2006-06-30 00:00:00 | *****UNSAT ***** |
| 1ST REVIEW, ELECTRICAL PLANS NOW |
| SUBMITTED. |
| |
| |
| ** PLEASE KNOW, PLANS ARE STILL ONLY |
| BEING SUBMITTED FOR "PLAN REVIEW" AND |
| HAVE NOT SUBMITTED FOR PERMIT. |
| |
| |
| 1) NOTE: PLEASE SEE MISSING REQUIRED |
| INFORMATION ON TITLE BLOCK FOR THE |
| ARCHITECTURAL FIRM. FAC 61G1-16.004. |
| PLEASE SEE MISSING THE PRINTED NAME AND |
| LICENSE NUMBER OF ARCHITECT, AND MISSING |
| THE CERTIFICATE OF AUTHORIZATION NUMBER |
| FOR ARCHITECTURAL FIRM. |
| THIS IS REQUIRED ON ALL SHEETS |
| CONTAINING A TITLE BLOCK FOR SADI FIRM. |
| ** THIS IS REQUIRED FOR ALL TRADES AND |
| FOR REVIEW WHETHER OR NOT COMMENT IS |
| MADE BY OTHER TRADES. |
| |
| 2) NOTE: PLEASE SEE FS SHEETS SUBMITTED |
| ARE NOT SIGNED,DATED, OR SEALED?? |
| PLEASE KNOW, IF THESE ARE SUBMITTED AS |
| PART OF THIS SETS FOR RECORD, EVEN IF |
| THE FS ARE UNDER SEPARATE PERMIT, THE |
| SHEETS SHALL BE SIGNED, DATED, AND |
| SEALED. |
| FS 471.025, FAC 61G15-23.002 |
| |
| 3) NOTE: PLEASE KNOW, WHEN THIS IS BEING |
| SUBMITTED FOR PERMIT, THE COMPLETE VALUE |
| FOR SCOPE OF WORK SHALL INCLUDE ALL |
| LABOUR AND MATERIALS, WHETHER OR NOT ANY |
| MATERIALS ARE OWNER SUPPLIED. |
| FBC 108.3 ADMIN SECT. |
| |
| 4) NOTE: PLEASE SEE THAT CONDUCTOR TYPE |
| SHALL BE INDICATED. |
| 215.5, |
| 106.1.2 FBC ADMIN SECT. |
| |
| 5) NOTE: PLEASE PROVIDE PHOTO-METRICS |
| FOR HALL WAYS. THIS CAN BE A TYPICAL |
| DETAIL AND SECTION AS EACH FLR SEEMS |
| TYPICAL. |
| NFPA-101 7.8, 7.9 PLEASE SEE A MIN OF |
| 1FT CANDLE SHALL BE PROVIDED UNDER |
| NORMAL AND EMCONDITIONS. |
| |
| 6) NOTE: PLEASE SEE THAT NOW, EACH OF |
| THESE UNITS HAVE BECOME "CONDOS", THE |
| WASHER AND DRYER RECEPT CIRCUIT WIRING |
| SHALL NOT BE INCLUDE ON THESE PLANS FOR |
| SCOPE OF WORK. |
| THE CALCULATIONS FOR THE ADDED LOAD TO |
| EACH METER BACNK AND MAIN SERVICE SHOUDL |
| REMAIN IN SETS. |
| 215.5 |
| |
| 7) NOTE: PLEASE SEE PANEL LOCATIONS. |
| UNABLE TO VERIFY WHICH SIDE OF THE |
| PANELS SHOWN ARE THE ACCESSIBLE/OPENING |
| SIDE. THE OPEING SIDE SHOULD ALL MEET |
| 110.26 AND CORRELATE. |
| 215.5 |
| |
| 8) NOTE: PLEASE SEE THAT THE ADDRESS FOR |
| PROJECT SHALL BE INDICATED ON ALL |
| SHEETS. |
| FAC 61G1-16.004, FAC 61G15-23.002 |
| PLEASE SEE ONLY THE "A" SHEETS CONTAINS |
| AN ADDRESS OF 1830 EMBASSY DR. |
| |
| 9) NOTE: PLEASE SEE LOAD CALCULATIONS |
| WHICH REFLECT NEC 220.84?? |
| UNABLE TO LOCATED THIS REFERENCE IN THE |
| CURRENT WE ARE UNDER IN THE STATE OF |
| FLORIDA. |
| NEC 2002 |
| |
| 10) NOTE: PLEASE SEE THAT PLANS REFLECT |
| THE FOLLOWING CODES. |
| 2004 FBC, 2002 NFPA-70(NEC), 2002 |
| NFPA-72, 2003 NFPA-101 |
| |
| 11) NOTE: PLEASE CLARIFY WHERE MAIN 1OF6 |
| IS?? RISER SHOWS 2OF6, THRU 6OF6. |
| 215.5 |
| |
| 12) NOTE: PLEASE SEE WHEN RESUBMITTING |
| PLANS TO BE SURE AN MAKE TWO COMPLETE |
| SETS FOR REVIEW AND STAMPING. PLEASE SEE |
| SOME ELECTRICAL SHEETS WERE IN SEPARATE |
| SETS. |
| 106.1.3 |
| |
| 13) NOTE: PLEASE BE SURE TO ADJUST SCOPE |
| OF WORK ON APPLICATION AS THIS DOES NOT |
| INCLUDE ALL THE REFEEDS TO HOUSE PANELS, |
| "CONDO"PANELS AND METER BANKS. |
| PLEASE SEE APPL MENTIONS INSTALLATION OF |
| GFI RECEPTS, YET THESE COULD NOT BE |
| LOCATED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |