Plan Review Notes For Permit 05120633 |
Permit Number |
05120633 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-06-26 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- PRODUCT APPROVAL SUBMITTED FOR METAL | | ROOFING IS DIFFERENT THAN ONE SUBMITTED | | IN PREVIOUS SUBMITTAL. PRODUCT APPROVAL | | SUBMITTED NOW IS LIMITED TO 52.5PSF | | DESIGN PRESSURE. NEED TO PROVIDE | | COMPLETERATIONAL ANALYSIS CALCULATIONS | | TO INCREASE THE DESIGN PRESSURES FOR | | PERIMETER AND CORNER AREAS. CALCULATIONS | | MUST BE DONE FOR SPECIFIC TYPE OF METAL | | ROOFING SYSTEM TO BE INSTALLED. SEE | | COMMENT #2 BELOW. | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 | | AND TABLE 1609.6B FBC 2004. | | | | 2- PRODUCT APPROVAL SUBMITTED HAS THREE | | DIFFERENT TYPE OF METAL ROOFING SYSTEMS. | | PROVIDE ONLY THE INFORMATION FOR PANEL | | SYSTEM TO BE INSTALLED. EG: 5V CRIMP | | PANELS, MASTERRIB PANELS OR ADVANTAGELOK | | PANELS. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|