2005-12-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- CONTRACTOR'S DECLARED VALUE ON THE
 APPLICATION IS EXTEMELY LOW. PROVIDE
 CORRECT VALUATION OR VALUATION MAY BE
 ESTIMATED USING THE MARSHALL-SWIFT OR
 MEANS CONSTRUCTION ESTIMATING BOOK. SEC.
 108.3 CITY AMENDMENTS TO THE FBC 2004.
  
 2- SPECIFY: A) MEAN ROOF HEIGHT, B) TYPE
 OF DECK, C) PROPOSED ROOF SYSTEM AND D)
 SPECIFY IF NEW ROOF, TEAR-OFF OR RECOVER
 ROOF AS REQUIRED BY THE CITY POLICY AND
 PROCEDURE FOR SUBMITTING PRODUCT
 APPROVALS FOR ROOFING/RE-ROOFING
 PERMITS. SEE ATTACHED COPY.
  
 3- PRODUCT APPROVAL SUBMITTED
 LIMITATIONS/CONDITIONS OF USE NOTE #10
 IN PAGE 4 OF 5 REQUIRES MEMBRANE
 FASTENERS WITHDRAWAL TESTING AND A
 QUALIFIED DESIGN PROFESSIONAL. SEE NOTE
 #10 FOR COMPLETE LIMITATION INFORMATION
 AND ADDRESS ISSUE AS REQUIRED.
  
 4- SEE FOOTNOTES FOR TYPE OF DECK TO
 HAVE ROOF INSTALLED TO DETERMINE THE
 MAXIMUM DESIGN PRESSURES. THEN, PROVIDE
 THE REQUIRED CALCULATIONS. EG: SEE
 FOOTNOTE K FOR CONSTRUCTION IN STEEL
 DECKS.
  
 5- DADE COUNTY NOA REPORT SUBMITTED IS
 NOT PART OF THE INFORMATION SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL.
  
 6- BUILDING INSPECTOR PRE-INSPECTION IS
 RECOMMENDED WHEN ROOF-OVERS ARE
 SPECIFIED TO VERIFY COMPLIANCE WITH SEC.
 1510 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.