2006-03-08 00:00:00 | ********** UNSAT 3RD REVIEW ************ |
| |
| ** PLEASE SEE THAT THE PREVIOUS DEINED |
| PLANS WERE NOT PICKED UP AND MADE INTO |
| TWO COMPLETE SETS BEFORE RESUBMITTING |
| PLANS. |
| PLEASE KNOW, MUST PICK UP ALL OLD PLANS |
| AND MAKE NEW SETS AND THEN RESUBMIT. |
| THIS WILL HELP TO ALLEAVIATE ANY |
| CONFUSION OF WHICH PLANS PASSED AND |
| WHERE THOSE PLANS ARE/WERE. |
| PLEASE SEE COMMENTS FROM OTHER REVIEW |
| WHICH IS NOW FAILED AS ORIGINAL PLANS |
| WERE NOT PICKED UP AND SUBMITTED BACK. |
| |
| ** PLEASE SEE NOTES BELOW AS MANY NOTES |
| ARE THE SAME AS NOTES ON PREVIOUS REVIEW |
| AND NEW NOTES AS RISER DIAGRAM HAS NOW |
| CHANGED.PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW. |
| |
| |
| |
| 1)NOTE: NOTE #1 NO, PLEASE SEE SHEETS |
| WHICH STILL CONTAIN TITLE BLOCK,SIGNED |
| AND DATED, HOWEVER THESE DO NOT CONTAIN |
| THE REQUIRED RAISED SEAL. |
| |
| **PLEASE SEE ANY PLANS CONTAINING |
| A TITLE BLOCK AND SIGNATURE OF AN |
| ENGINEER SHALL BEAR THE RAISED SEAL, AND |
| DATE BY THE SAID ENGINEER. FS471.025 |
| |
| 2)NOTE: NOTE #2 NO, PLEASE SEE SAME |
| SPECS WHICH DO NOT INDICATE A MCB. |
| |
| **PLEASE SEE SPECS SUBMITTED DO |
| NOT INDICATE THE USE OF AN ATS WITH A |
| MCB . PLEASE SEE MAINS ARE NOT GROUPED |
| PER 230.72,225.34 |
| |
| 3)NOTE: NOTE #3 NO, PLEAS SEE AN |
| EQUIPMENT GRND IS BEING SHOWN FROM METER |
| TO WHAT MAY BE THE FIRST MEANS OF |
| DISCONNECT ?(IF ATS CONTAINS A MCB?? |
| |
| ** PLEASE SEE 250.6,250.24 THE |
| "EQUIPMENT GROUNDING CONDUCTORS" ARE |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| PLEASE SEE RISER SHOWS FROM METER ETC. |
| 215.5 |
| |
| 4)NOTE: NOTE #4 NO, PLEASE SEE NEW SITE |
| PLANS IS NOT CLEAR AND VISABLE FOR |
| LOCATIONS OF EXISTING PANEL ETC. |
| PLEASE SEE NOW RISER HAS BEEN REVISED |
| REMOVING THE REQUIRED DISCONNECT?? |
| ONCE AGAIN, PLEASE KNOW, A DISCONNECT |
| WILL BE REQUIRED, GROUPED WITH OTHER |
| MAINS,AT THE HOUSE. |
| PLEASE CLARIFY RISER AS SHOWN. EXISTING |
| PANEL DOES NOT INDICATE A MCB AND |
| WHETHER OR NOT THS EXISTING PANEL(MCB?) |
| IS GROUPED WITH NEW ATS? |
| IT IS SUGGESTED TO CALL THIS OFFICE TO |
| GO OVER PLANS AND SCENERIO AS SHOWN TO |
| HELP ALLEAVIATE FURTHER REVIEWS. |
| |
| ** PLEASE SEE SITE PLANS DOES NOT |
| INDICATE THE NEW GEN DISCONNECT. |
| PLEASE SEE THE RISER SEEMS TO INDICATE |
| THE MEANS OF DISCONNECT REQUIRED IN |
| 225.31 AT GENERATOR? |
| PLEASE SEE IF GEN CONTAINS A CB , THEN |
| ONLY A DISCONNECTING MEANS IS REQUIRED |
| AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP |
| IS PERMITTED. |
| |
| 5)NOTE:NOTE #5, NO, PLEASE SEE NOTE |
| ABOVE BEFORE REVIEW NOTES AS TO PICKING |
| UP OF ANY OLD PLANS. |
| |
| **PLEASE SUBMIT TWO COMPLETE SETS |
| OF PLANS AND SPECS FOR REVIEW AND |
| STAMPING. |
| PLEASE SEE ALL SHEETS WERE SUBMITTED |
| LOOSELY AND NEED TO ATTACHED TOGETHER. |
| |
| 6)NOTE: NOTE #6 NO, COULD NOT LOCATE A |
| NEW RECORDED NOC? PLEASE KNOW, THIS NEED |
| ONLY BE SUBMITTED WHEN PICKING UP PERMIT |
| ONCE IT IS ISSUED. |
| |
| ** PLEASE SEE THE NOTICE OF |
| COMMENCMENT HAS SINCE EXPIRED PER FS |
| 713.13(2). IF WORK HAS NOT COMMENCED |
| WITHIN 90 DAYS OF RECORDING NOC, THE NOC |
| SHALL BECOME VOID. |
| |
| NEW COMMENT; |
| |
| 7)NOTE: PLEASE SEE FLORIDA STATUES |
| 553.80(2))B) WITH RESPECT TO DESIGN |
| PROFESSIONALS AND REPEAT COMMENTS FOR |
| PLANS REVIEW. PLEASE KNOW, IF PLANS COME |
| BACK WITH ANY OF THE SAME CODE COMPLIANT |
| COMMENTS STILL NOT ADDRESSED, THIS |
| OFFICE SHALL ACCESSED A 4X FEE FOR THE |
| PLAN REVIEW PORTION OF THE PERMIT FEE. |
| SEEATTACHED COPY OF THIS FS. |
| |
| |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |