Plan Review Notes For Permit 05120487 |
Permit Number |
05120487 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-07-18 00:00:00 | ***CORRECTIONS*** | | ***MAJOR WORKING DRAWING REVIEW*** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | NOTE - NO PLANS SUBMITTED ON FIRST | | REVIEW, REPORT ONLY. | | | | 1.)THE PRODUCT APPROVAL SUBMITTED | | FL6872 IS PENDING.CURRENT PRODUCT | | APPROVAL REQUIRED, FAC9B72.IF THE | | PRODUCT APPROVAL IS STILL PENDING AT THE | | TIME OF RESUBMITTAL, PLEASE ADVISE AND A | | LOCAL PRODUCT APPROVAL WILL BE ISSUED | | USING THE NOA. | | | | 2.)PROVIDE INFORMATION IN REGARDS TO | | THE EXISTING BUILDING - MINIMUM BUILDING | | TYPE FBC6 (INCLUDE A OR B), AREA, | | OCCUPANCY FBC3. | | | | 3.)RELATED TO COMMENT #2 ABOVE, | | SEVERAL DETAILS A7 SHOW COMBUSTIBLE | | FRAMING.IS THIS ALLOWED? | | | | 4.)DECLARE GOVERNING CODE, INCLUDING | | FBC 2004 EXISTING BUILDING CODE. | | | | 5.)DECLARE LEVEL OF ALTERATION, FBC EB | | 3. | | | | 6.)FS SHEETS ARE NOT SIGNED, SEALED | | AND DATED FAC61G15-23.002.THE | | INFORMATION REQUIRED TO BE ON THE TITLE | | BLOCK IS ILLEGIBLE. |
|