Date |
Text |
2006-02-10 00:00:00 | ********** UNSAT************ |
| |
| |
| 1)NOTE: PLEASE SEE ANY PLANS CONTAINING |
| A TITLE BLOCK AND SIGNATURE OF AN |
| ENGINEER SHALL BEAR THE RAISED SEAL, AND |
| DATE BY THE SAID ENGINEER. FS471.025 |
| |
| 2)NOTE: PLEASE SEE SPECS SUBMITTED DO |
| NOT INDICATE THE USE OF AN ATS WITH A |
| MCB . PLEASE SEE MAINS ARE NOT GROUPED |
| PER 230.72,225.34 |
| |
| 3)NOTE: PLEASE SEE 250.6,250.24 THE |
| "EQUIPMENT GROUNDING CONDUCTORS" ARE |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| PLEASE SEE RISER SHOWS FROM METER ETC. |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE SITE PLANS DOES NOT |
| INDOCATE THE NEW GEN DISCONNECT. |
| PLEASE SEE THE RISER SEEMS TO INDICATE |
| THE MEANS OF DISCONNECT REQUIRED IN |
| 225.31 AT GENERATOR? |
| PLEASE SEE IF GEN CONTAINS A CB , THEN |
| ONLY A DISCONNECTING MEANS IS REQUIRED |
| AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP |
| IS PERMITTED. |
| |
| 5)NOTE: PLEASE SUBMIT TWO COMPLETE SETS |
| OF PLANS AND SPECS FOR REVIEW AND |
| STAMPING. |
| PLEASE SEE ALL SHEETS WERE SUBMITTED |
| LOOSELY AND NEED TO ATTACHED TOGETHER. |
| |
| 6)NOTE: PLEASE SEE THE NOTICE OF |
| COMMENCMENT HAS SINCE EXPIRED PER FS |
| 713.13(2). IF WORK HAS NOT COMMENCED |
| WITHIN 90 DAYS OF RECORDING NOC, THE NOC |
| SHALL BECOME VOID. |
| |
| |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |