2006-12-20 19:39:07 | ** UNSAT ** |
| |
| 1) NOTE:NOTE OK, AS THE ELECTRICAL PERMIT WAS NOT |
| AATCHED IN COMPUTER SYSTEM, PREVIOUS NOTE FOR 4X FEE |
| AND HOLD REMOVED. |
| |
| |
| 2) NOTE: PLEASE COMPLETE PHOTO-METRICS AS PARTIALLY |
| SHOWN FOR HALLWAYS/EGRESS PATHS. |
| PLEASE SEE MINIMUM LIGHTING LEVELS UNDER NORMAL AND |
| EMERGENCY ARE REQUIRED. |
| PLEASE SEE NFPA-101 2003 7.8, 7.9 |
| PLEASE SEE ONLY A PARTIAL HALLWAY IS SHOWN FOR LIGHTING |
| LEVELS WHICH ARE ONLY JUST OVER MINIMUM AND OTHER AREAS |
| OF HALLWAYS NOT SHOWN CONTAIN LESS LIGHTING FIXTURES IS |
| OF CONCERN TO THIS OFFICE. |
| |