2005-12-28 00:00:00 | ************UNSAT ************ |
| |
| |
| 1)NOTE: PLEASE SEE FBC ADMINISTRATIVE |
| CODE 108.3, VALUTAION IS TO BE BASED ON |
| ALL LABOR AND MATERIALS, WHETHER OR NOT |
| ANY MATERIALS/ EQUIPMENT IS OWNER |
| SUPPLIED. |
| THE $3680, IS WAY TOO LOW. |
| |
| 2)NOTE: PLEASE PROVIDE A MEANS OF |
| DISCONNECT GROUPED WITH OTHER MAINS AS |
| REQUIRED PER 225.31-225.39 |
| PLEASE SEE NEW TRANSFER SWITCH AS |
| SUBMITTED WILL ONLY DISCONNECT POWER |
| FROM UITILITY AND NOT GENERATOR. PLEASE |
| SEE THE REQUIRED DISC SHALL BE RATED FOR |
| THE LOAD TO BE SERVED. (A TOGGLE SWITCH |
| IS NOT ACCEPTABLE). |
| |
| |
| 3)NOTE: PLEASE ALSO SEE THAT ONLY THE |
| NORMAL GENERAL LT, RECEPTS LOADS MAY BE |
| DE-RATED. ALL OTHER MOTOR, HEAT, |
| SPECIFIC APPLIANCE LOADS SHALL BE |
| FIGURED AT 100%, INCLUDING HEAT LOADS IN |
| A/C UNITS, UNLESS A MEANS OF SHEDDING |
| THESE LOADS IS PROVIDED. |
| 220, 702.5,90.4 |
| |
| 4)NOTE: PLEASE VERIFY THE EXISTING |
| METER/MAIN IS SHOWN AS 150A, YET ALL NEW |
| EQUIPEMNT IS 200A AND EXISTING PANEL IN |
| GARAGE DOES NOT INDICATE ANY SIZE?? |
| 215.5 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |