Plan Review Notes
Plan Review Notes For Permit 05120748
Permit Number 05120748
Review Stop B
Sequence Number 2
Notes
Date Text
2005-12-16 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- METAL ROOF SYSTEM SPECIFIES THAT MAX.
 UPLIFT PRESSURE IS -57.5PSF. THESE
 PRODUCT DOESN'T MEET THE DESIGN
 PRESSURES SPECIFIED ON TABLE 1609.6B OF
 FBC 2004.
 ***NOTE: TABLE FROM FBC 2004 IS
 PRESCRIPTIVE. ACTUAL UPLIFT CALCULATIONS
 (BY ENGINEER OR ARCHITECT)FOR THIS HOUSE
 MAY BE SUBMITTED TO SEE IF ACTUAL UPLIFT
 PRESSURES MAY BE LOWER.
  
 ALSO, LIMITATION #2 ON PAGE 5 OF 5
 SPECIFIES THAT NOT ADDITIONAL NAIL
 ENHANCING IS ALLOWED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712