Plan Review Notes
Plan Review Notes For Permit 05120430
Permit Number 05120430
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-08 00:00:00********** UNSAT 3RD REVIEW ************
  
 ** PLEASE SEE THAT THE PREVIOUS DEINED
 PLANS WERE NOT PICKED UP AND MADE INTO
 TWO COMPLETE SETS BEFORE RESUBMITTING
 PLANS.
 PLEASE KNOW, MUST PICK UP ALL OLD PLANS
 AND MAKE NEW SETS AND THEN RESUBMIT.
 THIS WILL HELP TO ALLEAVIATE ANY
 CONFUSION OF WHICH PLANS PASSED AND
 WHERE THOSE PLANS ARE/WERE.
 PLEASE SEE COMMENTS FROM OTHER REVIEW
 WHICH IS NOW FAILED AS ORIGINAL PLANS
 WERE NOT PICKED UP AND SUBMITTED BACK.
  
 ** PLEASE SEE NOTES BELOW AS MANY NOTES
 ARE THE SAME AS NOTES ON PREVIOUS REVIEW
 AND NEW NOTES AS RISER DIAGRAM HAS NOW
 CHANGED.PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE SHEETS
 WHICH STILL CONTAIN TITLE BLOCK,SIGNED
 AND DATED, HOWEVER THESE DO NOT CONTAIN
 THE REQUIRED RAISED SEAL.
  
 **PLEASE SEE ANY PLANS CONTAINING
 A TITLE BLOCK AND SIGNATURE OF AN
 ENGINEER SHALL BEAR THE RAISED SEAL, AND
 DATE BY THE SAID ENGINEER. FS471.025
  
 2)NOTE: NOTE #2 NO, PLEASE SEE SAME
 SPECS WHICH DO NOT INDICATE A MCB.
  
 **PLEASE SEE SPECS SUBMITTED DO
 NOT INDICATE THE USE OF AN ATS WITH A
 MCB . PLEASE SEE MAINS ARE NOT GROUPED
 PER 230.72,225.34
  
 3)NOTE: NOTE #3 NO, PLEAS SEE AN
 EQUIPMENT GRND IS BEING SHOWN FROM METER
 TO WHAT MAY BE THE FIRST MEANS OF
 DISCONNECT ?(IF ATS CONTAINS A MCB??
  
 ** PLEASE SEE 250.6,250.24 THE
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE RISER SHOWS FROM METER ETC.
 215.5
  
 4)NOTE: NOTE #4 NO, PLEASE SEE NEW SITE
 PLANS IS NOT CLEAR AND VISABLE FOR
 LOCATIONS OF EXISTING PANEL ETC.
 PLEASE SEE NOW RISER HAS BEEN REVISED
 REMOVING THE REQUIRED DISCONNECT??
 ONCE AGAIN, PLEASE KNOW, A DISCONNECT
 WILL BE REQUIRED, GROUPED WITH OTHER
 MAINS,AT THE HOUSE.
 PLEASE CLARIFY RISER AS SHOWN. EXISTING
 PANEL DOES NOT INDICATE A MCB AND
 WHETHER OR NOT THS EXISTING PANEL(MCB?)
 IS GROUPED WITH NEW ATS?
 IT IS SUGGESTED TO CALL THIS OFFICE TO
 GO OVER PLANS AND SCENERIO AS SHOWN TO
 HELP ALLEAVIATE FURTHER REVIEWS.
  
 ** PLEASE SEE SITE PLANS DOES NOT
 INDICATE THE NEW GEN DISCONNECT.
 PLEASE SEE THE RISER SEEMS TO INDICATE
 THE MEANS OF DISCONNECT REQUIRED IN
 225.31 AT GENERATOR?
 PLEASE SEE IF GEN CONTAINS A CB , THEN
 ONLY A DISCONNECTING MEANS IS REQUIRED
 AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP
 IS PERMITTED.
  
 5)NOTE:NOTE #5, NO, PLEASE SEE NOTE
 ABOVE BEFORE REVIEW NOTES AS TO PICKING
 UP OF ANY OLD PLANS.
  
 **PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS AND SPECS FOR REVIEW AND
 STAMPING.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NEED TO ATTACHED TOGETHER.
  
 6)NOTE: NOTE #6 NO, COULD NOT LOCATE A
 NEW RECORDED NOC? PLEASE KNOW, THIS NEED
 ONLY BE SUBMITTED WHEN PICKING UP PERMIT
 ONCE IT IS ISSUED.
  
 ** PLEASE SEE THE NOTICE OF
 COMMENCMENT HAS SINCE EXPIRED PER FS
 713.13(2). IF WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING NOC, THE NOC
 SHALL BECOME VOID.
  
 NEW COMMENT;
  
 7)NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2))B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 PLANS REVIEW. PLEASE KNOW, IF PLANS COME
 BACK WITH ANY OF THE SAME CODE COMPLIANT
 COMMENTS STILL NOT ADDRESSED, THIS
 OFFICE SHALL ACCESSED A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE.
 SEEATTACHED COPY OF THIS FS.
  
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]