Plan Review Notes For Permit 05120748 |
Permit Number |
05120748 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-12-16 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- METAL ROOF SYSTEM SPECIFIES THAT MAX. | | UPLIFT PRESSURE IS -57.5PSF. THESE | | PRODUCT DOESN'T MEET THE DESIGN | | PRESSURES SPECIFIED ON TABLE 1609.6B OF | | FBC 2004. | | ***NOTE: TABLE FROM FBC 2004 IS | | PRESCRIPTIVE. ACTUAL UPLIFT CALCULATIONS | | (BY ENGINEER OR ARCHITECT)FOR THIS HOUSE | | MAY BE SUBMITTED TO SEE IF ACTUAL UPLIFT | | PRESSURES MAY BE LOWER. | | | | ALSO, LIMITATION #2 ON PAGE 5 OF 5 | | SPECIFIES THAT NOT ADDITIONAL NAIL | | ENHANCING IS ALLOWED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|