2006-01-10 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PLANS SHOULD REFLECT
 THE CURRENT NFPA-70,72,101 ETC IN
 EFFECT.
 2002,2002,2003
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS THE PRINTED LICENSE # IS ALSO
 REQUIRED FOR ALL SHEETS DONE BY TF
 KENNEDY.
 FAC 61G15-23.002
  
 3)NOTE: PLEASE EITHER MOVE WATER HEATER
 OR PROVIDE PERMANANT CONSTRUCTION
 BARRIER FROM COMBUSTIBLES/EASILY
 IGNITIBLE MATERIALS.422.17 .
  
 4)NOTE: PLEASE VERIFY NEW OR EXISTING
 REQUIRED SIGN CIRCUIT.
 600.5
  
 5)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 220.10,220.11,220.13,215.3,230.42 ETC.
  
 6)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE THE FOOTER/BLDG STEEL TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE VERIFY AS THIS SEEMS TO BE AN
 EXISTING BLDG AND THE FOOTER STEEL WOULD
 NOT BE REQUIRED. IT IS PERMITTED ,
 HOWEVER NOT REQUIRED FOR EXISTING BLDGS.
 TWO GRND RODS WOULD BE REQUIRED.
 250.50
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  