Date |
Text |
2006-02-14 00:00:00 | |
| PLUMBING PLAN REVIEW EXAMINER |
| PAUL SCHMITZ 561-805-6692 |
| [email protected] |
| FBC PLUMBING 2004 |
| FBC FUEL GAS 2004 |
| FBC 2004 BUILDING CH 11 |
| DENIED |
| 1)SHT A-1 BREAK ROOM SINKS |
| 11-4.24.1 GENERAL. |
| SINKS REQUIRED TO BE ACCESSIBLE BY |
| SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| 11-4.24. |
| 11-4.24.3 KNEE CLEARANCE. |
| KNEE CLEARANCE THAT IS AT LEAST 27 |
| INCHES (685 MM) HIGH, 30 INCHES (760 MM) |
| WIDE, AND 19 INCHES (485 MM) DEEP SHALL |
| BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.4 DEPTH. |
| EACH SINK SHALL BE A MAXIMUM OF 61/2 |
| INCHES (165 MM) DEEP. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES |
| BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| PROVIDED IN FRONT OF A SINK TO ALLOW |
| FORWARD APPROACH. THE CLEAR FLOOR SPACE |
| SHALL BE ON AN ACCESSIBLE ROUTE AND |
| SHALL EXTEND A MAXIMUM OF 19 INCHES (485 |
| MM) UNDERNEATH THE SINK (SEE FIGURE |
| 11-32). |
| 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| HOT WATER AND DRAIN PIPES EXPOSED UNDER |
| SINKS SHALL BE INSULATED OR OTHERWISE |
| CONFIGURED SO AS TO PROTECT AGAINST |
| CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER SINKS. |
| 11-4.24.7 FAUCETS. |
| FAUCETS SHALL COMPLY WITH SECTION |
| 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, |
| TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED |
| MECHANISMS ARE ACCEPTABLE DESIGNS. |
| |
| 2)SHT P1.01 TOILET ROOM SHOWER. |
| 11-4.21.1 GENERAL. |
| ACCESSIBLE SHOWER STALLS SHALL COMPLY |
| WITH SECTION 11-4.21. |
| 11-4.21.2 SIZE AND CLEARANCES. |
| EXCEPT AS SPECIFIED IN SECTION 11-9.1.2, |
| SHOWER STALL SIZE AND CLEAR FLOOR SPACE |
| SHALL COMPLY WITH FIGURE 11-35(A) OR |
| FIGURE 11-35(B). THE SHOWER STALL IN |
| FIGURE 11-35(A) SHALL BE 36 INCHES BY 36 |
| INCHES (915 MM BY 915 MM). |
| 11-4.21.3 SEAT. |
| A SEAT SHALL BE PROVIDED IN SHOWER |
| STALLS 36 INCHES BY 36 INCHES (915 MM BY |
| 915 MM) AND SHALL BE AS SHOWN IN FIGURE |
| 11-36. THE SEAT SHALL BE MOUNTED 17 |
| INCHES TO 19 INCHES (430 MM TO 485 MM) |
| FROM THE BATHROOM FLOOR AND SHALL EXTEND |
| THE FULL DEPTH OF THE STALL. IN A |
| 36-INCH BY 36-INCH (915 MM BY 915 MM) |
| SHOWER STALL, THE SEAT SHALL BE ON THE |
| WALL OPPOSITE THE CONTROLS. IT SHALL BE |
| A FOLDING TYPE AND SHALL BE MOUNTED ON |
| THE WALL ADJACENT TO THE CONTROLS AS |
| SHOWN IN FIGURE 11-57. THE STRUCTURAL |
| STRENGTH OF SEATS AND THEIR ATTACHMENTS |
| SHALL COMPLY WITH SECTION 11-4.26.3. |
| 11-4.21.4 GRAB BARS. |
| GRAB BARS COMPLYING WITH SECTION 11-4.26 |
| SHALL BE PROVIDED AS SHOWN IN FIGURE |
| 11-37. |
| 11-4.21.5 CONTROLS. |
| FAUCETS AND OTHER CONTROLS COMPLYING |
| WITH SECTION 11-4.27.4 SHALL BE LOCATED |
| AS SHOWN IN FIGURE 11-37. IN SHOWER |
| STALLS 36 INCHES BY 36 INCHES (915 MM BY |
| 915 MM), ALL CONTROLS, FAUCETS, AND THE |
| SHOWER UNIT SHALL BE MOUNTED ON THE SIDE |
| WALL OPPOSITE THE SEAT. |
| 11-4.21.6 SHOWER UNIT. |
| A SHOWER SPRAY UNIT WITH A HOSE AT LEAST |
| 60 INCHES (1525 MM) LONG THAT CAN BE |
| USED BOTH AS A FIXED SHOWER HEAD AND AS |
| A HAND-HELD SHOWER SHALL BE PROVIDED. |
| 11-4.21.7 CURBS. |
| IF PROVIDED, CURBS IN SHOWER STALLS 36 |
| INCHES BY 36 INCHES (915 MM BY 915 MM) |
| SHALL BE NO HIGHER THAN ? INCH (13 MM). |
| SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| INCHES (760 MM BY 1525 MM) MINIMUM SHALL |
| NOT HAVE CURBS. |
| 11-4.21.8 SHOWER ENCLOSURES. |
| IF PROVIDED, ENCLOSURES FOR SHOWER |
| STALLS SHALL NOT OBSTRUCT CONTROLS OR |
| OBSTRUCT TRANSFER FROM WHEELCHAIRS ONTO |
| SHOWER SEATS. |
| |
| 3) SHT P-1.01 |
| CORRELATE DWV ISOMETRIC, WITH PLUMBING |
| FIXTURE LAY OUT, MOP SINK SHOWN ON |
| ISOMETRIC? |
| |
| 4)SHT P1.01 WATER HEATER,PROVIDE DETAIL |
| 607.3 THERMAL EXPANSION CONTROL. |
| A MEANS OF CONTROLLING INCREASED |
| PRESSURE CAUSED BY THERMAL EXPANSION |
| SHALL BE PROVIDED WHERE REQUIRED IN |
| ACCORDANCE WITH SECTIONS 607.3.1 AND |
| 607.3.2. |
| 607.3.1 PRESSURE-REDUCING VALVE. |
| FOR WATER SERVICE SYSTEM SIZES UP TO AND |
| INCLUDING 2 INCHES (51 MM), A DEVICE FOR |
| CONTROLLING PRESSURE SHALL BE INSTALLED |
| WHERE, BECAUSE OF THERMAL EXPANSION, THE |
| PRESSURE ON THE DOWNSTREAM SIDE OF A |
| PRESSURE-REDUCING VALVE EXCEEDS THE |
| PRESSURE-REDUCING VALVE SETTING. |
| END OF COMMENTS, QUESTIONS 561-805-6692 |