Plan Review Notes
Plan Review Notes For Permit 05120766
Permit Number 05120766
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-13 00:00:00DENIED
  
 REFERENCE:FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. TYPE OF GAS, (LP OR NATURAL)
 5. THE DRAWING SUBMITTED IS SIZED INCOR-
 RECTLY PLEASE SIZE CORRECTLY USING THE
 FBC-2004 FUEL GAS. SEE ATTACHED LETTERS
 AND FBC -2004 FUEL GAS TABLES.
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  