY CODE, SUPPLY FIRE SPRINKLER
 PLANS.
  
 10.)DECLARE GOVERNING CODE.IF
 EXTERIOR ALTERATIONS ARE INCLUDED IN
 THIS PROJECT, PROVIDE WIND DESIGN
 INFORMATION FBC1603.1.4.
  
 11.)WHY IS THERE A DIFFERENT WALL TYPE
 DEPICTED BETWEEN COLUMN LINES D AND F,
 WEST SIDE?IS THIS A WALL OR OPEN?
  
 12.)SHOW ALL REQUIRED FIRE
 SEPARATIONS, VERTICAL AND HORIZONTAL,
 AND NOTE HOW THIS RENOVATION WILL AFFECT
 THE FIRE SEPARATIONS.SCOPE OF WORK IS
 NOT CLEAR FROM THE PLAN.
  
 13.)WHAT IS THE PURPOSE OF THE NEW
 COLUMNS AND BEAMS?SPECIFY DESIGN
 LOADS.DECLARE OCCUPANCY OF THE SECOND
 FLOOR, WHICH THIS BEAM IS NOW APPARENTLY
 SUPPORTING.
  
 14.)THE RAMP IS TO COMPLY WITH
 FBC11-4.8.NO DETAIL OR SLOPE WAS
 PROVIDED.IF HANDRAILS ARE REQUIRED,
 THEY ARE TO COMPLY WITH FBC11-4.8.5.
 PROVIDE SLOPE AND ELEVATION CHANGE.THE
 RAMP APPEARS TO LEAD TO THE REAR AREA,
 WHICH WOULD IMPLY THAT THE HEAVY DASHED
 LINE IS NOT A WALL.PLEASE PROVIDE A
 LEGEND FOR CLARIFICATION.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE STAGE CONSTRUCTION.
  
 16.)HOW IS THE STAGE ACCESSIBLE?IT
 IS NOT CLEAR IF THE DARK LINE IS A WALL
 OR IF IT IS DELINEATING THE LINE BETWEEN
 THE AREA OF WORK AND AREA NOT INCLUDED
 IN THE REMODEL.
  
 17.)SHOW COMPLIANCE WITH FBC11-5.NO
 DETAILS IN REGARDS TO ACCESSIBILITY WERE
 SHOWN.
  