2006-01-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- ACCORDING TO FLORIDA STATUTES CHAPTER
 713 THE NOTICE OF COMMENCEMENT IS
 EXPIRED AFTER 90 DAYS IF WORK IS NOT
 COMMENCED. SEE ATTACHED COPY.
 NEED TO PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 2- BEDROOM WINDOWS NEED TO PROVIDE 24"
 MIN. CLEAR HEIGHT OPENING, 20" MIN.
 CLEAR WIDTH OPENING AND 5 SQUARE FEET
 MIN. TOTAL CLEAR OPENING AS REQUIRED BY
 SEC. R310.1 RESIDENTAIL FBC 2004.
  
 ***NOTE: REPLACEMENT OF WINDOW MAY BE
 REDUCED 5 PERCENT IN THE CLEAR OPENINGS
 DIMENSIONS. SEE SEC. 505 OF EXISTING
 BUILDING FBC 2004. PROVIDE WINDOWS CUT
 SHEETS TO SEE IF THEY MIGHT BE ACCEPTED
 USING THIS REDUCTION.
  
 ***SPECIFY DIMENSIONS OF WINDOWS TO BE
 INSTALLED SINCE SOME OPENINGS WILL HAVE
 2 WINDOWS MULLED TOGETHER TO VERIFY
 CLEAR OPENINGS FOR EGRESS.
  
 3- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR WINDOWS AND WINDOW
 MULLIONS. DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE FLORIDA
 PRODUCT APPROVAL. GO TO THE WEBSITE
 WWW.FLORIDABUILDING.ORG TO SEE IF THE
 MANUFACTURER HAS THE FLORIDA PRODUCT
 APPROVAL. THEN, PROVIDE FLORIDA COVER
 PAGE AND THE NOA THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712