Plan Review Notes
Plan Review Notes For Permit 05120430
Permit Number 05120430
Review Stop E
Sequence Number 4
Notes
Date Text
2006-03-31 00:00:00LOAD FOR AHU HEAT SHOULD HAVE BEEN
 FIGURED AT 100%, HOWEVER SHOWN AT 65%.
 EVEN IF FIGURED AT 100%, THE LOAD ON
 GENERATOR WOULD STILL BE IN DESIGNED
 LOAD.