2006-02-10 00:00:00********** UNSAT************
  
  
 1)NOTE: PLEASE SEE ANY PLANS CONTAINING
 A TITLE BLOCK AND SIGNATURE OF AN
 ENGINEER SHALL BEAR THE RAISED SEAL, AND
 DATE BY THE SAID ENGINEER. FS471.025
  
 2)NOTE: PLEASE SEE SPECS SUBMITTED DO
 NOT INDICATE THE USE OF AN ATS WITH A
 MCB . PLEASE SEE MAINS ARE NOT GROUPED
 PER 230.72,225.34
  
 3)NOTE: PLEASE SEE 250.6,250.24 THE
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE RISER SHOWS FROM METER ETC.
 215.5
  
 4)NOTE: PLEASE SEE SITE PLANS DOES NOT
 INDOCATE THE NEW GEN DISCONNECT.
 PLEASE SEE THE RISER SEEMS TO INDICATE
 THE MEANS OF DISCONNECT REQUIRED IN
 225.31 AT GENERATOR?
 PLEASE SEE IF GEN CONTAINS A CB , THEN
 ONLY A DISCONNECTING MEANS IS REQUIRED
 AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP
 IS PERMITTED.
  
 5)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS AND SPECS FOR REVIEW AND
 STAMPING.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NEED TO ATTACHED TOGETHER.
  
 6)NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT HAS SINCE EXPIRED PER FS
 713.13(2). IF WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING NOC, THE NOC
 SHALL BECOME VOID.
  
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION