Plan Review Notes For Permit 05120766 |
Permit Number |
05120766 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-13 00:00:00 | DENIED | | | | REFERENCE:FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PERMIT: | | | | 1.SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 4. TYPE OF GAS, (LP OR NATURAL) | | 5. THE DRAWING SUBMITTED IS SIZED INCOR- | | RECTLY PLEASE SIZE CORRECTLY USING THE | | FBC-2004 FUEL GAS. SEE ATTACHED LETTERS | | AND FBC -2004 FUEL GAS TABLES. | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 | | |
|