Plan Review Notes
Plan Review Notes For Permit 05120487
Permit Number 05120487
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-27 00:00:00 
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
  
 1.)NO BUILDING PLANS SUBMITTED.
  
 2.)FOR PERMITTING PURPOSES, SUBMIT A
 DETAIL OF THE 1 HOUR INFILL IN THE
 CORRIDOR.PROVIDE A UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FBC7.
  
 3.)THE ENGINEER'S REPORT IS TO COMPLY
 WITH FAC61G15-23.002.THE COFA NUMBER,
 PRINTED LICENSE NUMBER OF THE PERSON
 SEALING THE DOCUMENT ARE TO BE ON THE
 PLAN.