Date Text
2006-02-14 00:00:00 
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1)SHT A-1 BREAK ROOM SINKS
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 2)SHT P1.01 TOILET ROOM SHOWER.
 11-4.21.1 GENERAL.
 ACCESSIBLE SHOWER STALLS SHALL COMPLY
 WITH SECTION 11-4.21.
 11-4.21.2 SIZE AND CLEARANCES.
 EXCEPT AS SPECIFIED IN SECTION 11-9.1.2,
 SHOWER STALL SIZE AND CLEAR FLOOR SPACE
 SHALL COMPLY WITH FIGURE 11-35(A) OR
 FIGURE 11-35(B). THE SHOWER STALL IN
 FIGURE 11-35(A) SHALL BE 36 INCHES BY 36
 INCHES (915 MM BY 915 MM).
 11-4.21.3 SEAT.
 A SEAT SHALL BE PROVIDED IN SHOWER
 STALLS 36 INCHES BY 36 INCHES (915 MM BY
 915 MM) AND SHALL BE AS SHOWN IN FIGURE
 11-36. THE SEAT SHALL BE MOUNTED 17
 INCHES TO 19 INCHES (430 MM TO 485 MM)
 FROM THE BATHROOM FLOOR AND SHALL EXTEND
 THE FULL DEPTH OF THE STALL. IN A
 36-INCH BY 36-INCH (915 MM BY 915 MM)
 SHOWER STALL, THE SEAT SHALL BE ON THE
 WALL OPPOSITE THE CONTROLS. IT SHALL BE
 A FOLDING TYPE AND SHALL BE MOUNTED ON
 THE WALL ADJACENT TO THE CONTROLS AS
 SHOWN IN FIGURE 11-57. THE STRUCTURAL
 STRENGTH OF SEATS AND THEIR ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3.
 11-4.21.4 GRAB BARS.
 GRAB BARS COMPLYING WITH SECTION 11-4.26
 SHALL BE PROVIDED AS SHOWN IN FIGURE
 11-37.
 11-4.21.5 CONTROLS.
 FAUCETS AND OTHER CONTROLS COMPLYING
 WITH SECTION 11-4.27.4 SHALL BE LOCATED
 AS SHOWN IN FIGURE 11-37. IN SHOWER
 STALLS 36 INCHES BY 36 INCHES (915 MM BY
 915 MM), ALL CONTROLS, FAUCETS, AND THE
 SHOWER UNIT SHALL BE MOUNTED ON THE SIDE
 WALL OPPOSITE THE SEAT.
 11-4.21.6 SHOWER UNIT.
 A SHOWER SPRAY UNIT WITH A HOSE AT LEAST
 60 INCHES (1525 MM) LONG THAT CAN BE
 USED BOTH AS A FIXED SHOWER HEAD AND AS
 A HAND-HELD SHOWER SHALL BE PROVIDED.
 11-4.21.7 CURBS.
 IF PROVIDED, CURBS IN SHOWER STALLS 36
 INCHES BY 36 INCHES (915 MM BY 915 MM)
 SHALL BE NO HIGHER THAN ? INCH (13 MM).
 SHOWER STALLS THAT ARE 30 INCHES BY 60
 INCHES (760 MM BY 1525 MM) MINIMUM SHALL
 NOT HAVE CURBS.
 11-4.21.8 SHOWER ENCLOSURES.
 IF PROVIDED, ENCLOSURES FOR SHOWER
 STALLS SHALL NOT OBSTRUCT CONTROLS OR
 OBSTRUCT TRANSFER FROM WHEELCHAIRS ONTO
 SHOWER SEATS.
  
 3) SHT P-1.01
 CORRELATE DWV ISOMETRIC, WITH PLUMBING
 FIXTURE LAY OUT, MOP SINK SHOWN ON
 ISOMETRIC?
  
 4)SHT P1.01 WATER HEATER,PROVIDE DETAIL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.1 PRESSURE-REDUCING VALVE.
 FOR WATER SERVICE SYSTEM SIZES UP TO AND
 INCLUDING 2 INCHES (51 MM), A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED
 WHERE, BECAUSE OF THERMAL EXPANSION, THE
 PRESSURE ON THE DOWNSTREAM SIDE OF A
 PRESSURE-REDUCING VALVE EXCEEDS THE
 PRESSURE-REDUCING VALVE SETTING.
 END OF COMMENTS, QUESTIONS 561-805-6692