2006-01-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- ACCORDING TO FLORIDA STATUTES CHAPTER |
| 713 THE NOTICE OF COMMENCEMENT IS |
| EXPIRED AFTER 90 DAYS IF WORK IS NOT |
| COMMENCED. SEE ATTACHED COPY. |
| NEED TO PROVIDE RE-RECORDED NOTICE OF |
| COMMENCEMENT. |
| |
| 2- BEDROOM WINDOWS NEED TO PROVIDE 24" |
| MIN. CLEAR HEIGHT OPENING, 20" MIN. |
| CLEAR WIDTH OPENING AND 5 SQUARE FEET |
| MIN. TOTAL CLEAR OPENING AS REQUIRED BY |
| SEC. R310.1 RESIDENTAIL FBC 2004. |
| |
| ***NOTE: REPLACEMENT OF WINDOW MAY BE |
| REDUCED 5 PERCENT IN THE CLEAR OPENINGS |
| DIMENSIONS. SEE SEC. 505 OF EXISTING |
| BUILDING FBC 2004. PROVIDE WINDOWS CUT |
| SHEETS TO SEE IF THEY MIGHT BE ACCEPTED |
| USING THIS REDUCTION. |
| |
| ***SPECIFY DIMENSIONS OF WINDOWS TO BE |
| INSTALLED SINCE SOME OPENINGS WILL HAVE |
| 2 WINDOWS MULLED TOGETHER TO VERIFY |
| CLEAR OPENINGS FOR EGRESS. |
| |
| 3- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR WINDOWS AND WINDOW |
| MULLIONS. DADE COUNTY NOA ALONE IS NOT |
| AUTOMATICALLY AN STATEWIDE FLORIDA |
| PRODUCT APPROVAL. GO TO THE WEBSITE |
| WWW.FLORIDABUILDING.ORG TO SEE IF THE |
| MANUFACTURER HAS THE FLORIDA PRODUCT |
| APPROVAL. THEN, PROVIDE FLORIDA COVER |
| PAGE AND THE NOA THAT WAS SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. |
| |