Plan Review Notes
Plan Review Notes For Permit 05120487
Permit Number 05120487
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-30 00:00:00*****UNSAT *****
 1ST REVIEW, ELECTRICAL PLANS NOW
 SUBMITTED.
  
  
 ** PLEASE KNOW, PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "PLAN REVIEW" AND
 HAVE NOT SUBMITTED FOR PERMIT.
  
  
 1) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK FOR THE
 ARCHITECTURAL FIRM. FAC 61G1-16.004.
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE NUMBER OF ARCHITECT, AND MISSING
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 FOR ARCHITECTURAL FIRM.
 THIS IS REQUIRED ON ALL SHEETS
 CONTAINING A TITLE BLOCK FOR SADI FIRM.
 ** THIS IS REQUIRED FOR ALL TRADES AND
 FOR REVIEW WHETHER OR NOT COMMENT IS
 MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE FS SHEETS SUBMITTED
 ARE NOT SIGNED,DATED, OR SEALED??
 PLEASE KNOW, IF THESE ARE SUBMITTED AS
 PART OF THIS SETS FOR RECORD, EVEN IF
 THE FS ARE UNDER SEPARATE PERMIT, THE
 SHEETS SHALL BE SIGNED, DATED, AND
 SEALED.
 FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE KNOW, WHEN THIS IS BEING
 SUBMITTED FOR PERMIT, THE COMPLETE VALUE
 FOR SCOPE OF WORK SHALL INCLUDE ALL
 LABOUR AND MATERIALS, WHETHER OR NOT ANY
 MATERIALS ARE OWNER SUPPLIED.
 FBC 108.3 ADMIN SECT.
  
 4) NOTE: PLEASE SEE THAT CONDUCTOR TYPE
 SHALL BE INDICATED.
 215.5,
 106.1.2 FBC ADMIN SECT.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRICS
 FOR HALL WAYS. THIS CAN BE A TYPICAL
 DETAIL AND SECTION AS EACH FLR SEEMS
 TYPICAL.
 NFPA-101 7.8, 7.9 PLEASE SEE A MIN OF
 1FT CANDLE SHALL BE PROVIDED UNDER
 NORMAL AND EMCONDITIONS.
  
 6) NOTE: PLEASE SEE THAT NOW, EACH OF
 THESE UNITS HAVE BECOME "CONDOS", THE
 WASHER AND DRYER RECEPT CIRCUIT WIRING
 SHALL NOT BE INCLUDE ON THESE PLANS FOR
 SCOPE OF WORK.
 THE CALCULATIONS FOR THE ADDED LOAD TO
 EACH METER BACNK AND MAIN SERVICE SHOUDL
 REMAIN IN SETS.
 215.5
  
 7) NOTE: PLEASE SEE PANEL LOCATIONS.
 UNABLE TO VERIFY WHICH SIDE OF THE
 PANELS SHOWN ARE THE ACCESSIBLE/OPENING
 SIDE. THE OPEING SIDE SHOULD ALL MEET
 110.26 AND CORRELATE.
 215.5
  
 8) NOTE: PLEASE SEE THAT THE ADDRESS FOR
 PROJECT SHALL BE INDICATED ON ALL
 SHEETS.
 FAC 61G1-16.004, FAC 61G15-23.002
 PLEASE SEE ONLY THE "A" SHEETS CONTAINS
 AN ADDRESS OF 1830 EMBASSY DR.
  
 9) NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH REFLECT NEC 220.84??
 UNABLE TO LOCATED THIS REFERENCE IN THE
 CURRENT WE ARE UNDER IN THE STATE OF
 FLORIDA.
 NEC 2002
  
 10) NOTE: PLEASE SEE THAT PLANS REFLECT
 THE FOLLOWING CODES.
 2004 FBC, 2002 NFPA-70(NEC), 2002
 NFPA-72, 2003 NFPA-101
  
 11) NOTE: PLEASE CLARIFY WHERE MAIN 1OF6
 IS?? RISER SHOWS 2OF6, THRU 6OF6.
 215.5
  
 12) NOTE: PLEASE SEE WHEN RESUBMITTING
 PLANS TO BE SURE AN MAKE TWO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE SEE
 SOME ELECTRICAL SHEETS WERE IN SEPARATE
 SETS.
 106.1.3
  
 13) NOTE: PLEASE BE SURE TO ADJUST SCOPE
 OF WORK ON APPLICATION AS THIS DOES NOT
 INCLUDE ALL THE REFEEDS TO HOUSE PANELS,
 "CONDO"PANELS AND METER BANKS.
 PLEASE SEE APPL MENTIONS INSTALLATION OF
 GFI RECEPTS, YET THESE COULD NOT BE
 LOCATED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  