2005-12-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- CONTRACTOR'S DECLARED VALUE ON THE |
| APPLICATION IS EXTEMELY LOW. PROVIDE |
| CORRECT VALUATION OR VALUATION MAY BE |
| ESTIMATED USING THE MARSHALL-SWIFT OR |
| MEANS CONSTRUCTION ESTIMATING BOOK. SEC. |
| 108.3 CITY AMENDMENTS TO THE FBC 2004. |
| |
| 2- SPECIFY: A) MEAN ROOF HEIGHT, B) TYPE |
| OF DECK, C) PROPOSED ROOF SYSTEM AND D) |
| SPECIFY IF NEW ROOF, TEAR-OFF OR RECOVER |
| ROOF AS REQUIRED BY THE CITY POLICY AND |
| PROCEDURE FOR SUBMITTING PRODUCT |
| APPROVALS FOR ROOFING/RE-ROOFING |
| PERMITS. SEE ATTACHED COPY. |
| |
| 3- PRODUCT APPROVAL SUBMITTED |
| LIMITATIONS/CONDITIONS OF USE NOTE #10 |
| IN PAGE 4 OF 5 REQUIRES MEMBRANE |
| FASTENERS WITHDRAWAL TESTING AND A |
| QUALIFIED DESIGN PROFESSIONAL. SEE NOTE |
| #10 FOR COMPLETE LIMITATION INFORMATION |
| AND ADDRESS ISSUE AS REQUIRED. |
| |
| 4- SEE FOOTNOTES FOR TYPE OF DECK TO |
| HAVE ROOF INSTALLED TO DETERMINE THE |
| MAXIMUM DESIGN PRESSURES. THEN, PROVIDE |
| THE REQUIRED CALCULATIONS. EG: SEE |
| FOOTNOTE K FOR CONSTRUCTION IN STEEL |
| DECKS. |
| |
| 5- DADE COUNTY NOA REPORT SUBMITTED IS |
| NOT PART OF THE INFORMATION SUBMITTED |
| FOR FLORIDA PRODUCT APPROVAL. |
| |
| 6- BUILDING INSPECTOR PRE-INSPECTION IS |
| RECOMMENDED WHEN ROOF-OVERS ARE |
| SPECIFIED TO VERIFY COMPLIANCE WITH SEC. |
| 1510 FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712. |