2006-06-08 00:00:00 | REVISION CHECKLIST: |
| 1- CHANGE OF CONTRACTOR REQUIRES |
| NOTARIZED LETTER FROM PREVIOUS |
| CONTRACTOR RELEASING THE PERMIT TO THE |
| NEW CONTRACTOR. |
| |
| 2- NEW CONTRACTOR TO COMPLETE AND SIGN |
| NEW PERMIT APPLICATION. |
| |
| 3- SEE ATTACHED COPY OF CITY POLICY FOR |
| RE-ROOFING PERMITS AND PROVIDE ALL |
| INFORMATION AS REQUIRED. |
| PROVIDE: |
| A) FLAT ROOF SQUARE FOOTAGE AND METAL |
| ROOF SQUARE FOOTAGE TO UPDATE PERMIT |
| VALUATION AND FEES. |
| B) BUILDING MEAN ROOF HEIGHT |
| C) ROOF PITCH. |
| |
| 4- FLAT ROOF SYSTEM PRODUCT APPROVAL |
| SUBMITTED: A) NEED TO PROVIDE PAGES OF |
| SPECIFIC APPROVED ASSEMBLY THAT IS GOING |
| TO BE INSTALLED. SEE APPROVED ASSEMBLIES |
| IN THE DADE COUNTY NOA AND SELECT THE |
| ONE THAT IS GOING TO BE INSTALLED. |
| B) CLEARLY MARK SPECIFIC FASTENING |
| METHOD USED FOR THE BASE SHEET. |
| C) IF SELECTED ASSEMBLY IS LIMITED BY |
| GENERAL LIMITATION #7, THEN PROVIDE |
| CALCULATIONS FOR ENHANCED FASTENING AT |
| CORNER AND PERIMETER AREAS AS REQUIRED |
| BY THIS LIMITATION. SEE LAST PAGE OF NOA |
| GENERAL LIMITATIONS FOR REQ'D INFO. |
| D) IF SELECTED ASSEMBLY IS LIMITED BY |
| GENERAL LIMITATION #9, THEN SUCH SYSTEM |
| DOESN'T WORK FOR THIS AREA. |
| E) NOA SYSTEM SUBMITTED IS MISSING THE |
| LAST PAGE OF THE REPORT, WHICH CONTAINS |
| THE GENERAL LIMITATIONS. |
| |
| 5- GRACE ICE & WATER SHIELD UNDERLAYMENT |
| GENERAL LIMITATION #5 SPECIFIES THAT ALL |
| WORK SHALL BE PERFORMED BY A DADE COUNTY |
| LICENSED ROOFING CONTRACTOR FAMILIARIZED |
| WITH THE SYSTEM. COMPLY WITH THIS |
| LIMITATION. |
| |
| 6- METAL ROOFING PRODUCT APPROVAL: |
| PROVIDE UPDATED FLORIDA PRODUCT APPROVAL |
| COVER PAGE WITH 2004 CODE VERSION. |
| |