Plan Review Notes For Permit 05120334 |
Permit Number |
05120334 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-28 00:00:00 | *********** UNSAT ********** | | | | 1)NOTE: PLEASE SEE MISSING REQUIRED | | INFORMATION REQUIRED ON TITLE BLOCK AS | | REQUIRED UNDER FAC 61G15-23.002 AND FS | | 471.023. | | | | 2)NOTE: PLEASE INCLUDE A MIN OF 2-GRNDS | | RODS AND CWP AS PART OF THE GROUNDING | | ELECTRODE SYSTEM.250.50 | | TECHNICAL CODES MAY NOT BE QUOTED IN | | LEIU OF DETAILS ON PLANS. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 4)NOTE: PLEASE COMPLETE FEEDERS TO | | INTERIOR PANEL. | | PLEASE SEE CONDUCTORS ONLY SHOWN AS | | #1'S? HOW MANY #1'S, NEUTRALAND | | MISSING EQUIPMENT GROUNDING CONDUCTOR | | PER 250.110,250.24,250.122 | | 215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|