Plan Review Notes For Permit 05120677 |
Permit Number |
05120677 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-11 00:00:00 | NEED TO SHOW WHAT TYPE OF FIXTURES ARE | | TO BE USED. | | | | NEED TO SHOW VOLTAGE TYPE. | | | | NEED TO SHOW WHERE POWER COMES FROM FOR | | THE LOW VOLTAGE LIGHTS AND THE LOW | | VOLTAGE SIGN.SHOW RISER OR BRANCH | | CIRCUIT NUMBERS THAT FEED THESE LOADS. | | | | NEED CUT SHEETS FOR LIGHTPOLES THAT ARE | | BEING REPLACED. | | | | NEED TO SHOW LOADS FOR REPLACED LIGHTS | | ARE THEY THE SAME AS EXISTING OR SMALLER | | OR BIGGER? | | | | JAKE LEAHY 644-7291 |
|