2005-12-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM SELECTED IS LIMITED
 BY GENERAL LIMITATION #9 WITH THE MAX.
 DESIGN PRESSURES OF 45PSF. LIMITATION #9
 DOESN'T ALLOW ADDITIONAL NAIL ENHANCING
 TO INCREASE THE UPLIFT RESISTANCE. NEED
 SYSTEM THAT MEETS THE DESIGN PRESSURES
 AS SHOWN ON TABLE 1609.6B OF FBC 2004.
  